An earthing switch passes its short-circuit tests on two computed comparisons, not on the kA at the top of the nameplate: the fault I²t must sit inside the rated I²t, and the asymmetrical peak inside the rated peak withstand. Loop resistance is the third check, judged against a declared baseline.
On a 12 kV indoor unit the numbers usually read 31.5 kA for 4 s, an 80 kA peak and an 80 kA making current, as on the JN15-12/31.5 indoor earthing switch. What follows turns a fault study into a pass or fail and states what the enquiry must contain.
The three checks that decide acceptance
A closed earthing switch is judged as a short-circuit path; each check reads a different line of the rating table.
| Check | Site quantity | Rating reference | Pass rule |
|---|---|---|---|
| Thermal | Fault I²t in kA²s | Rated current squared, times duration | Site I²t at or below rated, clearance inside duration |
| Dynamic | Peak current, or X/R | Rated peak withstand | Site peak at or below rated peak |
| Making | May the bay close onto a live circuit | Making current, class E1/E2 | Class stated, making current at or above site peak |
| Path | Loop resistance per pole, micro-ohms | Type-test value or commissioning baseline | Inside the tolerance written into the specification |
Thermal duty: turning kA and seconds into I²t
The short-time rating is a pair, not a current. A 31.5 kA, 4 s unit carries 31.5 × 31.5 × 4 = 3,969 kA²s. Any fault below that figure, cleared inside 4 s, is inside the thermal rating. Working in I²t also ends the assumption that lower current is safer: only if protection clears it faster.
| Case | Fault current | Cleared in | Fault I²t | Against 3,969 kA²s |
|---|---|---|---|---|
| A | 25 kA | 1.0 s | 625 kA²s | Passes, 16% used |
| B | 31.5 kA | 4.0 s | 3,969 kA²s | At the rating, no margin |
| C | 40 kA | 2.0 s | 3,200 kA²s | Passes on I²t, fails on peak |
| D | 40 kA | 3.0 s | 4,800 kA²s | Fails, 21% over |
| E | 20 kA | 5.0 s | 2,000 kA²s | Fails on duration |
Case E catches buyers. Duration is a rating in its own right, set at 0.5, 1, 3 or 4 s by family. Take it from the backup stage of the protection study: the switch is closed precisely when normal protection is out of service. Here I²t at 1 s would allow 63 kA, but the peak check cuts that to about 32 kA.
Dynamic duty: why the peak check binds first
Thermal ratings are quoted against symmetrical current; the first loop of a fault is not symmetrical. Peak is symmetrical current times √2 times κ, which rises with X/R, approximated as κ = 1.02 + 0.98 e−3R/X. On a 31.5 kA fault the symmetrical peak alone is 44.5 kA, so an 80 kA rated peak allows κ of 1.80.
| X/R at the busbar | κ, approx. | Peak at 31.5 kA | Against 80 kA |
|---|---|---|---|
| 5 | 1.56 | 69 kA | Passes with margin |
| 10 | 1.75 | 78 kA | Passes, under 3% margin |
| 15 | 1.82 | 81 kA | Fails |
| 25 | 1.89 | 84 kA | Fails |
So a 31.5 kA earthing switch is not usable on a 31.5 kA busbar beside a transformer, where X/R runs high. Ask for the peak or the X/R at the point of earthing; the 2.5 multiplier screens at κ of 1.77 and understates a stiff busbar. For the definitions, see how short-time and peak withstand differ.
Loop resistance: micro-ohms against a stated baseline
Resistance shows contact condition before heat does. Measure with a DC source of at least 100 A, switch closed, terminal to terminal on each pole, ambient temperature recorded. The path runs through the earthing bar, so a loose earth connection reads as a bad contact, and one reading is meaningless without a baseline taken when the contacts were new.
Four values make the comparison work: the type-test resistance the supplier declares, the routine value tied to the serial number, the commissioning value taken before energisation, and each maintenance value measured against it. Fix the acceptance number in your specification, because the standards set the method and the temperature-rise duty, not a universal micro-ohm limit: declared value plus permitted drift, plus a maximum spread between poles. Then nobody argues whether 40 micro-ohms against 32 is a defect. The path also crosses whatever provides the isolating distance; on a panel using a GN30-12 indoor rotary disconnector, those contacts sit in series during the test.
What to write into the RFQ, and what comes back
- System data: rated voltage, system earthing, fault level as symmetrical current plus peak or X/R, backup clearing time.
- Ratings: short-time current and duration, peak withstand, making current, class E1 or E2 where the bay may close onto a live circuit.
- Insulation and site: power-frequency and impulse levels, pollution level, ambient, altitude, seismic. The 42 kV and 75 kV levels suit 12 kV indoor work at pollution level II.
- Mechanical fit: panel type, pole spacing, operating side, manual or motor mechanism.
- Evidence: type test report citing IEC 62271-102 and IEC 62271-1, routine report per serial number with resistance per pole, dimensional drawing for approval.
- Marking: nameplate data required, units loose or fitted in the panel.
Read the type test report for the duties applied and the contact condition afterwards; the routine report for the 42 kV withstand, resistance and interlocks proven both ways. The model runs from 165 mm to 275 mm between poles, so a drawing that misses the panel becomes a site problem. The two report types are distinguished in type test versus routine test reports.
Selection mistakes and their commercial cost
The expensive errors are documentary and surface after the panel is built.
- Buying on current alone. A 31.5 kA offer chosen without duration or peak is a different device on a high X/R busbar; the cost lands at commissioning.
- Leaving the class blank. A compliant E0 unit cannot close onto a live circuit, so the bay cannot be earthed in the one scenario the switch exists for.
- No baseline. Without a commissioning reading, a real contact problem is argued as normal variation until it makes a hot joint.
- Using it as an isolator. It has no breaking duty; an operating sequence that opens a live circuit with it is an arc-flash event.
All four are cheaper to prevent at the enquiry. The rating and interlock side is covered in how to specify an earthing switch.
Where Nahu Group Fits
Nahu Group builds indoor earthing switches for 12 kV metal-enclosed switchgear, including the JN15-12/31.5 at 31.5 kA for 4 s, 80 kA peak and making, 42 kV and 75 kV levels and 2,000 operations, with pole spacing from 165 mm to 275 mm. The wider earthing switch is specified against the panel it sits in.
For a configuration, send the single-line diagram with earthing points marked, the fault level with peak or X/R, clearing time, panel type, pole spacing, quantity and site conditions.
Frequently Asked Questions
What current can an earthing switch carry?
In the closed position it carries the rated short-time withstand current for the rated duration, which keeps a section safe if it is re-energised from the remote end. It does not break or interrupt current. Compare I²t, not the headline kA.
Is 31.5 kA for 4 s the same as 31.5 kA for 1 s?
No. The 4 s rating is 3,969 kA²s; a 1 s rating would be 992 kA²s. Faster clearing uses less thermal rating, but the peak duty limits how much headroom is available, so both run together.
How should loop resistance be measured?
Switch closed, DC source of at least 100 A, terminal to terminal, one pole at a time, ambient temperature recorded. Keep the earthing bar connections tight so the reading reflects the contact, then compare each pole with the declared value and the other two.
Does a higher peak withstand mean a better switch?
No, it has to match the site. A high peak rating is wasted on a low X/R busbar, a modest one is a liability near a transformer. The making class and the mechanism that delivers it matter as much as the withstand figure.
Can the earthing switch isolate a section for work?
No. Isolation needs a disconnector or a breaker giving a visible distance; the earthing switch is closed afterwards, on a section already proved dead. Reversing those steps injures people, and no rating makes it acceptable.