A potential transformer nameplate carries about a dozen lines, and four of them decide whether the unit can be accepted on site: rated primary voltage, rated secondary voltage, accuracy class together with the rated output that belongs to it, and rated voltage factor. Read those four against the drawing before anything else, because every remaining line is a check on how the unit will behave once it is energised at full system voltage.
The 12 kV trap: the ratio line is not the system voltage
The first line an engineer checks is the rated voltage ratio, printed as Ur1/Ur2 and read as 10000/100 V on a 10 kV unit. That is a no-load transformation ratio, and the meter multiplies its reading by 100 to recover the primary value. It is not the insulation class of the panel. A transformer marked 10000/100 V is routinely installed in switchgear whose highest voltage for equipment is 12 kV, because 10 kV is the nominal system voltage and 12 kV is the Um that the insulation is designed for. Buyers who compare the ratio line with the panel's Um reject a correct nameplate every month.
The second number matters just as much, and it is the one most often transcribed carelessly. A 100 V secondary is a phase-to-phase quantity; a 100/√3 V secondary, which reads 57.7 V, is a phase-to-earth quantity. Panels wired for one will misreport every earth-fault related value if a unit with the other is delivered, and the error is a factor of 1.73 that stays hidden until someone compares a meter reading with a clamp meter.
On outdoor units the plate sits on the front face of the casting, as on the JDZW-10R outdoor voltage transformer shown above, and it is usually the only place the ratio, the burden and the insulation level appear together. Photograph it at goods-inward inspection and file the image with the test certificate. When a unit is replaced three years later, that photograph is the only record of what was actually installed, because the switchgear drawing will show a generic symbol and the purchase order will show a model code that may already have been superseded.
Seven nameplate lines and what each one fixes
The table below is the acceptance check a project buyer can run in five minutes at the warehouse, before the unit goes into the panel. The third column is the part that matters commercially: what goes wrong when the line is misread, not when the unit is faulty.
| Nameplate line | What it fixes on site | What a misread costs |
|---|---|---|
| Rated primary voltage Ur1, e.g. 10000 V | The multiplier used by the meter and the relay | Systematic billing error for a whole tariff period, discovered only at a meter test |
| Rated secondary voltage Ur2, 100 V or 100/√3 V | Whether the secondary is a line or a phase-to-earth quantity | Every phase-to-earth reading wrong by 1.73, including residual voltage |
| Accuracy class with its rated output | Which core may be used for tariff work | Tariff core specified at a burden the panel exceeds; class no longer guaranteed |
| Rated output per class and maximum output | How much burden may be connected, and at what temperature limit | Relay and meter chain sized to the maximum output; accuracy drifts outside the class |
| Rated voltage factor, 1.2 or 1.9 | Behaviour of the unit during a single-phase earth fault | Unit over-excited on an unearthed system; insulation ageing or failure |
| Rated insulation level, e.g. 12/42/75 kV | Whether the unit matches the switchgear insulation co-ordination | Rejected at commissioning test; clearances inside the panel differ from the drawing |
| Rated frequency, 50 or 60 Hz | Flux density in the core and the resulting ratio error | A 60 Hz unit on a 50 Hz system saturates early; error leaves the class |
When the ratio line has three numbers, a residual winding is fitted
A unit with an open-delta winding prints a third number: 10000/100/100 V, or on a phase-to-earth design 11000/√3 / 110/√3 / 110/√3 V, or with a 100/3 V residual winding for a broken-delta connection. That third figure is a separate secondary winding with its own accuracy class and its own rated output, listed further down the plate. It is not a tolerance band and it is not a tapping range, and a buyer who reads it as either will specify the wrong winding arrangement.
The residual winding is where earth-fault protection is either made or lost. Its class is written separately, typically 3P or 6P, and its rated output is small because it only ever drives a relay coil. If the third number is missing from the nameplate but the drawing shows an open-delta connection, the unit cannot supply the scheme at all. The wiring and the voltage that appears across the broken delta are covered in the open delta connection of potential transformer walk-through, including the zero-sequence setting derived from it. Where three single-phase units are assembled into a set, the arrangement of the secondaries is dealt with in the three-phase PT connection diagram comparison, and the nameplate is what tells you which of those arrangements the units were built for.
Accuracy class and rated output are one line, not two
A class on its own commits the manufacturer to nothing, because the limits apply only at the burden printed beside it. That is why the plate reads 0.5 / 30 VA rather than 0.5. Specify the class and the VA together, and specify the VA as the burden the panel will actually present, not as a round number that looks generous.
| Class | Voltage error at 80–120% Ur | Phase displacement | Where it is normally used |
|---|---|---|---|
| 0.1 | ±0.1% | ±5 min | Laboratory reference, calibration |
| 0.2 | ±0.2% | ±10 min | Tariff and revenue metering |
| 0.5 | ±0.5% | ±20 min | Check metering, panel instruments |
| 1.0 | ±1.0% | ±40 min | Indication only |
| 3 | ±3.0% | 120 min | Coarse indication, no phase-sensitive duty |
| 3P | ±3.0% | ±120 min | Protection and residual voltage |
| 6P | ±6.0% | ±240 min | Protection where a coarse signal is acceptable |
The 80–120% band is the other half of the commitment, and it is frequently overlooked. Metering classes are guaranteed inside that range only; protection classes are specified over a much wider band, which is what makes them usable during a fault when the voltage has collapsed or risen. A 0.2 class unit asked to hold accuracy at 40% of rated voltage has no guaranteed limit there, and no test report will contradict you on that point.
