With three 300:5 CTs on a 300 A balanced feeder, a star connection gives each phase element 5 A, a delta connection gives 8.66 A in the delta loop, and a residual connection gives the earth element 0 A because the three phase currents cancel. The ratio is only half the specification: the connection of the three secondaries decides what the relay actually measures.

Most CT datasheets state a ratio, a class and a burden and stop there, because the secondary connection is a wiring decision taken by the panel builder or the protection engineer. That is also why the same CT can be correct on one scheme and wrong on the next. This article works through the three arrangements that appear in medium-voltage practice, what each one does to the current, and what has to be written into the RFQ so the cores arrive capable of the connection the scheme assumes.

How Is a Three-CT Star Connection Wired?

In the star or Y connection, the S1 terminal of each CT goes to its own phase element, and the three S2 terminals are joined at a common star point. The phase elements therefore sit in series with their own core and see that phase current alone. The star point is taken to the earth-fault element and then to a single earth, so the conductor between the star point and earth carries the vector sum of the three secondary currents, which is 3I0. On a balanced feeder that sum is zero, and the earth element sits at rest.

This is the default for feeder overcurrent and for metering, because it needs no ratio correction: 300 A primary through a 300:5 core gives 5 A to the relay, and the relay setting can be read straight off the CT nameplate. The star point is also the one place where the residual current of the whole set is available without a fourth CT, which is why most three-phase protection schemes are drawn this way before anything else is considered.

Red cast-resin LZZBJ9-10 indoor post-type current transformer with P1 and P2 cast into the body and a clear cover over the secondary terminal plate

How Is a Three-CT Delta Connection Wired?

The delta connection closes the three secondaries into a loop: S1 of phase A to S2 of phase B, S1 of B to S2 of C, and S1 of C back to S2 of A. The relay or the pilot cables are connected at the corners of that loop. Two things change at once. The current delivered to the relay is the current in the delta line, not the current in one core, so it is √3 times the core current, and it is displaced by 30 electrical degrees from the phase current that produced it.

That 30 degree shift is the reason the connection exists. On the differential protection of a transformer with a delta winding, the CTs on the star side are connected in delta so that the secondary currents arrive in phase with those from the delta side, and the differential element compares like with like. The magnitude change is a side effect that has to be paid for: at 300 A primary the relay now reads 8.66 A, so a pickup quoted as a multiple of rated current refers to a different base unless the setting is recalculated.

The delta is also blind to earth faults. Zero-sequence current cannot leave a closed delta; it circulates inside the loop and produces no output at the corners. A scheme that relies on delta-connected CTs alone has no earth-fault protection, which is acceptable only where a separate neutral CT, a core-balance CT or a residual set covers that function. The same applies to the burden: the cores are no longer independent, because current from one core returns through the other two, so the connected burden per core is higher than the relay coil figure and the class should be checked against the calculated burden rather than the nameplate.

Tall ribbed LZZBJ9-35 indoor current transformer in red cast resin with a transparent secondary terminal box on the left side of the base

How Is the Residual or Three-Phase Parallel Connection Wired?

The residual connection parallels the three secondaries: all S1 terminals are joined, all S2 terminals are joined, and one element is connected across the two common points. The phase elements stay connected individually across their own core, so this is not a substitute for the star, it is an addition to it. What the paralleled element sees is the sum of the three secondary currents, and on a healthy feeder that sum is zero by construction.

The arrangement is cheap, needs no fourth CT and works well for earth-fault sensitivity on a cable feeder, but it is only as good as the matching of the three cores. Three cores of the same ratio and class still differ by a fraction of a percent, and that fraction does not cancel. At full load, a 1% spread between cores leaves roughly 0.05 A standing in the residual circuit on a 5 A secondary, which is a quarter of a 0.2 A earth-fault setting before any fault current arrives. Cores of different ratio, different class or different manufacture turn that standing current into either a permanent loss of sensitivity or a trip on load.

Red cast-resin 35 kV current transformer with a ribbed insulator stack, a galvanized base plate and a small secondary terminal chamber at the foot

Which Connection Fits Which Protection Function?

The table below is the version to copy into a scheme sheet or a comparison of two supplier proposals. It assumes three identical cores, one per phase, and a 5 A secondary.

