145 kV · Outdoor installation · SF6, single-break live tank
The LW36-145T3150-40 is an outdoor live tank SF6 circuit breaker rated 145 kV, 3150 A and 40 kA. Each pole is a single-break interrupter carried on a porcelain pillar at line potential, and the three poles stand on one hot-dip galvanized frame driven by a single spring mechanism through a three-phase linkage. With no earthed tank around the interrupter, the breaker weighs 1,800 kg and needs one foundation per frame.
SF6 at 0.5 MPa at 20 C does the arc quenching and the insulation inside each pole. The three pole volumes are connected, so one density relay with temperature compensation watches the pressure for all three. Creepage distance is catalogued as 4495 / 3625 mm, and the design is built to a specific creepage of at least 31 mm per kV. Annual leakage is held to 0.5 percent or less and moisture to 150 uL/L.
Breaking is 40 kA, making 100 kA peak, short-time withstand 40 kA for 4 s, on an O-0.3s-CO-180s-CO sequence. Mechanical endurance is 10,000 operations and the main circuit resistance stays at 50 uOhm or less. The self-blast interrupter keeps the operating energy low, which is why one mechanism can drive all three poles.
Price
On request
MOQ 1 piece · Lead time 30 days
Quoted per project · lead time confirmed with the order
Rated values per IEC 62271-100. Ratings not listed are engineered to order.
| Parameter | Unit | Value |
|---|---|---|
| Rated voltage Ur | kV | 145 |
| Rated power-frequency withstand voltage, 1 min - to earth | kV | 275 |
| Rated power-frequency withstand voltage, 1 min - between interrupters | kV | 315 |
| Rated lightning impulse withstand voltage, 1.2/50 us - to earth | kV | 650 |
| Rated lightning impulse withstand voltage, 1.2/50 us - between interrupters | kV | 750 |
| Power-frequency withstand at zero gauge SF6 pressure, 5 min | kV | 95 |
| Rated frequency | Hz | 50/60 |
| Rated current Ir | A | 3150 |
| First-pole-to-clear factor | - | 1.5 |
| Rated short-circuit breaking current | kA | 40 |
| Rated short-circuit making current, peak | kA | 100 |
| Rated short-time withstand current | kA | 40 |
| Rated peak withstand current | kA | 100 |
| Rated short-circuit duration | s | 4 |
| Rated out-of-phase breaking current | kA | 10 |
| Rated close-in fault breaking current | % of Ik | 90 / 75 |
| Rated line-charging breaking current | A | 31.5 |
| Rated operating sequence | - | O-0.3s-CO-180s-CO |
| Main circuit resistance | uOhm | <= 50 |
| Rated SF6 gauge pressure at 20 C | MPa | 0.5 |
| Alarm and minimum functional pressure at 20 C | MPa | 0.45 +/- 0.03 |
| SF6 annual leakage rate | % | <= 0.5 |
| Moisture content of SF6 | uL/L | <= 150 |
| Mechanical endurance | operations | 10000 |
| Radio interference level | uV | <= 500 |
| Creepage distance | mm | 4495 / 3625 |
| SF6 gas weight per breaker | kg | 10 |
| Weight per breaker | kg | 1800 |
| Overall height | mm | 5080 |
| Overall width across poles | mm | 4480 |
| Pole centre distance | mm | 2000 |
| Front face (windward) area | m2 | 5 |
| Terminal load, per outline drawing | kN | 22 / 44 |
| Ambient temperature | C | -40 to +40 |
| Pollution level | - | IV |
Insulation levels are corrected for altitude with K = 1.13 per 2000 m and K = 1.28 at 3000 m. Creepage classes and terminal arrangements are confirmed per project.
The breaker is designed and manufactured to the IEC 62271 series. Where a project specifies GB or another national equivalent, the corresponding ratings are mapped at the technical agreement stage.
Type test reports for a specific configuration are issued with the technical offer on request.
Switching of outgoing feeders and transformer bays on 132 kV systems, where the 145 kV rating provides the insulation margin for the network.
Wind and solar farms stepping up to a 132 kV collector network, including capacitor bank and cable charging current switching.
Parallel and tie circuits carrying load transfer between 132 kV buses, using the out-of-phase breaking duty of 10 kA.
Arc furnace, mill and mine distribution where frequent operation and heavy pollution are normal, with an oil-free sealed interrupter to keep maintenance low.
Ratings below are the standard configuration. Other combinations are built to order and are not published as separate models.
| Item | Standard | On request |
|---|---|---|
| Rated current | 3150 A | Other ratings to order |
| Rated short-circuit breaking current | 40 kA | Higher duties to order |
| Pole arrangement | Three single-break pillars on one frame | - |
| Operating mechanism | Spring, three-phase linkage | - |
| Current transformers | Not supplied, post type CTs quoted with the bay | Ratios, classes and cores per project |
| Creepage class | IV, 4495 / 3625 mm as catalogued | Extended creepage for heavy pollution |
| Terminal load | 22 kN and 44 kN, as drawn | Verified against the bay layout |
What is the difference between a live tank and a dead tank 145 kV breaker?
A live tank breaker carries the interrupter on porcelain pillars at line potential, so the enclosure is not earthed and the gas volume is smaller. A dead tank breaker puts the interrupter inside an earthed metal tank and can carry the current transformers in the same enclosure. Live tank suits sites where the CTs already sit on separate post insulators and where the weight on the foundation matters.
Can a 145 kV breaker be used on a 132 kV system?
Yes. 145 kV is the highest voltage for equipment Um applied to 132 kV networks, and the power-frequency and lightning impulse levels in the table, 275 kV and 650 kV to earth, are dimensioned for that rating, so they cover the insulation coordination of a 132 kV network with margin.
Are current transformers included with the breaker?
No. On this live tank design the CTs are post type and are mounted separately, so ratios, classes and core counts are not part of the breaker. They are quoted with the bay, and the breaker terminals are dimensioned for the connecting leads.
What does the breaker need on site?
One foundation per frame with M24 anchor bolts at the positions given in the outline drawing, 2530 mm between the leg centres and 4480 mm overall. The drawing also gives the terminal load limits, 22 kN and 44 kN, that the connections must respect.