Maximum output is a temperature limit, not a second accuracy rating
The highest VA figure on the plate, often marked as maximum or thermal limiting output, is the apparent power at which the winding reaches its permitted temperature rise. It is not an accuracy class and no error limit applies at that load. A unit rated 0.2 / 15 VA with a maximum output of 200 VA is a 0.2 class transformer up to 15 VA and a heater above it.
A real sheet shows how the two figures separate. On the JDZ10-10 the ratio is identical across the rating table and only the permitted error changes with the column, which is exactly why the class has to be ordered together with a VA figure rather than on its own. The table below is the one to copy into a comparison sheet, because two suppliers quoting the same ratio can still be quoting different columns.
| Rated voltage ratio | Class 0.2 | Class 0.5 | Class 1 | Class 3 | Maximum output | Insulation level (kV) |
|---|---|---|---|---|---|---|
| 3000/100 V | 15 VA | 30 VA | 60 VA | 150 VA | 200 VA | 3.6/25/40 |
| 6000/100 V | 15 VA | 30 VA | 60 VA | 150 VA | 200 VA | 7.2/32/60 |
| 10000/100 V | 15 VA | 30 VA | 60 VA | 150 VA | 200 VA | 12/42/75 |
Read across the 10000/100 V row and the commercial problem becomes visible. The permitted burden grows tenfold from the first column to the fourth, and the price follows the core, not the ratio. Ordering by price alone usually means ordering the 150 VA column at class 3, then wondering at commissioning why the tariff meter disagrees with the reference meter.
Unlike a current transformer, the voltage circuit does not punish long secondary leads. At 100 V, a 15 VA burden draws 150 mA, so even 60 m of 2.5 mm² copper round trip drops a few tens of millivolts and consumes a fraction of a VA. The VA budget for a PT is therefore about the devices connected to it, not the cable, and it is easy to write down: meter, transducer, relay voltage coil, and any panel instrument that stays in circuit permanently.
The voltage factor line decides what happens during an earth fault
Rated voltage factor is printed as 1.2 or 1.9, and it describes how much above rated voltage the unit may be operated and for how long. A factor of 1.2 is continuous and suits a unit connected phase-to-phase on an effectively earthed system. A factor of 1.9 for 8 hours suits a unit connected phase-to-earth on a system that may run unearthed or impedance-earthed, where a single-phase fault raises the healthy phase voltages to the line value, about 1.73 times rated.
This is the line that decides whether a specification is met by a standard catalog unit or needs a different core. Put a 1.2 unit on an unearthed 11 kV system and the first sustained earth fault, which may last hours on a rural feeder, leaves the transformer over-excited at 1.73 times rated voltage for that whole period. Nothing fails immediately. The insulation ages, the error drifts, and the failure appears two winters later at a time with no obvious cause.
Insulation level: three numbers and why two datasheets disagree
The insulation level line is read as rated voltage / power-frequency withstand / lightning impulse withstand, all in kV. On the JDZ10-10 the three ratings are printed as 3.6/25/40, 7.2/32/60 and 12/42/75 kV, one line per voltage class, because a single transformer covers the 3 kV, 6 kV and 10 kV systems and only the insulation changes.
Here is where otherwise identical offers diverge. IEC 61869-1 lists 28 kV power-frequency withstand for equipment with Um of 12 kV, while many Asian and Middle East specifications and the sheet above use 42 kV for the same nominal class. Both units are sold as 12 kV class, both will pass a 28 kV test, and one of them is a different casting with different clearances and a different price. Ask for the three numbers, not the voltage class, and the comparison becomes possible.
The JDZW-40.5R outdoor voltage transformer above shows the same construction taken up one voltage step: the sheds lengthen and multiply as the class rises, and that change is what the third number on the plate is describing. Two units of the same ratio but a different insulation level are not interchangeable inside a panel, even though the ratio line reads the same.
What a misread line costs after the panel is energised
The costs fall into three groups, and only the first is recovered by a credit note. A ratio error is commercial: a 20% multiplier error on a feeder carrying 10 MWh a month mis-states 2 MWh a month, and the dispute runs backwards over the whole period the unit was in service. A voltage-factor error is mechanical: the unit survives the first fault and fails later, so the replacement cost includes an outage rather than just a transformer.
The third group is where most money is actually lost, and it happens before delivery. An insulation level taken from the wrong column, or a secondary voltage of 100 V ordered where the drawing needs 100/√3 V, is discovered at factory acceptance or at commissioning, after the units have been crated, shipped and installed. A 30 kg cast-resin unit returned by air freight and replaced, with the panel re-tested and energisation pushed back, costs far more than the price difference that caused the mistake.
