A potential transformer accuracy class is the maximum voltage error, in percent, that a winding is allowed to show at rated voltage and rated burden. A class 0.2 unit may therefore read 0.2% high or 0.2% low, with up to 10 minutes of phase displacement, but only between 80% and 120% of its rated primary voltage and between 25% and 100% of its rated burden at 0.8 power factor. Outside either window the class carries no guarantee at all, which is the root cause of most metering disputes that reach a supplier after the panel has been energised.
What the class number actually measures
Voltage error, also called ratio error, is (Kn × Us − Up) / Up expressed as a percentage, where Kn is the rated transformation ratio and Up and Us are the actual primary and secondary voltages. A transformer with a perfectly wound ratio still shows error, because the magnetising current and the winding impedance drop a small voltage, and both change as the load on the secondary changes. The class number is the outer limit of that drift under stated conditions.
Phase displacement is the angle between the primary voltage vector and the reversed secondary voltage vector, quoted in minutes because the angles involved are small. It matters because energy is measured as the product of voltage and current, so an angular error rotates the secondary voltage against the current by the same angle: at unity power factor the term vanishes, while at 0.8 lagging ten minutes of displacement is worth roughly 0.22% of the measured energy. That is why a unit can sit inside its ratio limit and still shift a tariff reading, and why the two numbers are always quoted as a pair.
Both limits are specified at rated frequency and at a stated burden, so a class is a four-part statement: a percentage, a minute value, a voltage window and a burden window. Drop any one of the four from a purchase specification and the supplier is free to choose it, usually in the direction that costs the factory less. This is the single most common gap in specifications written from a catalogue page rather than from the standard.
The measuring classes from 0.1 to 3.0
IEC 61869-3 defines five measuring classes. The class number is the permitted voltage error at rated voltage and rated burden, and the phase limit is a separate column of the same table. Class 3.0 carries no phase requirement at all, which is why it turns up on indication and auxiliary circuits rather than on a billing core.
| Class | Voltage error (±%) | Phase displacement (±min) | Phase displacement (±crad) | Where it is normally used |
|---|---|---|---|---|
| 0.1 | 0.1 | 5 | 0.15 | Laboratory and calibration reference |
| 0.2 | 0.2 | 10 | 0.30 | Revenue metering, utility billing points |
| 0.5 | 0.5 | 20 | 0.60 | Commercial metering, sub-metering |
| 1.0 | 1.0 | 40 | 1.20 | Panel instruments, check metering |
| 3.0 | 3.0 | Not specified | Not specified | Indication, auxiliary and control circuits |
Read the table as pairs rather than as a ranking. Class 0.1 belongs to laboratory work, 0.2 to high-value metering points, 0.5 to ordinary commercial metering and 1.0 to instruments a person reads through a panel door. A 0.2 unit bought for a feeder that spends most of its life at 15% of rated voltage is money spent outside the window where the class applies, and a 1.0 unit asked to carry a tariff core is an argument waiting to happen at the first meter test.
The same limits are reproduced in national standards that follow the IEC text, so a class 0.2 core quoted to GB/T 20840.3 or to an older IEC 60044-2 project should produce the same numbers. What differs between standards is the test list and the insulation values, which is why the quoting document matters as much as the class.
Why 0.2 holds only between 80% and 120% of rated voltage
Below 80% of rated voltage the core is lightly excited. The magnetising branch then draws a current that is large relative to the signal being transformed, and the ratio error drifts away from the value measured at rated voltage. Above 120% the core approaches saturation, excitation current rises steeply and the error moves in the other direction. The standard places the window at those two points because that is the band in which the error of a normal design stays predictable.
The practical consequence is narrower than most datasheets suggest. A unit on a feeder sitting at 103% to 108% of nominal is comfortably inside its class. The same unit feeding a generator voltage regulator, an undervoltage protection scheme or a long rural feeder that sags to 85% is being asked for accuracy it was never specified to deliver, and the failure will appear as a slow metering drift rather than as a fault.
If an application genuinely needs accuracy outside 80% to 120%, it has to be agreed separately and demonstrated by test on the actual design. No class label covers it, and no amount of extra core area turns a standard 0.2 unit into a guaranteed 0.2 at 60% voltage. When a tender asks for accuracy at 50% voltage, the honest answer is a special design with a test report, not a standard catalogue number with a reassuring sentence beside it.
The burden window is 25% to 100%, and the power factor counts
The second half of the class statement is the load the secondary circuit presents. IEC 61869-3 splits rated outputs into two families: range I, 1.0 to 10 VA at unity power factor, where accuracy holds from zero burden up to the rated value; and range II, 10 to 100 VA at 0.8 lagging, where accuracy holds only from 25% of rated burden. A 50 VA range II unit driving a 6 VA metering loop therefore sits below its own window, and the class does not apply even though nothing is overloaded.
