A current transducer delivers a signal a control system can read — 4–20 mA or 0–5 V into a PLC analog card — while a current transformer delivers 5 A or 1 A into a meter, a relay or a transducer. When the receiving device is a PLC, the output format decides the purchase, not the accuracy class on its own. Choosing by class first is how panels end up with a 5 A secondary that nothing on the control side can accept.

Red epoxy-cast LZZW-10 indoor current transformer on a steel base, with two primary bar terminals on top and a black nameplate at the front

The difference sits at the terminals, not in the measurement

Both devices measure the same quantity: primary current, through a magnetic core. A current transformer is a passive transformer whose secondary is standardized at 5 A or 1 A so that any meter, relay or test set can be connected to it. Its accuracy is defined by a class at a stated burden — on the current transformers product page the LZZW-10 is offered with 0.2S, 0.5 and 10P15 cores at 10, 15 and 15 VA. That definition does not change when the downstream device changes.

A current transducer carries the same kind of core plus a burden, an amplifier and an output stage. It converts secondary current into a control-level signal, and because the electronics need power it requires an auxiliary supply. The term is used loosely in the market: some catalogues call a split-core CT with a built-in 4–20 mA output a current transducer, others use it for a DIN-rail converter that takes 5 A in and gives 4–20 mA out. These are different products with different failure modes, and the RFQ has to say which one is intended.

The practical consequence is that the two devices are bought at different points in the project. The CT is ordered with the switchgear, against a single-line diagram and a metering class. The transducer is usually bought with the control panel, against a PLC input list. When those two purchases are made by different people without a shared core schedule, the mismatch appears at commissioning, not in either quotation.

Six differences that decide the choice

Read the table as a specification aid, not a ranking. The right-hand column is not better than the left; it is what a PLC-based control system can accept without extra hardware.

PropertyCurrent transformerCurrent transducer
Output signal5 A or 1 A AC, proportional to primary current4–20 mA, 0–5 V, 0–10 V or a serial bus value
Auxiliary supplyNone; passive, and live only while primary current flowsRequired, typically 24 V DC, loop-powered or separately fed
Load capabilityA burden in VA at rated current, e.g. 10–15 VA per coreA loop resistance, typically up to 500 Ω on a 24 V loop
Accuracy stated asClass at a stated burden and current range, e.g. 0.5 from 25 to 100% ratedPercentage of span, typically 0.2–0.5% of the 16 mA range
Interface to the control systemNeeds a shunt, a dedicated 5 A input module, or a transducerGoes directly to an analog input card or an RS-485 port
Parts and settings on the panelOne part, no setting, no supply to loseTwo parts if a CT is added upstream, one if it is an active CT

Two rows carry most of the commercial weight. The supply row decides whether a control cabinet needs another 24 V circuit, and the accuracy row decides whether the number on the HMI means anything. A transducer quoted as 0.2% of span is not comparable with a CT quoted as class 0.2, because the CT figure is measured at a specified burden while the transducer figure is measured on its own output, with the CT error still to be added.

Why a 5 A secondary cannot go straight into a PLC

An analog input card reads a voltage, usually 0–10 V, or a current loop, usually 4–20 mA. A 5 A secondary is a current source with no defined voltage, so it has to be converted, and the conversion is where panels get into trouble. A shunt of 1 Ω gives 5 V at rated current, which suits a 0–10 V card, but the burden it presents is 5 A squared times 1 Ω — 25 VA, more than the 10 or 15 VA that a medium voltage metering core is rated for.

Drop the shunt to 0.1 Ω and the burden falls to 2.5 VA, which the core can carry, but the signal at rated current becomes 0.5 V. Over a 40 m run inside a switchgear room, beside contactor coils and variable speed drives, that is a signal a 12-bit card reads with more noise than resolution. The practical answers are a dedicated 5 A input module, which is a transducer in another housing, or a proper transducer with a 4–20 mA output that tolerates loop resistance and drives a long cable.

Distance makes the argument sharper. On 1.5 mm² copper, roughly 12 Ω per km, a 300 m run adds about 3.6 Ω to the loop once the return conductor is counted. At 20 mA that costs 0.07 V of a 24 V supply, which is nothing against a 10 V compliance floor. The same 300 m at 5 A costs 5 A squared times 3.6 Ω, about 90 VA — six times the rating of the core driving it. This is the arithmetic behind the old rule that a 1 A secondary pays for itself on long runs, which is worked through in the burden and lead-size calculation.