There is also a quiet failure mode worth naming: a protection core ordered at 0.5 class because it was cheaper, then asked to drive a relay that needs a defined behaviour at 5% of rated voltage. Nothing is broken, no test fails, and the earth-fault protection simply picks up later than the setting sheet assumes. The relationship between the class and the voltage band is set out in the potential transformer testing sequence, where ratio, polarity and withstand are checked against the plate before the unit is accepted.
What to write into the RFQ and the datasheet
A PT enquiry that leaves any of the following to the supplier's judgement will be answered with whatever is in stock, and the answer will look correct on the quotation. Write them as requirements:
- System nominal voltage, and the Um of the switchgear it is going into.
- Earthing method of the system: effectively earthed, impedance earthed or unearthed.
- Ratio for every winding, including the residual winding, and the connection it serves.
- Accuracy class and rated output for each core, stated as a pair, with the burden calculated.
- Rated voltage factor for each winding, with the duration if 8 hours is acceptable.
- Insulation level as three numbers, taken from the utility's standard rather than the voltage class.
- Rated frequency, number of phases, indoor or outdoor mounting, and terminal marking convention.
- Ambient temperature, altitude and pollution level where they exceed normal service conditions.
- Documents: type test report to IEC 61869-3, and routine test results for ratio, polarity, power-frequency withstand, partial discharge and insulation resistance.
- Packing, marking and the quantity per panel.
Two of these are worth spelling out because they are the ones suppliers fill in silently. If the voltage factor is not stated, a 1.2 unit will be offered and it will be the cheapest compliant-looking option. If the residual winding class is not stated, a winding will appear on the drawing with no class beside it, and the relay setting will be written against an assumption. Both are resolved by one line each in the specification.
Where Nahu Group Fits
Nahu Group manufactures cast-resin voltage transformers for 3–12 kV and 27–40.5 kV switchgear, single-phase and three-phase, indoor and outdoor, with metering cores at class 0.2 and 0.5 and optional residual windings for earth-fault detection. The JDZ10-10 indoor voltage transformer covers the 3 kV, 6 kV and 10 kV systems with one casting, and the voltage transformer range lists the ratios, classes and insulation levels as they appear on the plate.
To get a configuration, send the single-line diagram with the PT symbol and its earth points, the system voltage and earthing method, the ratio required for each winding, the class and rated output per core with the connected burden, the insulation level your utility specifies, and the quantity per panel. With those six items a unit can be quoted against the drawing instead of against a model code, and the nameplate can be checked before it is cast rather than after it is delivered.
Frequently Asked Questions
Which line on a potential transformer nameplate matters most?
The ratio and the class-and-output pair matter most, in that order. The ratio decides every value the meter and relay calculate, and the class only means something at the rated output printed beside it. A plate reading 10000/100 V and 0.2 / 15 VA is a complete instruction; a plate reading 0.2 with no VA beside it is not, and should be queried before the order is placed.
Is 100 V the same as 100/√3 V on a nameplate?
No. A 100 V secondary is a phase-to-phase quantity, so the panel reads line voltage directly. A 100/√3 V secondary, which reads 57.7 V, is a phase-to-earth quantity, used where the protection or metering scheme works from phase voltages or from a broken delta. Fitting the wrong one produces a consistent 1.73 error on phase-to-earth readings and leaves the residual circuit without a usable signal.
Why does the nameplate list several rated outputs?
Because each accuracy class carries its own permitted burden, and a higher class permits a larger one on the same core. A single unit may be listed at 15 VA for class 0.2, 30 VA for class 0.5 and 60 VA for class 1. The correct reading is that the unit meets class 0.2 only up to 15 VA, and any panel burden above that figure moves the unit into the next column.
What does 12/42/75 kV mean on the plate?
It is the rated insulation level written as rated voltage, power-frequency withstand for one minute, and lightning impulse withstand, all in kV. The first number is the highest voltage for equipment the unit is built for, the second is what it must withstand at power frequency in a factory test, and the third is the impulse level. IEC and some national practices differ on the middle number for the same 12 kV class.
Can a 1.9 voltage factor unit replace a 1.2 unit?
Generally yes, provided the ratio, class and rated output match and the larger core fits the panel. The reverse substitution is the one to avoid: a 1.2 unit installed where the scheme assumes 1.9 will be over-excited during a sustained earth fault on an unearthed system. Check the outline drawing as well, because the higher factor usually comes with a taller or wider casting.
Where should the nameplate be recorded before installation?
At goods-inward inspection, before the unit is lifted into the panel. Photograph the plate, transcribe the ratio, class, rated output, voltage factor and insulation level into the project register, and file the image with the routine test certificate. Once the unit is bolted in, the plate on many indoor designs faces the rear of the compartment and can no longer be read without dismantling.
Sources and Further Reading
- IEC 61869-3:2011 — Instrument transformers, Part 3: Additional requirements for inductive voltage transformers — accuracy limits, rated output and rated voltage factor for inductive VTs
- IEC 61869-1:2023 — Instrument transformers, Part 1: General requirements — insulation levels, Um and the nameplate information common to voltage and current transformers
Published Nov 25, 2026 · Nahu Group (NAHU Electric Technology)