Connection Phase element sees Earth element sees Factor on core current Phase shift Zero sequence Typical use
Star (Y) Own phase current 3I0 in the star point 1.0 0 degrees Reaches the neutral Feeder overcurrent, metering, residual earth fault
Delta Delta line current Nothing √3 = 1.73 30 degrees lead Circulates, blocked Transformer differential, Yd phase compensation
Residual (parallel) Own phase current, if tapped individually 3I0 in the parallel element 1.0 per core, 3I0 summed 0 degrees Summed, not blocked Sensitive earth fault on cable feeders
Star point earthed twice Phase current plus circulating current Spurious 3I0 Unpredictable Unpredictable Circulating path Fault to be corrected at commissioning

What Do the Relay Currents Work Out To at 300 A?

Take a feeder carrying a balanced 300 A with no earth current, and run the same primary current through three different ratios. The core current is the primary divided by the ratio; the star element reads that value unchanged; the delta loop reads it multiplied by 1.732; the residual element reads zero because the three phase currents add to zero.

Ratio Core current at 300 A Star phase element Star neutral (3I0) Delta loop current Residual element (3I0)
300:5 5.00 A 5.00 A 0 A 8.66 A 0 A
300:1 1.00 A 1.00 A 0 A 1.73 A 0 A
600:5 2.50 A 2.50 A 0 A 4.33 A 0 A

Two readings from that table are worth carrying into a setting file. First, the delta connection makes the relay see 73% more current than the CT ratio implies, so any pickup expressed as a multiple of rated current has to be divided by 1.732 before it is entered, or the protection ends up 73% less sensitive than the study assumed. Second, a 600:5 core at 300 A gives only half the nominal current, which is a legitimate choice for a feeder that will grow, but it halves the current available to a high-impedance earth-fault element and should be checked against the minimum fault current at the far end of the cable.

What Changes When the Load Is Not Balanced?

The balanced case is the easy one. The moment one phase differs, the star point and the residual element stop reading zero, and the size of that reading is the whole point of the connection. The table below keeps the 300:5 ratio and shows what the earth element of a star or residual set reads for the disturbances that actually occur.

Condition Primary currents 3I0 primary Earth element at 300:5
Balanced load 300 / 300 / 300 A 0 A 0 A
Phase B open, single-phase load 300 / 0 / 300 A 300 A 5.00 A, trips the earth element
Earth fault, 90 A Load plus 90 A to earth 90 A 1.50 A
Earth fault, 30 A Load plus 30 A to earth 30 A 0.50 A
One secondary lead open Balanced 300 A 300 A apparent 5.00 A, false earth fault

The last two rows are the ones that surprise people. An open secondary lead in a star or residual set looks exactly like an earth fault of one third the load current, so a loose terminal in the star point produces a trip on load with no fault on the system. And because the earth element is fed from the same cores as the phase elements, a CT whose ratio drifts or whose burden is exceeded will shift the residual reading without any fault at all. That is why the residual function is only as trustworthy as the cores behind it, and why the burden and lead calculation matters more here than on a plain overcurrent element.

Which Selection Mistakes Cost Money at Commissioning?

The mistakes below are the ones that reach site and only appear during primary injection, when the panel is built, the cable is terminated and the outage is booked.

  • Delta wired, star settings. The relay sees 1.73 times the expected current and the pickup is wrong by the same factor. Re-testing, re-setting and a second outage follow.
  • Delta assumed to give earth fault. Zero sequence circulates inside the loop, so the function simply does not exist. The feeder runs with no earth-fault protection until someone reads the scheme.
  • Residual built from unmatched cores. Different ratios, classes or vintages leave a standing 3I0 that either blocks the setting or trips on load, and the fix is three new cores rather than a setting change.
  • Star point earthed at both ends. Two earths create a parallel path, part of the residual current bypasses the element, and the measured 3I0 no longer represents the fault.
  • Ratio chosen for the star case only. A core sized to give exactly 5 A in star gives 8.66 A in delta, which may sit above the relay range or outside the class accuracy at that point.

Each of these has the same commercial shape: the hardware is already mounted, the cable is already terminated, and the correction needs a shutdown rather than a purchase order. A delta-versus-star error found at primary injection typically costs a re-test, a revised setting file and a delay to energisation, and on a substation with a fixed commissioning window that delay is the expensive part, not the engineering time.

What Should the RFQ and Datasheet State?

A CT enquiry that gives the ratio and the class will be quoted, but it will not tell the supplier which connection the cores have to survive. The list below is what to write instead, phrased as requirements rather than requests.

