72.5 kV · Outdoor installation · SF6, single-break dead tank
The LW36-72.5T3150-40 is an outdoor, dead tank SF6 circuit breaker rated 72.5 kV, 3150 A and 31.5 kA. Each pole carries a single-break interrupter mounted horizontally inside a grounded aluminium alloy tank, and the three tanks stand on one common frame driven by a single CT26 spring operating mechanism through a three-phase mechanical linkage. Because the interrupter is enclosed in a tank at earth potential, current transformers are installed inside the same enclosure, so a breaker bay and its CTs occupy one footprint instead of two.
The design is oil-free: SF6 gas provides both arc quenching and insulation. Rated gauge pressure is 0.5 MPa at 20 °C, with a guaranteed annual leakage rate of 0.5 percent or less, monitored by a density relay with alarm and lockout contacts. Sealing uses compressed moulded seals, and the tight enclosure keeps the live parts independent of dust, humidity and small animals, which matters on coastal and desert sites where pollution class IV applies.
Mechanical endurance is 10,000 operations, with an electrical life of 24 breaking operations at 31.5 kA or 31 operations at 25 kA. The breaker is used to switch load current, fault current and parallel circuits on 66 kV systems, and can be combined with an isolating switch or a capacitor bank for reactive compensation duty.
Price
On request
MOQ 1 piece · Lead time 30 days
Quoted per project · lead time confirmed with the order
Rated values per IEC 62271-100. Ratings not listed are engineered to order.
| Parameter | Unit | Value |
|---|---|---|
| Rated voltage Ur | kV | 72.5 |
| Rated power-frequency withstand voltage, 1 min - to earth | kV | 160 |
| Rated power-frequency withstand voltage, 1 min - between interrupters | kV | 200 |
| Rated lightning impulse withstand voltage, 1.2/50 us - to earth | kV | 350 |
| Rated lightning impulse withstand voltage, 1.2/50 us - between interrupters | kV | 410 |
| Power-frequency withstand at zero gauge SF6 pressure, 5 min | kV | 84 |
| Rated frequency | Hz | 50 |
| Rated current Ir | A | 3150 |
| First-pole-to-clear factor | - | 1.5 |
| Rated short-circuit breaking current | kA | 31.5 |
| Rated short-circuit making current, peak | kA | 80 |
| Rated short-time withstand current | kA | 31.5 |
| Rated peak withstand current | kA | 80 |
| Rated short-circuit duration | s | 4 |
| Rated out-of-phase breaking current | kA | 8 |
| Rated close-in fault breaking current | % of Ik | 90 / 75 |
| Rated line-charging breaking current | A | 10 |
| Rated operating sequence | - | O-0.3s-CO-180s-CO |
| Main circuit resistance | uOhm | <= 40 |
| Rated SF6 gauge pressure at 20 C | MPa | 0.5 |
| Alarm and minimum functional pressure at 20 C | MPa | 0.45 +/- 0.03 |
| SF6 annual leakage rate | % | <= 0.5 |
| Moisture content of SF6 | uL/L | <= 150 |
| Mechanical endurance | operations | 10000 |
| Electrical life at 31.5 kA / at 25 kA | operations | 24 / 31 |
| Radio interference level | uV | <= 500 |
| Creepage distance - between interrupters / to earth | mm | 2585 / 2248 |
| SF6 gas weight per breaker | kg | 10 |
| Weight per breaker | kg | 1500 |
| Overall height | mm | 3818 |
| Front face (windward) area | m2 | 4.5 |
| Ambient temperature | C | -40 to +40 |
| Pollution level | - | IV |
External insulation level is corrected by the altitude factor K: K = 1.13 every 2000 m, K = 1.28 at 3000 m. CT ratios, classes and special creepage classes are confirmed per project.
The breaker is designed and manufactured to the IEC 62271 series. Rated characteristics, insulation coordination, breaking and making duties and the routine test schedule follow the clauses below. Where a project specifies GB or another national equivalent, the corresponding ratings are mapped at the technical agreement stage.
Type test reports for a specific configuration are issued with the technical offer on request.
Switching of outgoing feeders and transformer bays on 66 kV systems, where the 72.5 kV rating provides the insulation margin for the network.
Wind and solar farms stepping up to a 66 kV collector network, with capacitor bank switching and frequent load changes handled by the 10,000-operation mechanism.
The tank construction keeps the live parts low and enclosed, which suits sites with limited space or strict clearance requirements.
Arc furnace, mill and mine distribution systems that see frequent operation and heavy contamination, where an oil-free sealed interrupter reduces maintenance.
Ratings below are the standard configuration. Other combinations are built to order and are not published as separate models.
| Item | Standard | On request |
|---|---|---|
| Rated current | 3150 A | Other ratings to order |
| Rated short-circuit breaking current | 31.5 kA | Higher duties to order |
| Current transformers | Up to 12 cores, 0.2 / 0.2S / 5P / 10P | Ratios and burden per project |
| Operating mechanism | CT26 spring | - |
| Earthing switch | Not included | Integrated earthing switch |
| Creepage class | IV, 2585 mm between interrupters | Extended creepage for heavy pollution |
What is the difference between a dead tank and a live tank SF6 circuit breaker?
In a dead tank breaker the interrupter sits horizontally inside a grounded metal tank, so current transformers can be mounted inside the same enclosure and the assembly stays low. A live tank breaker carries the interrupter on porcelain columns at line potential, with separate post-type CTs. Dead tank suits compact sites; live tank is easier to inspect and usually cheaper at the same rating.
Can a 72.5 kV breaker be used on a 66 kV system?
Yes. 72.5 kV is the highest voltage for equipment applied to 66 kV networks, and the insulation levels, creepage and clearances in the table are dimensioned for that rating, which covers the insulation coordination of a 66 kV system with margin.
What CT ratios and classes can be built in?
The tank accepts up to twelve cores, from 0.2 or 0.2S for metering to 5P and 10P for protection. Ratios and burden are fixed per project and confirmed in the technical agreement, so they are not held as a catalogue item.
What maintenance does the breaker need?
Gas density is monitored continuously by a relay with alarm and lockout contacts, so routine work is limited to density checks, contact resistance measurement and mechanism inspection. Mechanical endurance is 10,000 operations and the annual leakage rate is guaranteed at 0.5 percent or less.
In a dead tank breaker the interrupter sits horizontally inside a grounded metal tank, so the enclosure is at earth potential and current transformers can be mounted inside the same tank. A live tank breaker carries the interrupter on top of porcelain columns at line potential, with separate post-type current transformers. Dead tank designs are lower in height and suit compact or indoor-adjacent substations; live tank designs are easier to inspect and usually cheaper at the same rating.
Yes. The 72.5 kV rating is the highest voltage for equipment Um applied to 66 kV networks. Insulation levels, creepage distance and clearances are dimensioned for 72.5 kV, which covers the insulation coordination requirements of a 66 kV system with margin.
The tank accepts up to twelve current transformer cores, with accuracy classes from 0.2 or 0.2S for metering to 5P and 10P for protection. Ratios, burden and class combinations are fixed per project, so the required set is confirmed at the technical agreement stage rather than held as a catalogue item.
Rated gauge pressure is 0.5 MPa at 20 C with a guaranteed annual leakage rate of 0.5 percent or less, and a density relay with alarm and lockout contacts monitors the gas. Mechanical endurance is 10,000 operations; electrical life at rated short-circuit current is 24 breaking operations at 31.5 kA, or 31 operations at 25 kA. Routine work is limited to gas density checks, contact resistance measurement and mechanism inspection.