A wound current transformer wins four of the six criteria that decide current sensing at 10–35 kV: long-term stability, no auxiliary supply, immunity to interference on the secondary, and a declared class defined by IEC 61869-2 that an inspector can audit. It loses on bandwidth and on DC, where a Rogowski coil or a Hall sensor is the honest choice.
The short answer: four wins out of six
The six criteria buyers actually use are primary range, stability over service life, auxiliary supply, EMI immunity, standards compliance and cost structure. On a feeder relay or a revenue meter, the last four decide the order. A CT needs no 24 V circuit, its ratio is fixed by turns rather than by a gain resistor, and its accuracy is quoted at a stated burden, so the class can be checked against a type test report instead of a datasheet claim.
The two criteria it does not own are the edges of the range. Below roughly 5 A primary, or where the current has a DC component, an iron core has nothing to work with; above a few kilohertz of harmonic content, its response rolls off. If your measurement lives at either edge, the alternatives are the correct instrument, not a compromise.
What each of the four sensors actually measures
A wound CT is a passive transformer. The primary conductor is the single-turn primary, the core couples it to a multi-turn secondary, and the secondary current is the primary current divided by the turns ratio, within the error limits of its class at a stated burden. It reports current, and only current.
A Rogowski coil is an air-core toroid. Its output is proportional to the rate of change of current, so an integrator converts it back. With no core to saturate it stays linear far beyond the iron range, but its accuracy now depends on coil geometry and on the gain stability of the electronics behind it.
A Hall sensor measures the flux in a core gap with a semiconductor element, so it needs a supply. Its advantage is DC and mixed DC/AC measurement; its weakness is offset drift with temperature and time, which is why such instruments are re-zeroed in service.
A shunt is a resistor in the current path: the voltage across it is current times resistance. Cheap, DC-capable and galvanically connected to the primary, it needs isolation, amplification and filtering before any control system can read it.
The six criteria side by side
Read this table as a specification aid, not a ranking. Each column is the correct answer under different conditions, and the last row explains why the purchase price and the installed cost are rarely the same number.
| Criterion | Wound current transformer | Rogowski coil | Hall sensor | Shunt |
|---|---|---|---|---|
| Primary range | Fixed ratio from a few amps to about 1,200 A in cast indoor units; extends with busbar primary designs | Linear from milliamps to hundreds of kiloamps; ratio set at the integrator | Milliamps to a few kiloamps, limited by gap and core size | Up to a few kiloamps; output falls to millivolts at high current |
| Stability over service life | Ratio fixed by turns; no gain drift, no zero drift | Depends on coil geometry and integrator gain over temperature and time | Offset drift with temperature; needs periodic re-zero | Resistance drift with temperature; alloy choice decides how much |
| Auxiliary supply | None; passive, live only while primary current flows | Required for the integrator | Required, typically a bipolar or 24 V DC rail | None for the element; conditioning electronics needed to use the signal |
| EMI immunity | Passive secondary; screened leads handle the rest | Low output level; screened cable and careful routing required | Electronics sit in the measuring gap; most exposed of the four | Millivolt signal; twisted pair and filtering required |
| Standards compliance | Accuracy class, burden and limits defined in IEC 61869-2, proven by type test | Covered by low-power instrument transformer standards, defined by a low-voltage output rather than a 5 A secondary | Same low-power family; application standards vary by industry | No instrument transformer class; accuracy stated by the resistor and amplifier |
| Cost structure | Device plus secondary wiring and test terminals; no electronics to calibrate | Coil inexpensive; integrator, supply and enclosure carry the cost | Sensor plus supply, conditioning and re-zero labor | Cheapest element; isolation, amplification and screening carry the cost |
Two rows carry most of the commercial weight. The supply row decides whether the panel needs another 24 V circuit and a battery test routine; the standards row decides whether the accuracy figure can be defended at witness testing, because a CT class carries the burden it was tested at and a percentage-of-reading claim does not.