  • System voltage, insulation level and whether the unit is bushing-mounted, bar primary or window type, with the bore or bar dimensions.
  • Ratio and class for every core separately, and the intended connection of the set: star, delta or residual. Where delta is intended, state it, because the core has to carry the delta line current and the connected burden.
  • Burden per core in VA and power factor, with the relay or meter model, plus the secondary lead length and cross-section, so the connected burden can be calculated rather than estimated.
  • Short-time thermal current and dynamic current for the switchgear fault level, and the instrument security factor for any metering core.
  • Routine test reports per unit: ratio, polarity, insulation and burden, with the test voltage stated, plus type test reports to IEC 61869-1 and IEC 61869-2 where the project requires them.
  • Terminal marking convention, P1 and S1 positions, and the polarity convention the protection settings assume.
  • Ambient and site conditions: 40 C or above, coastal humidity, dust, altitude, and whether the unit sits inside a cable box or an enclosure.
  • Approval drawing, packing and marking requirements, and the quantity with spare units stated separately.

The single line that prevents most of the trouble is the connection the scheme intends. Suppliers quote cores, not schemes, and a core that is correct for a star set can be marginal in a delta set at the same ratio and burden. Ask for the burden calculation to be shown against the connection, and the answer becomes checkable before the order rather than after the injection test.

Where Nahu Group Fits

Nahu Group makes current transformers for 3 to 12 kV switchgear, including indoor post-type units such as the LZZBJ9-10 post-type CT for panel mounting, and bushing-type window units that slip over a bushing or cable termination, such as the bushing-type CT rated 100 A to 600 A with 0.2S, 0.2 and 0.5 metering cores and 10P10 to 10P20 protection cores. The three-phase range is listed on the current transformer product page, which also covers the zero-sequence and split-core variants used where a residual set is not practical.

To get a configuration confirmed, send the system voltage, the ratio and class for each core, the connection the scheme uses, the burden per core with the lead length, the fault level and the bore or bushing dimensions. A drawing of the bay or the transformer terminal arrangement is more useful than a description, and it is enough to answer with a core list, a burden calculation and an outline drawing for approval. If the connection is still open, say so and the core recommendation will be made for the arrangement that fits the protection function rather than for the ratio alone.

Two related checks are worth reading before the enquiry goes out: CT polarity and what a reversed core does to each protection function, and how secondary lead length changes the required VA. Where the three secondaries end up earthed, the one-point earthing rule for CT secondaries explains why a second earth defeats the residual measurement. Where the scheme compares two sets of CTs, the combined three-phase unit is the alternative to three separate cores.

Frequently Asked Questions About CT Connections

Does a delta connection change the CT ratio?

The ratio of each core is unchanged; the current seen by the relay is not. Each core still delivers its own secondary current, but the delta loop adds the currents of two cores at 30 degrees apart, so the relay reads 1.732 times the core current. For settings and for burden calculations, treat the effective ratio as the nameplate ratio divided by 1.732.

Can three CTs be connected in delta for earth-fault protection?

No. Zero-sequence current has no path out of a closed delta, so it circulates in the loop and produces no output at the relay corners. Earth-fault protection needs a star point, a residual set, a dedicated neutral CT or a core-balance CT. A delta set covers phase functions only.

Why does the earth element read current on a balanced feeder?

A balanced feeder should read close to zero, and a steady reading means one of four things: an earth point at each end of the star point circuit, a core with a different ratio or class from the other two, an open or high-resistance secondary lead, or a burden that the cores cannot drive at that current. Each is a wiring or matching fault, not a setting problem.

Is the residual connection the same as a core-balance CT?

They measure the same quantity by different means. The residual connection sums three separate cores and therefore inherits their mismatch; a core-balance or zero-sequence CT links all three conductors through one core, so the sum is taken magnetically and mismatch does not arise. The core-balance unit is more sensitive for small earth-fault currents, at the cost of an extra device and its mounting space.

What ratio do I specify for a 300 A feeder?

A 300:5 core gives 5 A at full load in a star connection and 8.66 A in a delta connection, which is usually the practical choice for a feeder that will not grow. A 400:5 or 600:5 core leaves headroom for load growth but reduces the current available to sensitive earth-fault elements, so check the minimum fault current at the remote end before deciding.

Does the connection affect the class and burden I need?

Yes, for the delta in particular. The cores stop being independent, because current from one returns through the other two, so the connected burden per core is higher than the relay coil alone. Give the supplier the connection with the burden, and ask for the class to be confirmed against the calculated burden at the delta current rather than at the nameplate secondary current.