Control gear and switchgear are not rival product families. IEC 60947-1 uses "switchgear and controlgear" as one term, and the split is functional: switchgear makes, carries and breaks the main circuit; control gear commands, protects and indicates it. The one hard number is 1 kV — below it the IEC 60947 series applies, above it IEC 62271.

That boundary decides which type test file a bid is judged on, and why a 12 kV cabinet is quoted against two standards regimes at once. It is also why "switchgear" alone on a bill of quantities is an incomplete specification.

Indoor vacuum circuit breaker chassis with three red vacuum interrupters above a Nahu control panel showing closed and open buttons

What Is the Difference Between Control Gear and Switchgear?

Switchgear makes, breaks, carries or isolates current in a main circuit. Control gear governs how that switching happens: contactors and starters, protection and auxiliary relays, control switches, indication lamps, heaters and terminals. IEC 60947-1 covers both in one scope because they share an enclosure and the same safety requirements — not because they share ratings, tests or declarations.

Three questions place any device on the correct side of the line:

  • Is it in the main current path? Then it is switchgear — breaker, switch-disconnector, fuse, isolator, busbar.
  • Does it interrupt or protect the main circuit? Switchgear, even when the device is small.
  • Does it only command, sense or indicate? Control gear: coils, trip circuits, status contacts, heaters, relays.

Where IEC 60947 Stops and IEC 62271 Starts

IEC 60947-1 is written for circuits not exceeding 1,000 V AC or 1,500 V DC; IEC 62271-1 takes over above 1 kV. A 12 kV metal-enclosed cabinet therefore lives in both worlds, and they meet at the auxiliary transformer and the control supply: busbar, breaker and cable compartment follow IEC 62271; everything downstream of the auxiliary supply follows IEC 60947 and the assembly rules of IEC 61439-1.

Circuit inside the cabinetFunctionGoverning standardTypical ratingEvidence asked for
Main busbar and cable compartmentCarry and distribute main currentIEC 62271-200 with IEC 62271-112 kV, 630–1,250 AType tests on the enclosure, including internal arc
Vacuum circuit breakerMake and break load and fault currentIEC 62271-10012 kV, 20–31.5 kABreaking and making type tests at the stated rating
Switch-disconnector or load break switchSwitching and isolationIEC 62271-10312 kV, 630 ALoad-breaking and making tests
Disconnector and earthing switchIsolation and earthingIEC 62271-10212 kVShort-time and peak withstand tests
Current and voltage transformersMeasurement and protection signalsIEC 61869 seriesRatio and class as specifiedAccuracy and insulation tests per part
Low-voltage distribution inside the cabinetAuxiliary and station supplyIEC 61439-1 assembly, devices to IEC 60947400/415 V, up to 3,150 A in a GGDDesign verification of the assembly plus component declarations
Control, indication and interlocking circuitsCommand and statusIEC 60947-1 with IEC 60947-5-1110 V DC or 230 V ACComponent declarations and routine checks
Contactor or starter for auxiliariesSwitching a control loadIEC 60947-4-1Coil voltage as specifiedUtilisation category and electrical life data

The split is of duties, not of importance: a trip circuit built to the wrong part of IEC 60947 will not open a breaker that is perfectly type-tested to IEC 62271-100, and the fault is recorded against the whole cabinet.

A metal-enclosed cabinet is type-tested as an assembly — dielectric withstand, temperature rise, short-time withstand and internal arc — to IEC 62271-200. That file says nothing about the control devices inside, qualified separately: the assembly to IEC 61439-1, the devices to their own IEC 60947 parts. Inspection asks for both, and a supplier who sends only the first has proved the enclosure, not the function; the type test reports for MV switchgear guide lists the set.

Which Devices Sit on Each Side of the Line

The switchgear family is short: circuit breakers, switch-disconnectors, load break switches, disconnectors, earthing switches, fuses and the assemblies that house them. The control gear family is longer than most RFQs allow for — contactors, overload and protection relays, control switches, lamps, heaters, thermostats and terminals, each with its own rated voltage.

Three-phase outdoor vacuum interrupter poles with grey silicone sheds, ring current transformers and a stainless steel mounting base

A pole-mounted vacuum interrupter shows the split plainly. The three epoxy poles and their current transformers are switchgear: they carry and interrupt line current and are type-tested as a breaker. The weatherproof box beside them — motor, controller, secondary wiring, remote terminal — is control gear. Both are bought as one unit and approved as two.

Indoors the logic is unchanged: in a KYN28A-12 armored cubicle the 12 kV compartment follows IEC 62271-200 while the relay and control compartment follows IEC 60947 — the arrangement set out in the metal-enclosed switchgear cabinet guide.

Does the Split Change on Pole-Mounted Switchgear?

