The open delta connection of a potential transformer turns three single-phase units into a zero-sequence voltage sensor: close to 0 V while the network is healthy, and 100 V across the broken-delta terminals when one phase goes solidly to earth on an isolated 10–35 kV system. Everything else in the scheme exists to protect that one number, and most of the failures come from the parts that were left off the order.

Three-unit cast-resin voltage transformer set with three red phase units on one steel base, top primary bushings and front secondary terminal boxes

What the Open Delta Connection Actually Measures

The quantity is the residual voltage, usually written 3U0: the phasor sum of the three phase-to-earth voltages. In a healthy three-phase system those three voltages are equal and 120 degrees apart, so they sum to zero. When one phase is connected to earth, the neutral of the system shifts by exactly the missing phase voltage, the two healthy phases rise to line-to-line value, and the sum stops being zero. Three PTs measure that shift by reproducing each phase voltage at low level; connecting their residual windings in series puts the three reproductions end to end, and the voltage that survives is 3U0.

The number that matters is the ratio between healthy state and fault state. With residual windings rated 100/3 V — about 33.3 V each on a 10 or 11 kV system — a solid single-phase earth fault drives the healthy windings to 57.7 V and the faulted one to nearly zero. Two windings at 57.7 V, 60 degrees apart, add to 100 V across the open corner. That is why the relay input is a 100 V residual voltage input and why the specified output of the scheme is quoted as 100 V, not 300 V.

This is a measurement of system neutral displacement, not of the faulted phase and not of fault current. On an isolated or resonant-earthed network the earth-fault current is mostly capacitive and often a few amperes, well below any phase overcurrent setting. Voltage is the only quantity that responds reliably, which is why 10–35 kV distribution panels in the Middle East, South Asia and Africa are specified with a residual voltage winding almost as a matter of course.

How the Three Units Are Wired, and Why the Earthing Point Matters

Three single-phase units are mounted side by side, one per phase. Their primary windings are connected in star, and the star point is solidly connected to the earthed neutral of the system — on an isolated network that connection is the only earth reference the panel has, and it is what allows the neutral displacement to appear across the primaries at all. Each unit's main secondary winding feeds the metering and protection circuits in star, with the star point earthed at one point only, normally at the terminal block next to the transformers.

The residual windings are a separate circuit and are connected in series, polarity-aided: a1 to b1, a2 to b2, a3 to b3, leaving b3 and a1 as the two output terminals that go to the relay. This is the broken delta, and it is deliberately left open at the fourth corner. It is not a neutral, it is not earthed, and it must never be shorted. A shorted broken delta reads zero volts for ever and looks perfectly healthy on a multimeter.

The usual construction for a 10 kV panel is either three cast-resin units in a voltage-transformer truck or a three-unit cast set on a single base, which keeps the phase spacing and the star-point links fixed at the factory. Either way the second bushing on each single unit is the star-point terminal, not a second phase connection; leaving it floating is the same electrical mistake as removing the earth link, and it produces erratic residual readings that are hard to diagnose afterwards.

Single indoor JDZ-10 cast-resin voltage transformer with two primary bushings mounted above an exposed laminated steel core

What Voltage Appears at the Broken-Delta Terminals

The table below is the one worth keeping with the commissioning file. It converts a relay reading into a diagnosis, which is the fastest way to separate a real earth fault from a wiring mistake during energisation.

Condition on the networkResidual winding voltageBroken-delta outputWhat it usually means
Healthy, balanced33.3 V each, 120° apart0–3 VNormal. The small figure is system unbalance plus PT ratio error.
Normal load unbalanceSlightly unequal1–5 VNormal. Do not set the pickup inside this band.
Solid single-phase earth fault57.7 V on two, near 0 V on the faulted phase100 VReal earth fault. Definite pickup, then time delay.
Arcing or intermittent earth faultFluctuatingBursts toward 100 VReal fault, but the reading chatters; a 1–3 s delay is what makes it usable.
Two earth faults on different phasesComposite57–100 VEarth fault plus overcurrent; treat as a double fault on an isolated system.
One primary fuse blown0 V on one windingAbout 33 V standingNot a fault. One third of full scale is the fuse signature.
Broken delta shorted by a test linkCorrect0 V alwaysScheme dead, panel looks healthy. Check the links before blaming the relay.

