A surge arrester and a lightning arrester are the same device under two names. IEC 60099-4, the standard both are tested to, calls it a surge arrester; "lightning arrester" survives in older utility specification templates and in catalogue headings, ours included. The distinction that changes what you buy sits one level up: arrester, lightning rod, or low-voltage SPD.
Are a surge arrester and a lightning arrester the same device?
Yes. The name described a duty rather than a principle: a unit on top of a transformer that stood between the line and earth and took the surge before the winding did. Early units had a series spark gap and silicon-carbide blocks; when gapless zinc-oxide elements replaced them, the standard moved to "surge arrester" and the installed base kept the older word. Both remain in circulation because specification templates age more slowly than standards.
So an RFQ line reading "lightning arrester, 33 kV, 10 kA" is an order for an arrester, and the fields that follow it — rated voltage, continuous operating voltage, residual voltage at nominal discharge current, creepage distance — only exist on an arrester datasheet. A lightning rod has no rated voltage and no residual voltage, so nothing on those lines can be answered for a rod.
The device families and the selection route for 10 to 35 kV units are set out in lightning arrester types and how to select them. This page stays on the terminology and on what each of the three devices is actually tested to.
Three devices, three different jobs
The confusion is not between two names for one product. It is between three products that all carry the word lightning and all connect to earth. They differ in what they protect, where they sit, and how much current they are built to survive.
Read the table by column, not by row. The third column is where procurement decisions are usually made, and the fourth is what the supplier is asked to prove.
| Device | What it protects | Where it is installed | Energy it is built for | Governing standard |
|---|---|---|---|---|
| Lightning rod (air termination) | The structure and anything under its protective angle, by intercepting the stroke | Highest point: roof, gantry, tank top | Full stroke current, carried by the down conductor to earth | IEC 62305 series, lightning protection of structures |
| Medium-voltage surge arrester | Insulation at the terminals of a transformer, switchgear, cable or capacitor bank | In parallel with that equipment, phase to earth, as close as the layout allows | A share of the surge, clamped to a residual voltage below the equipment impulse withstand | IEC 60099-4 |
| Low-voltage SPD | Electronic and distribution circuits downstream of a board | Inside or beside a distribution board, in parallel with the busbar | Coordinated impulse current, declared by SPD type and test waveform | IEC 61643-11 |
Why a lightning rod cannot replace an arrester
A rod does one thing well: it offers the stroke a preferred attachment point above the equipment, and a down conductor takes that current to earth. It never limits the voltage at the transformer terminals. That is the whole of the argument, and it is the reason a site with a fully compliant rod system still loses transformers.
The overvoltage that damages insulation reaches the equipment along the phase conductor, either induced by a nearby stroke or transferred through the earthing and neutral system. Limiting it requires a device in parallel with the insulation that conducts at a defined voltage and stops conducting when the surge passes. A rod is not in parallel with the winding; it is above it.
There is a second effect that catches designers. A rod and its down conductor raise the potential of the whole earthing system during a strike, and that rise arrives at the low-voltage neutral and at cable screens as a common-mode surge. The remedy is bonding and coordinated arresters, not a taller rod. How the earth lead and the distance to the protected equipment spend the margin is treated in how the earth lead adds to the protection level.
What each device is actually tested to
Comparing a rod, an arrester and an SPD on one kA number is the most common error in a comparison sheet, because the test waveforms are not the same. An arrester is tested with an 8/20 µs discharge current and is quoted at a residual voltage for that current. An SPD declares an impulse current for Type 1 and a nominal discharge current for Type 2. A rod is tested as part of a protection system, not as a clamp.
| Device | Rating that appears on the datasheet | Values you will meet | What it lets the buyer decide |
|---|---|---|---|
| MV arrester | Nominal discharge current, 8/20 µs | Standard values are 1.5, 2.5, 5, 10 and 20 kA | Which residual voltage line applies, and therefore the protection margin against the equipment BIL |
| MV arrester | Rated voltage and continuous operating voltage | For a 10 kV system, a 13 kV rated unit is typical; DC 1 mA reference voltage 20 kV or more on the 10 kV overhead type | Whether the unit survives a phase-to-earth fault and the resulting voltage rise on the healthy phases |
| MV arrester | Line discharge class | Class assigned by system voltage and duty | Whether the unit absorbs the energy of a line discharge, not just a single impulse |
| LV SPD | Type, with Iimp at 10/350 µs or In at 8/20 µs | Declared per pole and per mode | Whether it may sit at the origin of an installation that has a lightning protection system |
| Lightning rod | None of the above | Material, diameter, height, protection angle | Only the position of the interception point, never the voltage at the equipment |
Gapless, gapped and drop-out: what the RFQ should name
"Lightning arrester" also hides three constructions that behave differently on the same line. The difference is where the gap sits — or whether there is one at all — and that decides the earthing, the inspection routine and the failure mode.
A gapless metal-oxide unit carries continuous power-frequency voltage across its own blocks, so its continuous operating voltage rating becomes a hard limit rather than a formality. In exchange it gives the lowest residual voltage for a given rated voltage and the simplest installation: one line connection, one earth connection. The YH (HY) composite arrester is built this way, in polymer housing, with the gapped variant offered where the specification still calls for a series gap.
An external-gap unit puts an air gap in series with the blocks, typically 60 to 130 mm on the piercing type used for 10 kV overhead insulated conductors, adjustable by sliding the mounting plates. Under normal voltage the gap and the block do nothing; when a surge arrives the gap breaks down and the power-frequency follow current burns in the open air instead of inside the housing. The trade is a discharge voltage that includes the gap, and a spacing that has to survive installation and inspection.