When the two-stage CT plus transducer scheme is the only option

Three-phase current transformers clamped to a pole gantry below an overhead line, with cast-resin bodies and secondary cables running down the pole

A two-stage chain — CT first, transducer second — is not a compromise. Five situations make it the only arrangement that passes commissioning and inspection.

  • Existing switchgear with cores already allocated. When the cores of a feeder CT are taken by metering, protection, indication and earth fault, the control system gets a transducer on the indication core rather than a new CT. The core logic is set out in the four-cores walk-through.
  • Tariff metering that must keep its class. A revenue meter belongs on a 5 A or 1 A core of class 0.5S or better. Putting a 0.5% transducer in series with that meter changes the class of the metering chain, and a utility witness test will find it. Keep the meter on the CT and take the control signal from a separate core.
  • Long runs to a control room. Secondary lead resistance adds directly to the burden, and at 5 A it adds as the square of the current. A 4–20 mA loop carries the value over 300 m on 1.5 mm² wire; a 5 A circuit over the same distance does not, as the previous section shows.
  • Several readers for one measurement. A local display, a PLC and a SCADA gateway cannot all sit on one 5 A core without adding burden three times. A loop signal or a serial value can be shared, and the burden stays at the transducer input.
  • Retrofit where the panel has no space. A DIN-rail transducer fits beside existing terminals; a second 5 A meter does not. This is the everyday case on outdoor installations such as the pole set shown above, where the CT is already on the gantry and only the control cabinet is being replaced.

There is a single-device alternative: an active CT with the electronics potted into the secondary box. It saves panel space and one set of terminals, and it is the right answer for a packaged unit built in one factory. It is the wrong answer where the installation has to be maintained by a utility crew, because a failed output stage then means replacing the CT rather than a DIN-rail module that costs a fraction of it and can be swapped with the primary circuit still in service.

Accuracy: where the error stack comes from

Tall red cast-resin 35 kV current transformer column with a long shedded body and a secondary terminal box at its base

A CT class is a promise made at a stated burden and over a stated current range, and it lapses outside both. Once a transducer is added, the chain error is the sum of the parts, and the parts are specified by different documents. The stack below is what a metering or SCADA engineer should be able to reconstruct before accepting a design.

Element in the chainTypical contributionWhere it is specified
CT ratio error at 5% and at 120% of rated current0.2–0.5% for class 0.2S and 0.5S, wider below 5%IEC 61869-2 type test report, per class
CT phase displacement10–30 minutes for class 0.5, smaller for 0.2SSame type test report
Burden mismatch, leads includedRises steeply once the actual burden exceeds rated VAA calculation, not a catalogue figure
Transducer zero and span0.2–0.5% of span before temperature driftManufacturer data sheet
PLC analog input0.1–0.5% of full scale on a 12-bit cardCard manual

The common mistake is to quote the CT class as the accuracy of the measurement. A 0.5 class CT feeding a 0.5% transducer and a 12-bit card can be a 1% chain, and the number that matters for a control decision is the chain, not the certificate. The class comparison in the accuracy class comparison covers what each CT class guarantees at its test burden; everything below the CT in the table has to be added by the buyer.

Selection mistakes and what they cost

The expensive mistakes are not the ones that fail at the bench. They are the ones that pass a factory test and are then found at site acceptance, or worse, in a revenue reconciliation three months later.

MistakeWhat actually happensCommercial consequence
Transducer placed on the tariff coreMetering chain class drops below the utility requirementRe-test and a second site visit; billing start delayed
No auxiliary supply allowed forLoop dead at energisation, no reading on the PLCPanel rework and a 24 V supply added after the fact
1 A CT wired into a 5 A transducer inputReading sits at one fifth of actual; alarms and trends wrongFalse alarms until someone checks the ratio; trust in the data lost
Secondary opened to change a meterDangerous voltage across the open core, saturation and heatInjury risk and a damaged CT; short the core first, always
Split-core 4–20 mA unit used for protectionResponse in the hundreds of milliseconds, pick-up drifts with temperatureProtection does not clear the fault in time; the CT is not the problem

One mistake deserves a separate line because it is invisible on a drawing: the transducer input impedance is itself a burden on the secondary. A unit quoted at 1–2 VA is harmless on a 15 VA metering core at short lead length, but add 80 m of 2.5 mm² leads and the same core is now carrying the transducer plus the leads. If the only spare core is a protection core with a 10P15 class, using it for a transducer is acceptable for indication and not acceptable for metering, because a protection core is not specified for ratio error in the normal load range at all.