Two signatures are worth memorising. A standing residual of roughly one third of full-scale, with no earth fault on the system, is almost always a blown primary fuse or one unit not connected; the missing winding removes a third of the sum. A standing residual of roughly two thirds of full-scale points the other way, at polarity, because a reversed winding produces twice one winding voltage instead of cancelling.

Which Nameplate Fields Decide Whether the Scheme Works

A potential transformer can be correct in every respect and still be wrong for this scheme, because the residual winding is an option. The unit in the photograph below is a JDZ10-10 for 10 kV indoor service with two secondaries, both rated 100 V, class 0.2, 15 VA. It is a perfectly good metering transformer, and it cannot produce 3U0, because neither of its secondaries is a residual winding. The same model is available with an open-delta residual winding; the nameplate is what tells the two apart.

Indoor JDZ10-10 voltage transformer with English nameplate listing two 100 V class 0.2 secondaries and a clear terminal cover

Read four fields before accepting a delivery. The residual winding rated voltage should be 100/3 V on a 10–35 kV system; if the works ordered 100 V residual windings, the open corner will deliver 300 V at a solid fault and the relay input will be driven into saturation. The residual accuracy class is normally 3P or 6P, and its rated burden in VA is small — a few tens of volt-amperes — so a damping resistor sized on the main winding's burden will overload it. The voltage factor should be 1.9 for continuous service, because on an isolated network the healthy-phase windings sit at 1.73 times rated for as long as the earth fault lasts.

Nameplate fieldWhat to checkIf it is wrong
Residual winding rated voltage100/3 V per unit for 10–35 kV100 V windings give 300 V at the open corner; relay saturates or is damaged
Number and duty of secondariesOne metering, one protection or residual; not two metering windingsNo 3U0 available at all; scheme cannot be commissioned
Residual accuracy class3P or 6PClass 0.2 metering winding used for protection: no declared behaviour at high voltage factor
Residual rated burdenMatch to relay input plus damping resistorWinding overheats; the resistor chosen for the main winding is far too heavy
Rated voltage factor1.9, continuousOverheating or insulation stress during a sustained earth fault
Insulation level12/42/75 kV for a 10 kV systemWrong class rejected at type-test review or at site inspection

Why One Reversed Unit Cancels the Sum

Series connection only adds if the three windings point the same way. Every residual winding is marked a and b for polarity, and the chain has to run a1-b1, a2-b2, a3-b3. One unit connected b-to-b reverses its contribution, and the arithmetic stops being a sum of three equal phasors 120 degrees apart: the reversed winding now adds twice its own voltage instead of cancelling.

On a healthy network with 33.3 V windings, the result is a standing 67 V at the relay, two thirds of the fault-level output, with nothing wrong on the system. Depending on the setting, that either holds the earth-fault element picked up permanently or blocks a scheme that has a startup supervision threshold. Both outcomes cost the same thing: an afternoon of chasing a fault that is not there, or worse, an operator who learns to ignore the alarm.

The check belongs in commissioning, not in fault-finding. Inject three-phase rated voltage in correct phase rotation with the relay disconnected, and the open corner should read close to zero — a few volts, consistent with the PT errors. Then reverse one unit's residual leads deliberately: the reading must jump to roughly two thirds of full scale. If it does not move, the wiring is not what the drawing says. The ratio and polarity tests on the individual units described in the PT testing sequence catch a wrongly marked unit before it reaches the panel.

A Zero-Sequence Setting Worked Through on 11 kV

Take an 11 kV isolated or resonant-earthed busbar with three single-phase PTs, main secondaries 100/√3 V, residual windings 100/3 V. Phase-to-earth primary voltage is 11000/√3, about 6351 V, against 57.7 V on the main secondary. At a solid single-phase earth fault the residual voltage is three times that phase voltage, 19.05 kV primary, which is also √3 times the 11 kV system voltage. Scaled by the residual winding ratio, 19.05 kV appears as 100 V at the open corner.

A pickup of 15 V therefore corresponds to 2.86 kV of primary 3U0, or 15 percent of the full fault-level value. The table below converts the usual settings into primary terms so the number can be checked against the network rather than against a habit.