No. The 1 kV line holds outdoors, and the evidence splits the same way. What changes is the enclosure and the interface: ingress protection, pollution level, UV exposure and animal contact join the switchgear specification, while the control box is often a separate assembly with its own cable and connector. The standards question becomes a scope question — which party declares that box, and against which standard.

Pole-mounted vacuum switchgear and insulators installed on a concrete utility pole with overhead jumper conductors connected

At handover that decides who tests it: a loose control box must be covered by site acceptance, where a missing declaration becomes a hold point.

Selection Mistakes and Their Commercial Consequence

  • Writing "switchgear" and stopping there. The quote covers the main circuit and leaves control and protection as options; the variation order arrives after award and pushes drawing approval back by weeks.
  • A control supply nobody agreed. A 230 V AC scheme ordered for a station with a 110 V DC battery means new coils, lamps and relay plus a rebuilt loom — rework at the works or on site before energisation.
  • No evidence for the IEC 60947 side. The cabinet passes its dielectric test and the control circuit is unproven; re-inspection is charged to the project and energisation moves.
  • An LV device outside its rated voltage. A 400 V device on a 690 V auxiliary bus is outside its standard, and the substitution surfaces at approval rather than at design.
  • Losing the classification at the border. When cabinet and control section ship separately, the customs description must match the standard actually declared — the difference the switchgear HS code breakdown sets out.

What to Write Into the RFQ

State the two sides separately. A supplier given one merged paragraph prices the part he knows and assumes the rest.

Item to stateMain circuit side (IEC 62271)Control side (IEC 60947 / IEC 61439)
Voltage basisU_m, rated voltage, lightning and switching impulse levelControl and auxiliary supply voltage, AC or DC, tolerance
Current basisRated current, rated short-time withstand current and duration, peak withstandRated operational current and utilisation category of each control device
DutyBreaking and making capacity required at the stated fault levelOperating duty, electrical life and duty cycle of contactors
ProtectionCT ratios and classes, relay functions, trip logicOverload range, control fuses or MCBs, interlocking scheme
EnclosureIP rating, compartment arrangement, internal arc classificationControl compartment access, segregation, cable entry
EnvironmentAmbient maximum, altitude, pollution level, seismic requirementHeater and thermostat requirement, condensation control
DocumentsIEC 62271-200 and IEC 62271-1 type test reports, routine test report, approval drawingsIEC 61439-1 verification, component declarations, terminal and wiring schedule
Marking and packingNameplate data, rating plate language, sea-worthy packingSpare control devices, labelled spare cores, test certificates

Add one sentence that removes most of the argument later: state the standard each item is declared against. A supplier who cannot answer per line has built to a drawing, not to a standard.

Frequently Asked Questions

Is a circuit breaker switchgear or control gear?

Switchgear. It carries main current and makes and breaks load or fault current, type-tested to IEC 62271-100 at a stated rating. The relay that tells it to trip, and the trip circuit, are control gear. The breaker without the relay protects nothing; the relay without the breaker interrupts nothing.

Does the 1 kV boundary apply to DC circuits too?

The ceiling for IEC 60947-1 is 1,000 V AC or 1,500 V DC; DC switchgear above that falls under IEC 62271. The practical case is the station battery and its distribution, inside the IEC 60947 range — but state the DC ratings: a device rated for AC will not necessarily break DC.

Which control voltage should be specified?

Whatever the station actually provides. With a battery, 110 V DC is common and 220 V DC in larger substations; without one, 230 V AC from the auxiliary supply is usual. State the voltage, the tolerance and whether the supply is backed up — all three change relay, coil and lamp selection.

What proves the low-voltage side of a medium-voltage cabinet?

Two documents. The assembly is verified to IEC 61439-1 by design and routine verification; each device inside is declared against its own IEC 60947 part. Ask for both by name in the RFQ with the wiring schedule, and the control circuit stops being the unexamined part of a tested cabinet.

Can one cabinet be certified to both regimes?

Yes, and most medium-voltage cabinets are. The main circuit is type-tested to IEC 62271-200; the auxiliary and control section follows IEC 61439-1 and IEC 60947. The files are separate and the buyer should expect both — one certificate covering "the switchgear" is a description, not evidence.

Where Nahu Group Fits

Nahu Group builds the cabinet families that carry both sides of this split: the KYN28A-12 armored withdrawable cabinet for 3.6, 7.2 and 12 kV systems, the HXGN15-12 ring network unit built to IEC 62271-200 with IP3X enclosure and manual or electric operation, and the GGD low-voltage distribution cabinet at 380 V and up to 3,150 A on the auxiliary side.

To get a configuration, send the single-line diagram, system voltage and insulation level, busbar and feeder currents with the short-time withstand value, the fault level in kA, the control supply voltage, IP and ambient requirements, the quantity of each cubicle type, and the standards your approval requires on each side. The high-voltage distribution cabinet lists the three families these inputs are matched to.

Sources and Further Reading

Published Nov 16, 2026 · Nahu Group (NAHU Electric Technology)