Range, ratio and voltage class
The practical range of a cast indoor CT is wider than most buyers assume. One 24 kV family covers rated primary currents from 5–150 A through 1000/1200 A, with metering outputs of 10–30 VA, accuracy classes 0.2S, 0.5S, 10P10 and 10P15, one-second thermal current from 31.5 to 63 kA and dynamic current from 80 to 130 kA. Those figures are catalogue values for the LZZBJ9-24 indoor current transformer, and they show the shape of the problem: the ratio is chosen from a table, not designed from scratch.
Voltage class changes the body, not the principle. A 35 kV indoor unit carries more creepage, so the cast body grows into a taller stack of skirts and the panel depth grows with it, which is what the second photograph shows. If your switchgear is 35 kV and the panel depth is already fixed by the busbar arrangement, that dimension belongs in the RFQ, not in the post-award drawing review.
Where the CT genuinely stops is DC and wideband. A core cannot reproduce a current that never reverses, and its response falls away as harmonic order climbs. Rogowski coils are linear there, and that is the honest reason to specify one.
Stability, supply and standards: what survives twenty years
Three of the four CT advantages are quiet ones, in the sense that nothing on site announces them. A turns ratio does not drift, because there is nothing to drift: the ratio is the number of turns, and the core is a fixed assembly. There is no gain resistor to age, no amplifier offset to re-zero, no firmware to update. Over a twenty-year service life in a substation that is the whole argument.
The absent supply is the second. A passive secondary is live only while primary current flows, so a CT adds no load to the DC system, no battery autonomy calculation and no alarm on loss of auxiliary power. In a retrofit, where a new 24 V circuit means a new MCB, new wiring and a new drawing, that single fact can decide the scheme.
The third is the standard. IEC 61869-2 defines what a class means, at which burden and over which current range, and those values are demonstrated by type test on a representative unit. A class 0.2S claim can therefore be audited: ask for the report, compare the tested burden with the actual burden, and see whether the class still holds. For the error limits behind the class letters, see what class 0.2S and 5P20 actually guarantee.
What the advantages cost: saturation, open circuit and volume
Every advantage has a price, and three of them show up on site rather than in the quotation.
| Condition | What happens | Commercial consequence |
|---|---|---|
| DC offset in the fault current, high X/R ratio | Core saturates part-way through the fault; secondary no longer reproduces primary | Protection may operate slower than the study assumed; accuracy limit factor must be specified, not assumed |
| Secondary open-circuited with primary energized | Very high voltage across the open terminals and core heating | Test terminal and a written shorting procedure become mandatory; an incident here injures people |
| 35 kV body in a fixed panel depth | Creepage skirts increase the height and the depth required | Cabinet rework or a different model; the cost lands after award |
| Actual burden above the rated burden | Class not held in service even though the nameplate is correct | Larger VA, shorter or thicker leads, or a second round of inspection |
Saturation is the price of the iron core, and the way to control it is to specify the accuracy limit factor rather than accept the default. Open-circuit risk is the price of a passive secondary, and it is managed by hardware, a shorting terminal block, plus a procedure. Volume is the price at the upper voltage classes. The counterweight is that the smallest ratios stay compact: a 10 kV unit rated from 5/5 A fits a standard panel depth, which is what the third photograph shows.
Selection mistakes and what they cost on site
The mistakes that cost money are not exotic. They are the four or five that recur in every second enquiry.
- Class 0.5 specified for revenue metering. The utility's tariff class is 0.2S, the CT arrives as 0.5, and the meter is rejected at commissioning. The device is not defective; the specification was.
- Burden taken from the nameplate instead of the circuit. Relay, meter and lead resistance add up to more than the rated VA, the class is not held, and the fix is a larger core or new cable after the panel is wired.
- No accuracy limit factor on protection cores. The relay is set from a study that assumed faithful reproduction of a close-in fault, and the core saturates before the study's assumption holds.