Relay pickup (secondary)Primary 3U0Share of full-scale fault outputWhat it responds to
10 V1.9 kV10 %High-resistance and incipient faults; closest to normal unbalance, so the margin over the standing reading must be verified
15 V2.9 kV15 %Common starting point for alarm on an isolated busbar
20 V3.8 kV20 %Firm alarm, tolerant of unbalance and PT error
30 V5.7 kV30 %Trip-level setting where nuisance operation is the greater risk

Two constraints sit outside the arithmetic. First, 3U0 is bus-wide: on a board with six feeders it says that something on this bus is earthed, not which feeder. Selecting the feeder needs a directional element comparing U0 with I0, or a core-balance current transformer per feeder. Second, the pickup has to clear the standing value measured at commissioning by a comfortable factor, typically two to three times, otherwise load unbalance on a long rural feeder will operate it. The delay does the rest: 1–3 s is enough to ride through arcing bursts and switching transients without hiding a real fault.

Four Ways to Obtain 3U0, and the Two That Fail

Most of the arguments at the drawing-review stage come from treating these as interchangeable. They are not, and only three of the five arrangements below can deliver a usable residual voltage.

ArrangementHardwareHealthy outputOutput at solid earth faultUsable for 3U0?
Three single-phase PTs, residual windings in broken delta3 units plus star-point linksAbout 0 V100 VYes; the standard 10–35 kV switchgear scheme
Three-phase five-limb PT with residual winding1 unitAbout 0 V100 VYes, if the residual winding is ordered with the right ratio
Three-phase three-limb PT, neutral not earthed1 unitDepends on unbalanceDistorted, not proportionalNo; the core has no return path for zero-sequence flux
Two PTs in V/V2 unitsLine voltages onlyNo output at the open cornerNo; there is no path for a zero-sequence quantity
Core-balance CT around the three cores1 CT per feederNear 0 AResidual current 3I0It measures current, not voltage; complementary, not a substitute

The V/V row is the one that catches refurbishment projects. Two PTs connected phase to phase are entirely adequate for metering and for voltage-based protection that only needs line quantities, which is why they appear on older drawings and on cost-reduced panels. They have no residual output, so a scheme inherited from such a drawing will have an earth-fault relay with nothing connected to it — and it will pass a functional test with an injected voltage, because the injection bypasses the missing transformer.

Selection Mistakes and What They Cost

These are the failures that appear between delivery and energisation, in the order they usually surface. None of them is caught by a functional test on the relay alone.

MistakeHow it surfacesCommercial and schedule cost
PTs ordered without a residual windingWiring check at commissioning: open corner reads zero under all conditionsReplacement units, new FAT, energisation delayed by weeks
Residual windings specified at 100 V instead of 100/3 V300 V at the open corner during a primary injection testRelay input saturated or damaged; either derate with a divider or replace the units
V/V arrangement carried over from an old drawingNo U0 circuit exists to connectEarth-fault protection out of service on a network that depends on it
One unit connected in reverse polarity67 V standing on a healthy busNuisance alarms, disputed protection settings, site investigation time
Test link or shorting bar left across the open cornerReads 0 V during a real fault; nothing operatesUndetected earth fault, insulation damage, outage after the event
No damping resistor on an isolated networkFerroresonance after single-pole switching; fuse or PT failureRepeat failures that look like a product fault; see why the PT is the usual suspect
Primary fuse alarm contact not wired33 V standing residual read as an earth faultRepeated call-outs for a fuse that nobody replaced

What to Write Into the RFQ and the Datasheet

The residual winding is an option on most 10–35 kV PT ranges, so a requirement that is not written down will not be delivered. The list below is written as requirements rather than preferences, which is what a supplier needs in order to quote a set that can be commissioned without argument.

