Home/ Products/ SF6 Circuit Breakers/ LW36-126T3150-40

126kV SF6 Dead Tank Circuit Breaker

126 kV · Outdoor installation · SF6, single-break dead tank

LW36-126T 126 kV SF6 dead tank circuit breaker, three poles on a common frame
Outdoor SF6 Dead Tank Breaker

Overview

The LW36-126T3150-40 is an outdoor dead tank SF6 circuit breaker rated 126 kV, 3150 A and 40 kA. Each pole carries a single-break interrupter mounted horizontally inside a grounded aluminium alloy tank, and the three tanks share one common frame driven by a single CT26 spring mechanism through a three-phase linkage. Because the enclosure sits at earth potential, current transformers are built into the same tank as bushing type cores, so a 110 kV breaker bay and its CTs occupy one foundation instead of two.

SF6 gas does both jobs: arc quenching and insulation. Rated gauge pressure is 0.5 MPa at 20 °C, the guaranteed annual leakage rate is 0.5 percent or less, and a density relay with alarm and lockout contacts watches the gas. Creepage is 3906 mm between interrupters and 3150 mm to earth, above 31 mm per kV, which keeps pollution class IV sites in service; a heating jacket is fitted where the ambient drops below the standard range.

The breaker clears 40 kA, makes 100 kA peak and carries 40 kA for 4 s on an O-0.3s-CO-180s-CO sequence. Mechanical endurance is 10,000 operations. It switches load current, transformer and line faults and parallel circuits on 110 kV networks, and is ordered with an integrated earthing switch or a disconnector where the bay layout calls for one.

At a glance

Model
LW36-126T3150-40
Type
SF6, single-break, dead tank
Voltage class
126 kV
Rated current
3150 A
Breaking current
40 kA
Current transformers
Built in, bushing type
Operating mechanism
Spring, CT26

Price

On request

MOQ 1 piece · Lead time 30 days

Quoted per project · lead time confirmed with the order

Technical specifications

Rated values per IEC 62271-100. Ratings not listed are engineered to order.

Table 1 - Main technical parameters
ParameterUnitValue
Rated voltage UrkV126
Rated power-frequency withstand voltage, 1 min - to earthkV230
Rated power-frequency withstand voltage, 1 min - between interrupterskV265
Rated lightning impulse withstand voltage, 1.2/50 us - to earthkV550
Rated lightning impulse withstand voltage, 1.2/50 us - between interrupterskV630
Power-frequency withstand at zero gauge SF6 pressure, 5 minkV95
Rated frequencyHz50
Rated current IrA3150
First-pole-to-clear factor-1.5
Rated short-circuit breaking currentkA40
Rated short-circuit making current, peakkA100
Rated short-time withstand currentkA40
Rated peak withstand currentkA100
Rated short-circuit durations4
Rated out-of-phase breaking currentkA10
Rated close-in fault breaking current% of Ik90 / 75
Rated line-charging breaking currentA31.5
Rated operating sequence-O-0.3s-CO-180s-CO
Main circuit resistanceuOhm<= 40
Rated SF6 gauge pressure at 20 CMPa0.5
Alarm and minimum functional pressure at 20 CMPa0.45 +/- 0.03
SF6 annual leakage rate%<= 0.5
Moisture content of SF6uL/L<= 150
Mechanical enduranceoperations10000
Radio interference leveluV<= 500
Creepage distance - between interrupters / to earthmm3906 / 3150
SF6 gas weight per breakerkg15
Weight per breakerkg2200
Overall heightmm4096
Front face (windward) aream24.7
Ambient temperatureC-40 to +40
Pollution level-IV

Insulation levels are corrected for altitude with K = 1.13 per 2000 m and K = 1.28 at 3000 m. CT ratios, classes and special creepage classes are confirmed per project.

Standards and design basis

The breaker is designed and manufactured to the IEC 62271 series. Where a project specifies GB or another national equivalent, the corresponding ratings are mapped at the technical agreement stage.

  • IEC 62271-1 - Common specifications for high-voltage switchgear: service conditions, insulation levels and sealing.
  • IEC 62271-100 - Alternating-current circuit breakers above 1 kV: ratings, operating sequences and breaking duties.
  • IEC 61869-2 - Current transformers, applied to the cores built into the tank.
  • IEC 62271-102 - Disconnectors and earthing switches for integrated earthing options.

Type test reports for a specific configuration are issued with the technical offer on request.

Applications

110 kV substation feeders

Switching of outgoing feeders and transformer bays on 110 kV systems, where the 126 kV rating provides the insulation margin for the network.

Renewable collector substations

Wind and solar farms stepping up to a 110 kV collector network, with capacitor bank switching and frequent load changes handled by the 10,000-operation mechanism.

Tie lines between substations

Parallel and tie circuits that carry load transfer between 110 kV buses, including the out-of-phase duty of 10 kA allowed by the standard rating.

Industrial and mining 110 kV networks

Arc furnace, mill and mine systems with frequent operation and heavy contamination, where an oil-free interrupter cuts maintenance.

Ratings and options

Ratings below are the standard configuration. Other combinations are built to order and are not published as separate models.

ItemStandardOn request
Rated current3150 AOther ratings to order
Rated short-circuit breaking current40 kAHigher duties to order
Current transformersBushing type, built into the tankRatios, classes and burden per project
Operating mechanismCT26 spring-
Earthing switchNot includedIntegrated earthing switch
Creepage classIV, 3906 mm between interruptersExtended creepage for heavy pollution
Heating jacketNot includedConfigured for the ambient temperature

Frequently asked questions

How do I choose between 72.5 kV and 126 kV dead tank breakers?

The rating follows the system voltage. A 72.5 kV breaker is applied to 66 kV networks, a 126 kV breaker to 110 kV networks. Both share the same dead tank layout and CT26 mechanism, so the substation voltage decides.

Can a 126 kV breaker be used on a 110 kV system?

Yes. 126 kV is the highest voltage for equipment Um applied to 110 kV networks, and the power-frequency and lightning impulse levels in the table, 230 kV and 550 kV to earth, are dimensioned for that rating, so they cover the insulation coordination of a 110 kV network with margin.

What current transformers can be built into the tank?

The tank carries bushing or feedthrough type current transformers inside the grounded enclosure. Ratios, accuracy classes (0.2, 0.2S, 5P, 10P) and burden are fixed per project in the technical agreement.

What maintenance does the breaker need?

A density relay with alarm and lockout contacts monitors the gas continuously, so routine work is limited to density checks, contact resistance measurement and mechanism inspection. Rated gauge pressure is 0.5 MPa at 20 C, the annual leakage rate is guaranteed at 0.5 percent or less, and mechanical endurance is 10,000 operations.

Questions about this product?

Our engineers can confirm CT ratios, insulation levels, drawings and lead time for the LW36-126T3150-40.