In a dead tank breaker the interrupter sits inside a tank that is bolted to earth, so the current transformers can be built into the bushings and the whole three-pole assembly shares one frame, one CT26 spring mechanism and one three-phase linkage. The LW36-126 weighs 2200 kg as a complete unit and stands 4096 mm tall, which is a compact answer for a substation that wants the CTs inside the breaker rather than on separate posts. In a live tank breaker the interrupter is carried on a porcelain pillar at line potential with no earthed enclosure around it, so it is lighter per pole and easier to erect, but the current transformers have to be post-type and mounted outside. The LW36-145 is 1800 kg for the same 3150 A and 40 kA as its dead tank sibling. At 252 kV the trade goes further: the LW□-252 stands each pole on its own galvanised support with its own mechanism cabinet, 1500 kg per pole and 4500 kg for three, coupled electrically rather than by a single linkage. Neither arrangement is better in the abstract; one puts the CTs inside the footprint, the other keeps the lifted weight down.
The range covers 72.5, 126, 145 and 252 kV, which is the 72.5 to 245 kV band a transmission substation is usually built in, with the 145 kV unit offered at 50 or 60 Hz. Breaking current steps 31.5 kA at 72.5 kV, 40 kA at 126 and 145, and 50 kA at 252 kV where the rated current also rises from 3150 A to 4000 A. Insulation follows the class: 160/350 kV power-frequency and impulse at 72.5 kV to earth, 230/550 at 126, 275/650 at 145 and 460/1050 at 252, with the across-the-break figures higher in every case because the open gap has to hold the recovery voltage. At 252 kV the standard states that gap as an addition rather than a single number, 460 plus 146 kV, and a buyer reading only the to-earth column will under-specify the interrupter.
Every unit here is filled to 0.5 MPa gauge at 20 °C, except the 252 kV breaker at 0.6 MPa, and every one has two thresholds above atmospheric: an alarm that tells the control room to plan a top-up, at 0.45 MPa ±0.03 on the three smaller units and 0.55 MPa ±0.015 at 252 kV, and a minimum functional pressure the interrupter can still break at. Between those two pressures the breaker is expected to work, which is why the alarm is a maintenance signal rather than a trip. The figure worth quoting in a specification is the zero-gauge withstand: 84 kV at 72.5 kV and 95 kV at 126 and 145 kV for five minutes with no gas pressure at all. That is a dielectric guarantee about the solid insulation, not about the interrupter, and it is what allows a bay to be worked on after the gas has been recovered. Leakage is held to 0.5% of the fill per year and moisture to 150 ppm, because water in SF6 is what turns a healthy breaker into an internal flashover.
Mechanical endurance is 10000 operations on all four breakers, and the 72.5 kV unit also publishes an electrical life: 24 operations at 31.5 kA, or 31 at 25 kA. The gap between those two numbers is the whole economics of a breaker. A spring mechanism that closes and opens 10000 times is a mechanism doing no electrical work; the contacts and the gas are what wear when the current is interrupted, and at full breaking current they are good for a couple of dozen operations before the nozzle and the contact tips are consumed. That is why the electrical life is quoted against a current, never as a single number, and why a breaker applied to a capacitor bank or a frequently switched reactor runs out of life long before its mechanism does.
A short-circuit rating says nothing about the four other duties a transmission breaker is asked to perform. Out-of-phase breaking is 8 kA at 72.5 kV, 10 kA at 126 and 145, and 12.5 kA at 252 — the current that flows when two systems drift apart and the breaker has to separate them. Line-charging current runs from 10 A on the smallest unit to 31.5 A on the 126 and 145 kV breakers and 200 A at 252 kV, and it is the duty that punishes a breaker with restrikes rather than with contact wear. Close-in fault breaking is 90% of the rated short-circuit current for a fault at the terminals and 75% for a fault one line span away, and the first-pole-to-clear factor is 1.5 everywhere except the 252 kV unit, which is 1.3. All four come with the same operating sequence, O-0.3s-CO-180s-CO, meaning one trip, a 0.3 second dead time for the auto-reclose, a close-open, then 180 seconds before the next close-open.
Six items settle a quotation. The system voltage and the highest system voltage the substation is designed for. The prospective short-circuit current, and the duration the upstream protection needs, since the short-time rating here is 4 s and 3 s at 252 kV. The continuous current, 3150 A or 4000 A, and whether the current transformers have to be built into the breaker. The pollution level and the creepage it implies, 2248 mm to earth at 72.5 kV against 6900 mm at 252 kV, because all four are quoted at pollution level IV. The ambient range and altitude: −40 to +40 °C on the 72.5 to 145 kV units and −30 °C at the cold end of the 252 kV one, with a 2000 m altitude limit published for that breaker. And the seismic or wind load, given that the 252 kV poles present 2500 kg horizontally and 6000 kg downwards to their foundations.
Dead tank puts the interrupter in a tank bolted to earth, so the current transformers sit in the bushings and the three poles share one frame and one spring mechanism; LW36-126 is 2200 kg and 4096 mm tall as a whole unit. Live tank carries the interrupter on a porcelain pillar and is the usual choice where CTs stay on separate posts.
31.5 kA at 72.5 kV, 40 kA at 126 and 145 kV, and 50 kA at 252 kV, where the rated current also rises from 3150 A to 4000 A. Insulation steps with the class: 160/350 kV at 72.5 kV, 230/550 at 126, 275/650 at 145 and 460/1050 at 252.
No. Fill pressure is 0.5 MPa gauge at 20 °C, or 0.6 MPa at 252 kV. The alarm at 0.45 ±0.03 MPa (0.55 ±0.015 at 252 kV) is a maintenance signal: the breaker is still expected to break between the alarm and the minimum functional pressure.
Mechanical endurance is 10,000 operations on all four. That figure is the mechanism, not the contacts: the 72.5 kV unit publishes 24 operations of electrical life at 31.5 kA, or 31 at 25 kA.
Out-of-phase breaking (8 kA at 72.5 kV, 10 kA at 126 and 145, 12.5 kA at 252), line-charging current from 10 A to 200 A, and close-in fault breaking. The short-time rating is 4 s, 3 s at 252 kV — state both the fault level and the clearing time with an enquiry.