252 kV · Outdoor installation · SF6, single-break live tank
The LW□-252(W)/T4000-50 is an outdoor live tank SF6 circuit breaker rated 252 kV, 4000 A and 50 kA. Each pole is a single-break interrupter carried on a porcelain pillar at line potential, standing on its own galvanized support with its own spring mechanism cabinet. The three poles are coupled electrically rather than by a single linkage, so one command operates all three. Each pole weighs 1500 kg; the complete set is 4500 kg with gas.
SF6 at 0.6 MPa at 20 C quenches the arc and insulates the pole. The three pole volumes are separate and each carries its own density relay with temperature compensation, so a leak in one pole is visible on its own gauge. Annual leakage is held to 0.5 percent or less and moisture to 150 ppm. Creepage is at least 8660 mm between interrupters and 6900 mm to earth, which serves pollution class IV sites up to 2000 m altitude.
The breaker clears 50 kA, makes 125 kA peak and carries 50 kA for 3 s, on an O-0.3s-CO-180s-CO sequence; out-of-phase breaking is 12.5 kA and line-charging current 200 A. Mechanical endurance is 10,000 operations and the main circuit resistance stays below 55 uOhm. The self-blast interrupter and the single-break pillar keep the moving mass low, which is what allows a separate mechanism on each pole.
Price
On request
MOQ 1 piece · Lead time 30 days
Quoted per project · lead time confirmed with the order
Rated values per IEC 62271-100. Ratings not listed are engineered to order.
| Parameter | Unit | Value |
|---|---|---|
| Rated voltage Ur | kV | 252 |
| Rated power-frequency withstand voltage, 1 min - to earth | kV | 460 |
| Rated power-frequency withstand voltage, 1 min - between interrupters | kV | 460 + 146 |
| Rated lightning impulse withstand voltage, 1.2/50 us - to earth | kV | 1050 |
| Rated lightning impulse withstand voltage, 1.2/50 us - between interrupters | kV | 1050 + 206 |
| Rated frequency | Hz | 50 |
| Rated current Ir | A | 4000 |
| First-pole-to-clear factor | - | 1.3 |
| Rated short-circuit breaking current | kA | 50 |
| Rated short-circuit making current, peak | kA | 125 |
| Rated short-time withstand current | kA | 50 |
| Rated peak withstand current | kA | 125 |
| Rated short-circuit duration | s | 3 |
| Rated out-of-phase breaking current | kA | 12.5 |
| Rated close-in fault breaking current | % of Ik | 90 / 75 |
| Rated line-charging breaking current | A | 200 |
| Rated operating sequence | - | O-0.3s-CO-180s-CO |
| Main circuit resistance | uOhm | <= 55 |
| Rated SF6 gauge pressure at 20 C | MPa | 0.6 |
| Alarm and minimum functional pressure at 20 C | MPa | 0.55 +/- 0.015 / 0.50 +/- 0.015 |
| SF6 annual leakage rate | % | <= 0.5 |
| Moisture content of SF6 | ppm | <= 150 |
| Mechanical endurance | operations | 10000 |
| Radio interference level | uV | <= 500 |
| Creepage distance - between interrupters | mm | >= 8660 |
| Creepage distance - to earth | mm | >= 6900 |
| SF6 gas weight per breaker | kg | 24 |
| Weight per pole | kg | 1500 |
| Weight of three poles with gas | kg | 4500 |
| Overall height | mm | 6913 |
| Pole centre distance | mm | 3000 - 4000 |
| Foundation static load, three poles | kg | 4500 |
| Dynamic load - horizontal / up / down | kg | 2500 / 3500 / 6000 |
| Ambient temperature, minimum | C | -30 |
| Pollution level | - | IV |
| Altitude | m | <= 2000 |
Insulation levels are corrected for altitude with K = 1.13 per 2000 m and K = 1.28 at 3000 m. Creepage classes and terminal arrangements are confirmed per project.
The breaker is designed and manufactured to the IEC 62271 series. Where a project specifies GB or another national equivalent, the corresponding ratings are mapped at the technical agreement stage.
Type test reports for a specific configuration are issued with the technical offer on request.
Switching of outgoing feeders and transformer bays on 220 kV systems, where the 252 kV rating provides the insulation margin for the network.
Parallel and tie circuits carrying bulk load transfer between 220 kV buses, using the out-of-phase breaking duty of 12.5 kA.
Large wind and solar plants stepping up to a 220 kV collector network, including cable and line charging current switching.
Mining, metals and process plants with heavy contamination and frequent operation, where an oil-free sealed interrupter keeps maintenance low.
Ratings below are the standard configuration. Other combinations are built to order and are not published as separate models.
| Item | Standard | On request |
|---|---|---|
| Rated current | 4000 A | Other ratings to order |
| Rated short-circuit breaking current | 50 kA | Higher duties to order |
| Pole arrangement | Three single-break pillars, separate foundations | - |
| Operating mechanism | Spring, one per pole, three-phase electrically linked | - |
| Current transformers | Not supplied, post type CTs quoted with the bay | Ratios, classes and cores per project |
| Creepage class | IV, 8660 mm between interrupters | Extended creepage for heavy pollution |
| Foundation | One per pole, 3000 - 4000 mm spacing | Layout drawing per project |
Why does each pole have its own operating mechanism?
Above 200 kV the three poles stand too far apart for one mechanism to drive them through a simple linkage, so each pole carries its own spring mechanism inside its cabinet. The three are coupled electrically, so one command operates all three poles together, and a single pole can still be serviced without opening the other two.
Can a 252 kV breaker be used on a 220 kV system?
Yes. 252 kV is the highest voltage for equipment Um applied to 220 kV networks. The power-frequency and lightning impulse levels in the table, 460 kV and 1050 kV to earth, are dimensioned for that rating and cover the insulation coordination of a 220 kV network.
Are current transformers included?
No. This is a live tank design, so CTs are post type and mounted separately on the bay. Ratios, classes and core counts are quoted with the switchgear, and the terminal blocks are prepared for the connecting leads.
What foundation does it need?
One foundation per pole, with the poles set 3000 to 4000 mm apart. Static load is 4500 kg for the three poles, 1500 kg per pole; the dynamic loads to design for are 2500 kg horizontal, 3500 kg vertical upward and 6000 kg vertical downward.