This is where over-specified panels lose the accuracy they paid for. A buyer adds up the meter, the transducer and the voltmeter, rounds up to the next standard output for margin, and ends up with a transformer that is accurate only when loaded far more heavily than the panel will ever load it. The correct move runs the other way: calculate the real burden, add a modest allowance for the wiring, and choose the smallest rated output that covers the total at the power factor the instruments actually present.
Two-winding units add a subtlety that datasheets often omit. The windings interact magnetically, so the standard requires an output range to be declared for each winding, with the other winding loaded anywhere from zero to its rated value during the accuracy test. A two-winding unit specified without those ranges has an accuracy claim that cannot be reproduced on a test bench.
Protection windings 3P and 6P are judged over a different window
Protection cores use the same percentage convention with a P suffix, but the evaluation points are not the metering ones. The limits for 3P and 6P apply at 5% of rated voltage and at rated voltage multiplied by the rated voltage factor, and at 2% of rated voltage the permitted errors double. That range is chosen for the conditions a relay actually sees: a voltage that has collapsed during a close-in fault, and a voltage that has risen on the healthy phases during an earth fault.
| Class | Voltage error (±%) | Phase displacement (±min) | Evaluation points |
|---|---|---|---|
| 3P | 3.0 | 120 | 5% of rated voltage and rated voltage × voltage factor |
| 6P | 6.0 | 240 | 5% of rated voltage and rated voltage × voltage factor |
| 3P or 6P at 2% Un | Twice the class value | Twice the class value | 2% of rated voltage |
Two rules follow from that table. A residual or broken-delta winding must be class 6P or better, because the relay has to resolve a small zero-sequence voltage sitting on top of three large phase voltages, and a metering-grade winding will not do the job. And a protection winding is never a substitute for a metering winding: it is deliberately allowed a much larger error and its phase behaviour at normal voltage is not characterised to a revenue standard. Panels that economise by sharing one winding between the meter and the earth-fault relay usually discover the problem during commissioning tests, when the residual voltage reads too low to trip.
Reading a real rating grid: 0.2 at 15 VA is half the specification
Open the page of any indoor cast-resin unit and the ratings appear as a grid rather than a single class. On the JDZX10-10, for a 10000/√3 V primary with a 100/√3 V metering secondary and a 100/√3/3 V residual winding, the class follows the output: 0.2 at 15 VA, 0.5 at 30 VA, 1 at 60 VA, 3 at 150 VA, and 6P (3P) at 50 VA, against a thermal maximum of 200 VA. The same frame is offered at every one of those ratings, and the class printed on the nameplate is only meaningful next to the output printed beside it.
Three things are worth taking from that grid. The thermal maximum is a temperature limit, not an accuracy rating, so buying 200 VA and expecting 0.2 is a misreading that shows up as a failed meter test. The residual winding carries its own class and its own thermal rating, referred to eight hours because it is loaded only while an earth fault lasts. And the insulation level printed beside the ratios, 12/42/75 kV on the 10 kV row of that page, is a national convention for Um, power-frequency withstand and lightning impulse: a European datasheet quoting 12/28/75 kV for the same Um is not a weaker transformer, it is the same class of equipment tested to a different convention.
Phase-to-earth units add one more line that buyers lose in the copy-paste: the rated voltage factor, always as a pair. 1.2 continuous, 1.5 for 30 s, 1.9 for 30 s on effectively earthed systems, 1.9 for 8 h on isolated or resonant-earthed systems. A unit rated 1.9/30 s installed where a fault can persist for hours will not fail on the first earth fault. It will saturate, drift out of class and overheat, and the accuracy that was quoted is gone long before the insulation is.
Selection mistakes and what they cost
The failures that come back to a supplier are rarely about a wrong class number. They are about a class quoted without the conditions that make it true, and they surface at the worst moment, which is the meter test at commissioning or the first month of billing.
| Mistake | What shows up on site | Commercial cost |
|---|---|---|
| Class quoted without the output it holds at | Unit passes the factory routine test, fails the utility meter test | Re-test, replacement and delayed energisation |
| 50 VA range II unit in a 6 VA loop | Slow drift below 25% burden, disputed readings | Retrofit with a lower-rated unit, back-billing argument |
| Metering winding used for earth-fault detection | Residual voltage too low, relay does not pick up | Rewiring to a 6P core, another outage window |
| 0.2S requested for a voltage transformer | Supplier ships a different class or a re-labelled unit | Type-test report cannot be produced, goods rejected |
| Voltage factor quoted without its duration | Overheating and lost accuracy after a long earth fault | Unit replaced inside its first year, spares mismatch |
Two further traps deserve a line each. Asking for a 0.2S voltage transformer marks a specification copied from a current transformer datasheet, because S classes exist only for CTs; the CT accuracy class table explains why the S row exists there and not here. And a two-winding unit specified without an output range for each winding cannot be type tested to a defined condition, so the accuracy claim on the quotation is a calculation rather than a measurement. Both errors are cheap to fix on paper and expensive to fix after the panel is built.