RequirementWhat to state
Network earthingIsolated, resonant-earthed or effectively earthed, and the system voltage
Insulation level12/42/75 kV for 10–11 kV; the matching level for 33 kV where applicable
Ratio per phaseFor example 11000/√3 : 100/√3 V, with the star point brought out
SecondariesNumber, class and burden of each; metering and protection kept on separate windings
Residual windingRated voltage 100/3 V, class 3P, rated burden in VA, voltage factor 1.9 continuous
DampingWhether a damping resistor across the broken delta is supplied, and its value and thermal rating
Polarity markinga and b marked on every residual winding, with the three units identified as one set
FusingPrimary fuse rating and whether the striker or alarm contact is wired to a terminal
Earthing provisionsStar-point link and earthing terminal for the primary star, separate earth stud for the secondary star
Tests and documentsType test reports to IEC 61869-3, routine test report per unit, ratio and polarity record, drawings for approval
MarkingNameplate in English, with ratio, classes, burdens, voltage factor and insulation level
PackingSet packed as one unit so the three phases cannot be mixed with another batch on site

Two of those rows are worth arguing about at quotation stage rather than later. The damping resistor belongs with the transformer supplier, because its value depends on the residual winding's thermal rating, not on the relay; a resistor sized by the panel builder from the main winding's burden has cooked more than one residual winding. And the batch marking matters more than it sounds: three units from different production runs will have slightly different ratio errors, and the standing residual on a healthy bus is the sum of those errors. Mixed sets are a routine source of a few volts of permanent offset that nobody can explain.

Where the panel also carries current transformers on the same feeders, the two device types are usually ordered together, and the differences in how they are specified — series against parallel, burden in ohms against burden in volt-amperes — are set out in the CT and PT comparison for one incomer. Keeping the two schedules separate but issued together is the simplest way to avoid a CT burden being copied onto a PT line.

Where Nahu Group Fits

Nahu Group manufactures cast-resin voltage transformers for indoor and outdoor medium-voltage service, including single-phase units for 10–12 kV panels, three-unit cast sets on a common base for ring-main and distribution switchgear, and 35 kV and 40.5 kV outdoor units. The voltage transformer lists the models with their ratios, classes and burdens, so a residual winding requirement can be checked against a real unit rather than assumed from a family name.

For a three-unit set intended for earth-fault detection, the closest starting points are the JDZX10-10 indoor unit with a residual winding, which is ordered as three pieces with the star-point links, and the 3XZNOLP-10M three-unit cast set, which arrives assembled on one base for a 10 kV truck. For metering-only positions the JDZ10-10 two-winding unit is the equivalent without a residual winding, and it is exactly the unit that cannot be used for this scheme.

To get a configuration, send the single-line diagram or the VT schedule, the system voltage and earthing method, the required ratio and secondary classes, the residual winding rating you need, and the quantity per panel. If the panel is new rather than a retrofit, the phase spacing and the truck dimensions are worth including as well, because a three-unit set and three separate units do not occupy the same space.

Frequently Asked Questions

Is an open delta connection the same as a broken delta?

In this context, yes. Both names describe three residual windings connected in series with one corner left open, so the output is the phasor sum of the three windings. Broken delta is the more precise term because it emphasises that the delta is deliberately incomplete, which is what allows a zero-sequence voltage to appear across the two output terminals.

Can two PTs in V/V be used for earth-fault detection?

No. A V/V set measures line voltages only, and a zero-sequence quantity has no path through it, so there is nothing to connect to a residual voltage relay. A scheme inherited from a V/V drawing will have an earth-fault relay with open terminals, and it will still pass a functional test if the test voltage is injected at the relay.

What should each residual winding be rated at?

For a 10 to 35 kV system, 100/3 V per unit, about 33.3 V. Three of those in series give close to 0 V in health and 100 V at a solid single-phase earth fault. If the units are ordered with 100 V residual windings, the same fault drives 300 V at the open corner and saturates the relay input.

Why does the broken delta read about 33 V when no phase is earthed?

That is one third of full-scale output, and it usually means one residual winding is contributing nothing, either because a primary fuse has blown on that phase or because one unit was never connected. The remaining two windings sum to about one third of the fault-level voltage, which reads like a permanent earth fault until the fuse is replaced.

Should the open corner of the broken delta be earthed?

No. The broken delta is a measuring circuit, not a neutral, and it must be left unearthed with both output terminals going only to the relay. Earthing one corner creates a parallel path that changes the reading and can circulate current through the residual windings. Earth the primary star point and the main secondary star point, each at one point only.

Can one three-phase five-limb PT replace three single-phase units?

Yes, provided it is ordered with a residual winding of the right ratio and the neutral is earthed. The five-limb core gives zero-sequence flux a return path, which a three-limb core does not, so a three-limb unit with an unearthed neutral produces a distorted reading that cannot be used for protection settings. Confirm the residual winding on the nameplate.