- P1 and P2 reversed, or cores swapped. Polarity tests fail at commissioning, and in a differential scheme the consequence is a trip that cannot be explained until the secondary is traced.
- Metering core used where a protection core was intended. The instrument security factor protects the meter, not the relay, and a fault current can damage a core that was never meant to see it.
Each of these is caught by a specification review that takes an hour, and missed by a purchase order that takes five minutes. The burden arithmetic itself is worth doing properly once; a worked burden and secondary lead-size example shows how quickly lead resistance consumes a 10 VA rating.
What to write into the RFQ or the datasheet
Phrase these as requirements, so the offer can be checked line by line instead of inferred from a catalogue page.
- System voltage and insulation level, plus indoor or outdoor installation and the ambient range.
- Rated primary current and ratio, per core if the unit is multi-core, with the ratio range acceptable for the load study.
- Accuracy class and rated burden for each core separately, for example 0.2S at 10 VA metering and 5P20 at 15 VA protection.
- Accuracy limit factor for protection cores and instrument security factor for metering cores.
- Short-time thermal current and dynamic current, taken from the switchgear fault level rather than guessed.
- Secondary current, 5 A or 1 A, and the terminal arrangement expected by the panel builder.
- Tests and documents: type test reports, routine test reports, ratio and polarity records, drawings for approval before manufacture.
- Mounting, busbar or cable entry, and packing suitable for the transport route.
If the signal has to leave the panel as a 4–20 mA loop rather than a 5 A secondary, the comparison changes; that case is covered in where a transducer ends and a CT begins.
Where Nahu Group Fits
Nahu Group builds indoor and outdoor current transformers from 10 kV to 35 kV, including the LZZBJ9-24 and LZZBJ9-35 indoor families and the compact LZZJ-10 at small ratios. The full range, with ratio tables and class combinations, is on the current transformer product page.
To get a configuration rather than a brochure, send four things: the single-line diagram or panel drawing, the system voltage and fault level, the ratio and class you need for each core, and the quantity with the required delivery date. That is enough to return a model selection, a terminal arrangement and the test documents your inspector will ask for.
Frequently asked questions
Are current transformers more accurate than Rogowski coils?
Not in general, but differently. A CT declares a class at a stated burden and proves it by type test, so its accuracy is verifiable on paper and at witness testing. A Rogowski coil is linear over a far wider range but its accuracy depends on coil geometry and integrator gain, which are harder to audit after installation. For revenue metering, the CT route is the auditable one.
Do current transformers need an auxiliary power supply?
No. A CT is passive: the secondary current is produced by the primary current, and the device is live only while load or fault current flows. That removes a 24 V circuit, a battery autonomy calculation and an alarm on loss of auxiliary supply from the panel design, which matters most in retrofits where new DC wiring is expensive.
Why does a current transformer saturate when a Rogowski coil does not?
Because the CT has an iron core and the Rogowski coil is air-core. Iron concentrates flux, which is what makes a passive CT practical, but it has a finite flux capacity. A fault current with a DC offset and a high X/R ratio drives the core into saturation, and the secondary stops reproducing the primary. Specifying the accuracy limit factor is how you bound that risk.
Can a current transformer measure DC current?
No. A CT responds to alternating current, because the core needs a changing flux to induce secondary current. For DC or mixed DC/AC measurement the instrument is a Hall sensor, a fluxgate or a shunt with isolation. Trying to use a CT there produces a reading that looks plausible and is wrong.
What happens if the secondary is left open-circuited?
With primary current flowing, an open secondary can develop a very high voltage across its terminals and heat the core, which is a hazard to people and to the device. Short the secondary at a test terminal before removing a meter or relay, and specify a shorting terminal block so that the safe action is also the easy one.
Is a shunt cheaper than a current transformer?
The resistor is cheaper than the CT, but it is not the whole system. A shunt sits at primary potential, so isolation, amplification, filtering and screening have to be added, and none of it carries an instrument transformer class. At medium voltage the installed cost usually favors the CT, and the audit trail certainly does.