The drop-out version adds a disconnector in series with the earth connection. If the unit fails short, the disconnector operates and the unit hangs clear, so the line is not left with a permanent earth fault and the failure is visible from the ground. It is not a switching device and must not be operated as one.
| Construction | Where the gap sits | What the buyer gains | What to plan for |
|---|---|---|---|
| Gapless metal-oxide | No gap; blocks carry continuous voltage | Lowest residual voltage for the rating, simplest earthing, one condition indicator to read | Continuous operating voltage must not be exceeded; leakage or counter monitoring is the condition check |
| External series gap | 60–130 mm in air, above the block | Blocks see no continuous voltage; follow current burns outside the housing | Discharge voltage includes the gap; spacing set and verified on site |
| Drop-out | Internal gap with a disconnector to earth | A failed unit disconnects itself and shows its state visually | Clearance below the unit for the drop; the disconnector is not for switching |
Selection mistakes and what they cost
The first mistake is buying a rod package and recording the line as protected. It passes a visual inspection, so nothing surfaces until a transformer fails and the failure is attributed to the transformer rather than to the missing clamp.
The second is choosing the arrester by system voltage alone. Rated voltage has to cover the temporary overvoltage the unit will see during a phase-to-earth fault, which depends on how the neutral is earthed. A unit sized for an effectively earthed system installed on an isolated or resonant-earthed network is a warranty argument waiting to happen, and the replacement usually arrives after the outage, not before.
The third is ignoring the site. Pollution, salt and dust decide creepage, and altitude and ambient decide derating; a standard unit on a coastal or high-altitude site may pass the factory test and still track in service. The fourth is coordination: an SPD at the low-voltage board does not protect the medium-voltage winding, and two arresters of the same class in series do not add up to a lower residual voltage.
What to write into the RFQ
State the device by function, then give the numbers that decide it. A line that names the standard, the duty and the site conditions is answered with a configuration instead of a question list.
- System nominal voltage, highest system voltage, and the earthing arrangement of the neutral.
- Rated voltage and continuous operating voltage required, or the temporary overvoltage the unit must ride through.
- Residual voltage limit at the nominal discharge current, and the equipment impulse withstand it has to sit under.
- Nominal discharge current and line discharge class, or the utility standard clause that fixes them.
- Construction: gapless, external gap, or drop-out with disconnector; counter and disconnector accessories by suffix.
- Site conditions: ambient range, altitude, pollution level, seismic requirement, indoor or outdoor.
- Documents: type test report, routine test report, drawing for approval, and the packing needed for the transport route.
Where Nahu Group Fits
Nahu Group makes polymer-housed metal-oxide surge arresters from 3 kV to 220 kV, in station, line, capacitor, neutral and series-gap designs. The high-voltage lightning arrester lists three current types: the gapless YH (HY) composite arrester, the piercing-type external gap arrester for 10 kV overhead insulated conductors, and the YH5WS-TB drop-out arrester.
Send the system voltage and earthing arrangement, the residual voltage you need to stay under, the site conditions and the quantity, with the drawing or the utility clause the units must satisfy, and we return a model with its ratings and a drawing for approval. If the choice between gapless and gapped is still open, say so — the configuration follows from the duty, not the other way round.
Frequently Asked Questions
Is a lightning arrester the same as a surge arrester?
Yes, for the medium-voltage device. Both names describe a unit connected between line and earth that clamps a surge. IEC 60099-4 uses "surge arrester", and the older term persists in utility specifications. What is not the same device is a lightning rod, which intercepts the stroke but never limits the voltage at the equipment terminals.
Can a lightning rod protect a transformer on its own?
No. A rod sets where the stroke attaches and gives it a path to earth; it does nothing about the surge arriving on the phase conductor or the potential rise on the earthing system. Transformers behind a complete rod installation still need arresters at their terminals, sized to the winding impulse withstand.
Does an SPD replace a medium-voltage arrester?
No. An SPD to IEC 61643-11 protects low-voltage circuits downstream of a board and is rated in impulse current for that duty. It cannot clamp a medium-voltage surge, and it does not protect the transformer winding. Where both exist, they are coordinated by distance and by energy, not substituted for one another.
Which is better, gapless or gapped?
Neither in general. Gapless gives the lower residual voltage and the simpler installation, but the continuous operating voltage becomes a hard limit. A gapped unit keeps continuous voltage off the blocks, at the cost of a discharge voltage that includes the gap and a spacing that must be set on site. The duty decides.
Why does the rated voltage exceed the system voltage?
Because a phase-to-earth fault raises the voltage on the healthy phases, and the arrester has to stay intact until the protection clears the fault. The multiplier depends on the earthing arrangement. Sizing on nominal system voltage alone is how units end up failing in service on networks that are not effectively earthed.
What is a drop-out arrester for?
It adds a disconnector in series with the earth connection. If the unit fails short, the disconnector operates and the unit hangs clear, so the line keeps running instead of being held at earth by a failed arrester, and the fault is visible from the ground. It is not a switching device.
Sources and Further Reading
- IEC 60099-4 — Surge arresters, Part 4: Metal-oxide surge arresters without gaps for a.c. systems — rated voltage, continuous operating voltage, nominal discharge current and residual voltage limits quoted throughout this page.