What to write into the RFQ or the datasheet

Write the requirement, not the product name. A supplier who receives the list below can quote a CT and state plainly whether the transducer is theirs or has to come from another vendor, which is the answer needed before the panel drawing is frozen.

  • Primary current and ratio, number of cores, and what each core feeds: revenue meter, protection relay, indication, PLC.
  • Class and rated burden per core, the current range over which the class must hold, and the actual connected burden including lead resistance.
  • For the transducer: input range in A, output in mA or V, loop-powered or separately supplied, maximum loop resistance, response time, isolation level, and accuracy as a percentage of span.
  • Site conditions: indoor or outdoor, maximum ambient, altitude, pollution level, and any coastal or desert dust requirement.
  • Tests and documents: routine test report, type test report to IEC 61869-2, EMC report for the transducer, outline drawing and terminal marking for approval.
  • Quantity, packing, and the drawing revision the quotation is based on.

Two of those lines are routinely omitted and both are cheap to add. The current range over which the class must hold decides whether a 0.5S core is needed at all, because a utility that meters from 2% of load upward is buying a different core from one that meters from 20%. The drawing revision decides whether the outline that arrives matches the panel that was built, which is the single most common cause of a returned delivery on medium voltage CTs.

Where Nahu Group Fits

Nahu Group makes epoxy-cast current transformers for indoor and outdoor medium voltage installations from 0.66 kV to 35 kV, with metering cores in 0.2S and 0.5 and protection cores in 5P and 10P. The outdoor range includes the LZZW-10 outdoor current transformer for 10 kV networks, with ratios from 10 A to 1500 A and 10P15 protection cores, and the LZZW-35 outdoor current transformer for 35 kV systems. For panel-mounted installations the LZZBJ9-10 indoor current transformer is the equivalent cast-resin body.

Nahu Group does not supply the transducer itself and says so, rather than bundling an unspecified module. What the CT can do is make the two-stage scheme straightforward: a dedicated measuring core with its own class and burden, so a third-party transducer sits on a core the meter does not depend on. To get a configuration, send the ratio per core, the class and burden each duty needs, the panel or gantry drawing, the ambient and pollution level, and the quantity — enough to propose a core allocation and return an outline drawing for approval.

Frequently asked questions

Can a 5 A current transformer connect directly to a 4–20 mA input?

No. A 4–20 mA input expects an active source with a defined compliance voltage, while a CT secondary is an AC current source that produces a dangerous voltage if the loop opens. You need a transducer or a dedicated 5 A input module in between. A shunt alone will not do: at rated current it either exceeds the core burden or leaves a signal too small for the card.

Is a current transducer more accurate than a current transformer?

Usually not. A metering CT of class 0.2S or 0.5S is tested at a defined burden and range under IEC 61869-2, while a transducer is quoted as a percentage of its own span. The transducer adds error rather than replacing it, so a 0.5 class CT with a 0.5% transducer is a roughly 1% chain. Buy the CT class for metering and treat the transducer as an extra term.

Does the transducer need its own core?

For revenue metering, yes. The meter should keep a core of its own so that its class is not affected by anything added downstream. For indication and SCADA, sharing a core is normal, provided the combined burden stays inside the rated VA at the actual lead length. Ask for a dual-core body such as the 0.2S/0.5/10P15 combinations offered on the LZZW-10, and allocate the duties explicitly on the drawing.

What supply does a 4–20 mA transducer need?

Most loop-powered units take 24 V DC and are wired in series with the analog card, so one pair of wires carries both power and signal. Four-wire units have a separate supply and suit high loop resistance or an isolated output. Confirm which type is quoted: a two-wire unit cannot be fed from a card with no loop supply, and that error surfaces at commissioning.

What happens if the secondary is opened while a transducer is removed?

The core saturates and a high voltage appears across the open terminals, a hazard to the person working and a risk to the CT insulation. Short the secondary with a test link before breaking the circuit and restore it before the primary is re-energised. On a two-stage scheme, short the CT on the primary side before any work on the loop.

Can one CT feed a meter, a relay and a transducer?

Only if the VA budget allows it at the real lead length. Add the meter burden, the relay burden and the transducer input impedance, then the lead burden from length and cross-section, and compare the total with the rated VA of the core. When it exceeds the rating, a second core on the same body is the usual fix, keeping ratio and footprint unchanged.

Published Nov 26, 2026 · Nahu Group (NAHU Electric Technology)