What to write into the RFQ and the datasheet
A voltage transformer requirement that cannot be misread has six elements, and each missing one moves a decision from the buyer to the supplier. The wording below is deliberately written as requirements rather than as preferences, because that is what a quotation is priced against.
- System voltage and earthing arrangement, from which the primary rating and the voltage factor follow.
- Ratio in full, stating whether the primary is phase-to-earth or phase-to-phase.
- Class and the output at which that class applies, with the power factor and the burden range spelled out.
- Rated voltage factor with its duration, not the multiplier alone.
- Insulation level with the convention named, IEC or national, so two quotes can be compared.
- Tests and documents: routine accuracy and partial-discharge records with measured values, a type-test report for the exact design, and an outline drawing for approval.
Add the quantity, the terminal orientation and the primary fuse protection, because those three items turn a catalogue number into a delivered unit. A sentence such as "10/√3 kV / 100/√3 V / 100/√3/3 V, class 0.2 at 15 VA, 0.8 lagging, voltage factor 1.2/1.9/8 h, insulation 12/42/75 kV, IEC 61869-3, routine accuracy record with measured phase displacement" closes every hole that "10 kV, 0.2 class" leaves open. The nameplate line-by-line reading covers what each of those fields fixes on the plate itself.
Where Nahu Group Fits
Nahu Group builds indoor cast-resin voltage transformers for 3-12 kV and 15-24 kV systems, including the single-phase JDZX10-10 and the JDZX11-15 and JDZX11-20 families, alongside current transformers, metering units and switchgear. Ratings are quoted per class and per output, so the class on an offer is tied to the burden it holds at rather than to a headline figure, and the wider voltage transformer range covers oil and cast-resin designs for both indoor and outdoor service.
To get a configuration, send the system voltage and earthing arrangement, the ratio, the class you need and the burden it has to hold, the voltage factor with its duration, the insulation convention and the quantity. A drawing is issued for approval before production, so the terminal orientation, the mounting and the fuse arrangement match the panel the unit goes into. How each rating is proven at routine test describes the records that travel with the shipment.
Frequently asked questions
Is a 0.2 class the same as 0.2% accurate?
No. It is 0.2% accurate at rated voltage and rated burden, with a phase displacement inside 10 minutes, and only between 80% and 120% of rated voltage and 25% to 100% of rated burden. Below 25% burden or outside the voltage band the class does not apply, even though the transformer may still be perfectly healthy.
Why is there no 0.2S voltage transformer?
The S suffix belongs to current transformers, where it extends the accuracy range down to 1% or 5% of rated current for revenue metering. Voltage transformers are specified over a voltage band instead, so there is nothing for an S class to extend. A VT datasheet offering 0.2S is either a translation error or a copy from a CT sheet, and the type-test report will not exist.
Does a higher VA rating make a voltage transformer more accurate?
No. VA is the burden the class is guaranteed into, not a quality grade. A larger rated output generally means a larger core that holds its class into a heavier load, but if the panel presents only a few VA the unit runs below the 25% floor of the range II window and its class no longer applies.
Can a 3P winding be used for metering?
Not for billing. A 3P winding permits 3% voltage error and 120 minutes of phase displacement, which is fifteen times the metering error budget and enough to shift a tariff reading by a visible margin. Use a separate 0.2 or 0.5 winding for the meter and keep the protection winding on its own circuit to the terminal block.
What happens if the burden is below 25% of rated output?
The accuracy guarantee stops. In range II the standard guarantees the class only from 25% to 100% of rated burden at 0.8 lagging, so a 50 VA unit loaded to 5 VA is outside its window and may drift. The remedy is a smaller rated output, or a range I unit where accuracy holds from zero burden.
Does the accuracy class still hold during an earth fault?
For the metering winding, no: the voltage moves outside the 80% to 120% band by design. That is what the protection winding is for. Its 3P or 6P limits are evaluated at 5% of rated voltage and at rated voltage times the voltage factor, which is the range the relay needs while the fault is being cleared.
Sources and further reading
Limits quoted in this article follow IEC 61869-3:2011, Instrument transformers, Part 3: Additional requirements for inductive voltage transformers, read together with IEC 61869-1:2023, Part 1: General requirements. Rating figures for the JDZX10-10 are taken from the product page in this site's catalogue.