Home/ Products/ SF6 Circuit Breakers/ LW□-252(W)/T4000-50

252kV SF6 Live Tank Circuit Breaker

252 kV · Outdoor installation · SF6, single-break live tank

LW-252 SF6 live tank circuit breaker, three single-break porcelain pillars with mechanism cabinets
Outdoor SF6 Live Tank Breaker

Overview

The LW□-252(W)/T4000-50 is an outdoor live tank SF6 circuit breaker rated 252 kV, 4000 A and 50 kA. Each pole is a single-break interrupter carried on a porcelain pillar at line potential, standing on its own galvanized support with its own spring mechanism cabinet. The three poles are coupled electrically rather than by a single linkage, so one command operates all three. Each pole weighs 1500 kg; the complete set is 4500 kg with gas.

SF6 at 0.6 MPa at 20 C quenches the arc and insulates the pole. The three pole volumes are separate and each carries its own density relay with temperature compensation, so a leak in one pole is visible on its own gauge. Annual leakage is held to 0.5 percent or less and moisture to 150 ppm. Creepage is at least 8660 mm between interrupters and 6900 mm to earth, which serves pollution class IV sites up to 2000 m altitude.

The breaker clears 50 kA, makes 125 kA peak and carries 50 kA for 3 s, on an O-0.3s-CO-180s-CO sequence; out-of-phase breaking is 12.5 kA and line-charging current 200 A. Mechanical endurance is 10,000 operations and the main circuit resistance stays below 55 uOhm. The self-blast interrupter and the single-break pillar keep the moving mass low, which is what allows a separate mechanism on each pole.

At a glance

Model
LW□-252(W)/T4000-50
Type
SF6, single-break, live tank
Voltage class
252 kV
Rated current
4000 A
Breaking current
50 kA
Poles
Three, one per pole
Operating mechanism
Spring per pole, electrically linked

Price

On request

MOQ 1 piece · Lead time 30 days

Quoted per project · lead time confirmed with the order

Technical specifications

Rated values per IEC 62271-100. Ratings not listed are engineered to order.

Table 1 - Main technical parameters
ParameterUnitValue
Rated voltage UrkV252
Rated power-frequency withstand voltage, 1 min - to earthkV460
Rated power-frequency withstand voltage, 1 min - between interrupterskV460 + 146
Rated lightning impulse withstand voltage, 1.2/50 us - to earthkV1050
Rated lightning impulse withstand voltage, 1.2/50 us - between interrupterskV1050 + 206
Rated frequencyHz50
Rated current IrA4000
First-pole-to-clear factor-1.3
Rated short-circuit breaking currentkA50
Rated short-circuit making current, peakkA125
Rated short-time withstand currentkA50
Rated peak withstand currentkA125
Rated short-circuit durations3
Rated out-of-phase breaking currentkA12.5
Rated close-in fault breaking current% of Ik90 / 75
Rated line-charging breaking currentA200
Rated operating sequence-O-0.3s-CO-180s-CO
Main circuit resistanceuOhm<= 55
Rated SF6 gauge pressure at 20 CMPa0.6
Alarm and minimum functional pressure at 20 CMPa0.55 +/- 0.015 / 0.50 +/- 0.015
SF6 annual leakage rate%<= 0.5
Moisture content of SF6ppm<= 150
Mechanical enduranceoperations10000
Radio interference leveluV<= 500
Creepage distance - between interruptersmm>= 8660
Creepage distance - to earthmm>= 6900
SF6 gas weight per breakerkg24
Weight per polekg1500
Weight of three poles with gaskg4500
Overall heightmm6913
Pole centre distancemm3000 - 4000
Foundation static load, three poleskg4500
Dynamic load - horizontal / up / downkg2500 / 3500 / 6000
Ambient temperature, minimumC-30
Pollution level-IV
Altitudem<= 2000

Insulation levels are corrected for altitude with K = 1.13 per 2000 m and K = 1.28 at 3000 m. Creepage classes and terminal arrangements are confirmed per project.

Standards and design basis

The breaker is designed and manufactured to the IEC 62271 series. Where a project specifies GB or another national equivalent, the corresponding ratings are mapped at the technical agreement stage.

  • IEC 62271-1 - Common specifications for high-voltage switchgear: service conditions, insulation levels and sealing.
  • IEC 62271-100 - Alternating-current circuit breakers above 1 kV: ratings, operating sequences and breaking duties.
  • IEC 62271-102 - Disconnectors and earthing switches for integrated earthing options.

Type test reports for a specific configuration are issued with the technical offer on request.

Applications

220 kV substation feeders

Switching of outgoing feeders and transformer bays on 220 kV systems, where the 252 kV rating provides the insulation margin for the network.

220 kV tie lines

Parallel and tie circuits carrying bulk load transfer between 220 kV buses, using the out-of-phase breaking duty of 12.5 kA.

Renewable step-up substations

Large wind and solar plants stepping up to a 220 kV collector network, including cable and line charging current switching.

Industrial 220 kV networks

Mining, metals and process plants with heavy contamination and frequent operation, where an oil-free sealed interrupter keeps maintenance low.

Ratings and options

Ratings below are the standard configuration. Other combinations are built to order and are not published as separate models.

ItemStandardOn request
Rated current4000 AOther ratings to order
Rated short-circuit breaking current50 kAHigher duties to order
Pole arrangementThree single-break pillars, separate foundations-
Operating mechanismSpring, one per pole, three-phase electrically linked-
Current transformersNot supplied, post type CTs quoted with the bayRatios, classes and cores per project
Creepage classIV, 8660 mm between interruptersExtended creepage for heavy pollution
FoundationOne per pole, 3000 - 4000 mm spacingLayout drawing per project

Frequently asked questions

Why does each pole have its own operating mechanism?

Above 200 kV the three poles stand too far apart for one mechanism to drive them through a simple linkage, so each pole carries its own spring mechanism inside its cabinet. The three are coupled electrically, so one command operates all three poles together, and a single pole can still be serviced without opening the other two.

Can a 252 kV breaker be used on a 220 kV system?

Yes. 252 kV is the highest voltage for equipment Um applied to 220 kV networks. The power-frequency and lightning impulse levels in the table, 460 kV and 1050 kV to earth, are dimensioned for that rating and cover the insulation coordination of a 220 kV network.

Are current transformers included?

No. This is a live tank design, so CTs are post type and mounted separately on the bay. Ratios, classes and core counts are quoted with the switchgear, and the terminal blocks are prepared for the connecting leads.

What foundation does it need?

One foundation per pole, with the poles set 3000 to 4000 mm apart. Static load is 4500 kg for the three poles, 1500 kg per pole; the dynamic loads to design for are 2500 kg horizontal, 3500 kg vertical upward and 6000 kg vertical downward.

Questions about this product?

Our engineers can confirm insulation levels, drawings, foundation loads and lead time for the LW□-252(W)/T4000-50.