Home/ Products/ SF6 Circuit Breakers/ LW36-145T3150-40

145kV SF6 Live Tank Circuit Breaker

145 kV · Outdoor installation · SF6, single-break live tank

LW36-145T 145 kV SF6 live tank circuit breaker, three porcelain pillars on one frame
Outdoor SF6 Live Tank Breaker

Overview

The LW36-145T3150-40 is an outdoor live tank SF6 circuit breaker rated 145 kV, 3150 A and 40 kA. Each pole is a single-break interrupter carried on a porcelain pillar at line potential, and the three poles stand on one hot-dip galvanized frame driven by a single spring mechanism through a three-phase linkage. With no earthed tank around the interrupter, the breaker weighs 1,800 kg and needs one foundation per frame.

SF6 at 0.5 MPa at 20 C does the arc quenching and the insulation inside each pole. The three pole volumes are connected, so one density relay with temperature compensation watches the pressure for all three. Creepage distance is catalogued as 4495 / 3625 mm, and the design is built to a specific creepage of at least 31 mm per kV. Annual leakage is held to 0.5 percent or less and moisture to 150 uL/L.

Breaking is 40 kA, making 100 kA peak, short-time withstand 40 kA for 4 s, on an O-0.3s-CO-180s-CO sequence. Mechanical endurance is 10,000 operations and the main circuit resistance stays at 50 uOhm or less. The self-blast interrupter keeps the operating energy low, which is why one mechanism can drive all three poles.

At a glance

Model
LW36-145T3150-40
Type
SF6, single-break, live tank
Voltage class
145 kV
Rated current
3150 A
Breaking current
40 kA
Poles
Three, one mechanism
Operating mechanism
Spring, three-phase linkage

Price

On request

MOQ 1 piece · Lead time 30 days

Quoted per project · lead time confirmed with the order

Technical specifications

Rated values per IEC 62271-100. Ratings not listed are engineered to order.

Table 1 - Main technical parameters
ParameterUnitValue
Rated voltage UrkV145
Rated power-frequency withstand voltage, 1 min - to earthkV275
Rated power-frequency withstand voltage, 1 min - between interrupterskV315
Rated lightning impulse withstand voltage, 1.2/50 us - to earthkV650
Rated lightning impulse withstand voltage, 1.2/50 us - between interrupterskV750
Power-frequency withstand at zero gauge SF6 pressure, 5 minkV95
Rated frequencyHz50/60
Rated current IrA3150
First-pole-to-clear factor-1.5
Rated short-circuit breaking currentkA40
Rated short-circuit making current, peakkA100
Rated short-time withstand currentkA40
Rated peak withstand currentkA100
Rated short-circuit durations4
Rated out-of-phase breaking currentkA10
Rated close-in fault breaking current% of Ik90 / 75
Rated line-charging breaking currentA31.5
Rated operating sequence-O-0.3s-CO-180s-CO
Main circuit resistanceuOhm<= 50
Rated SF6 gauge pressure at 20 CMPa0.5
Alarm and minimum functional pressure at 20 CMPa0.45 +/- 0.03
SF6 annual leakage rate%<= 0.5
Moisture content of SF6uL/L<= 150
Mechanical enduranceoperations10000
Radio interference leveluV<= 500
Creepage distancemm4495 / 3625
SF6 gas weight per breakerkg10
Weight per breakerkg1800
Overall heightmm5080
Overall width across polesmm4480
Pole centre distancemm2000
Front face (windward) aream25
Terminal load, per outline drawingkN22 / 44
Ambient temperatureC-40 to +40
Pollution level-IV

Insulation levels are corrected for altitude with K = 1.13 per 2000 m and K = 1.28 at 3000 m. Creepage classes and terminal arrangements are confirmed per project.

Standards and design basis

The breaker is designed and manufactured to the IEC 62271 series. Where a project specifies GB or another national equivalent, the corresponding ratings are mapped at the technical agreement stage.

  • IEC 62271-1 - Common specifications for high-voltage switchgear: service conditions, insulation levels and sealing.
  • IEC 62271-100 - Alternating-current circuit breakers above 1 kV: ratings, operating sequences and breaking duties.
  • IEC 62271-102 - Disconnectors and earthing switches for integrated earthing options.

Type test reports for a specific configuration are issued with the technical offer on request.

Applications

132 kV substation feeders

Switching of outgoing feeders and transformer bays on 132 kV systems, where the 145 kV rating provides the insulation margin for the network.

Renewable collector substations

Wind and solar farms stepping up to a 132 kV collector network, including capacitor bank and cable charging current switching.

Tie lines between substations

Parallel and tie circuits carrying load transfer between 132 kV buses, using the out-of-phase breaking duty of 10 kA.

Industrial and mining networks

Arc furnace, mill and mine distribution where frequent operation and heavy pollution are normal, with an oil-free sealed interrupter to keep maintenance low.

Ratings and options

Ratings below are the standard configuration. Other combinations are built to order and are not published as separate models.

ItemStandardOn request
Rated current3150 AOther ratings to order
Rated short-circuit breaking current40 kAHigher duties to order
Pole arrangementThree single-break pillars on one frame-
Operating mechanismSpring, three-phase linkage-
Current transformersNot supplied, post type CTs quoted with the bayRatios, classes and cores per project
Creepage classIV, 4495 / 3625 mm as cataloguedExtended creepage for heavy pollution
Terminal load22 kN and 44 kN, as drawnVerified against the bay layout

Frequently asked questions

What is the difference between a live tank and a dead tank 145 kV breaker?

A live tank breaker carries the interrupter on porcelain pillars at line potential, so the enclosure is not earthed and the gas volume is smaller. A dead tank breaker puts the interrupter inside an earthed metal tank and can carry the current transformers in the same enclosure. Live tank suits sites where the CTs already sit on separate post insulators and where the weight on the foundation matters.

Can a 145 kV breaker be used on a 132 kV system?

Yes. 145 kV is the highest voltage for equipment Um applied to 132 kV networks, and the power-frequency and lightning impulse levels in the table, 275 kV and 650 kV to earth, are dimensioned for that rating, so they cover the insulation coordination of a 132 kV network with margin.

Are current transformers included with the breaker?

No. On this live tank design the CTs are post type and are mounted separately, so ratios, classes and core counts are not part of the breaker. They are quoted with the bay, and the breaker terminals are dimensioned for the connecting leads.

What does the breaker need on site?

One foundation per frame with M24 anchor bolts at the positions given in the outline drawing, 2530 mm between the leg centres and 4480 mm overall. The drawing also gives the terminal load limits, 22 kN and 44 kN, that the connections must respect.

Questions about this product?

Our engineers can confirm insulation levels, drawings, terminal loads and lead time for the LW36-145T3150-40.