S11 series · 50-2500 kVA · 30-35 kV / 400-433 V · Dyn11 or Yyn0
The S11 series is a three-phase oil-immersed distribution transformer for 33 kV networks with a 0.4 kV secondary, built in a corrugated tank with a conservator and a radiator bank. The conservator takes the oil expansion and keeps a positive oil head on the bushings, while the radiators provide the cooling surface needed at this voltage class; the tank wall itself is corrugated for stiffness and extra cooling area.
Ratings run from 50 to 2500 kVA at 30 / 33 / 35 kV primary with 400, 415 or 433 V secondary, Dyn11 or Yyn0 vector groups, and a tapping range of plus or minus 5 % or plus or minus 2 by 2.5 %. No-load loss runs from 210 W at 50 kVA to 2950 W at 2500 kVA, and load loss at 75 C from 1270 W to 23,200 W over the same range.
Short-circuit impedance is 6.5 % for all ratings. Total weight goes from 590 kg to 5100 kg, of which the oil is 190 kg to 1005 kg, so transport and foundation loads can be checked against the table before the unit is ordered.
Price
On request
MOQ 1 piece · Lead time 30 days
General data for the S11 33 kV series. Ratings not listed are built to order.
| Parameter | Unit | Value |
|---|---|---|
| Rated high voltage | kV | 30 / 33 / 35 |
| Rated low voltage | V | 400 / 415 / 433 |
| Rated capacity | kVA | 50 - 2500 |
| Number of phases | - | Three |
| Rated frequency | Hz | 50 / 60 |
| Vector group | - | Dyn11 / Yyn0 |
| Tapping range | - | ±5 % or ±2×2.5 % |
| Short-circuit impedance | % | 6.5 % for all ratings |
| Tank type | - | Corrugated wall with conservator and radiators |
| Core | - | Laminated cold-rolled silicon steel |
| Winding | - | Oxygen-free copper, multi-layer cylinder |
| Design standard | - | IEC 60076, GB 1094 |
Load loss is stated at 75 C. Outline drawings with the bushing arrangement and the installation pitch are issued per rating.
Standard ratings at 33 kV / 400-433 V. Dimensions are tank length, width and height in mm.
| Rating (kVA) | No-load loss (W) | Load loss 75 C (W) | No-load current (%) | Oil weight (kg) | Total weight (kg) | L (mm) | W (mm) | H (mm) | Pitch L1/L2 (mm) |
|---|---|---|---|---|---|---|---|---|---|
| 50 | 210 | 1,270 | 2.0 | 190 | 590 | 985 | 675 | 1,290 | 400/400 |
| 80 | 260 | 1,800 | 1.9 | 205 | 630 | 985 | 670 | 1,300 | 450/450 |
| 100 | 290 | 2,120 | 1.8 | 210 | 685 | 950 | 665 | 1,325 | 450/450 |
| 125 | 340 | 2,500 | 1.7 | 250 | 825 | 1,000 | 695 | 1,390 | 550/550 |
| 160 | 260 | 2,970 | 1.6 | 260 | 950 | 1,055 | 770 | 1,405 | 550/550 |
| 200 | 430 | 3,500 | 1.5 | 275 | 1,030 | 1,180 | 690 | 1,450 | 550/550 |
| 250 | 510 | 4,160 | 1.4 | 280 | 1,095 | 1,305 | 850 | 1,390 | 550/550 |
| 315 | 610 | 5,010 | 1.4 | 300 | 1,220 | 1,315 | 865 | 1,500 | 660/660 |
| 400 | 730 | 6,050 | 1.3 | 345 | 1,425 | 1,445 | 945 | 1,530 | 660/660 |
| 500 | 860 | 7,280 | 1.2 | 380 | 1,605 | 1,460 | 945 | 1,600 | 660/660 |
| 630 | 1,040 | 8,280 | 1.1 | 515 | 2,035 | 1,640 | 1,155 | 1,595 | 660/660 |
| 800 | 1,230 | 9,900 | 1.0 | 575 | 2,315 | 1,760 | 1,225 | 1,660 | 820/820 |
| 1000 | 1,440 | 12,150 | 1.0 | 595 | 2,595 | 1,845 | 1,305 | 1,725 | 820/820 |
| 1250 | 1,760 | 14,670 | 0.9 | 655 | 3,020 | 1,860 | 1,315 | 1,735 | 820/820 |
| 1600 | 2,120 | 17,550 | 0.8 | 765 | 3,580 | 1,905 | 1,370 | 1,870 | 820/820 |
| 2000 | 2,380 | 19,700 | 0.7 | 870 | 4,125 | 1,865 | 1,295 | 1,900 | 820/1070 |
| 2500 | 2,950 | 23,200 | 0.6 | 1,005 | 5,100 | 2,070 | 1,470 | 1,920 | 820/1070 |
The transformer is designed and manufactured to the IEC 60076 series, with GB 1094 as the equivalent national basis. Routine tests are carried out on every unit; type test reports for a specific rating are issued with the technical offer on request.
Step-down duty on 33 kV feeders for industrial estates, commercial buildings and municipal networks.
Corrugated tanks with a conservator tolerate rain, dust and wide temperature swings for outdoor installation.
Step-up duty at solar and wind sites, where the conservator gives a visible oil level and the radiators handle the load cycle.
Factory distribution boards, with losses and impedance published per rating for protection settings.
How is the oil expansion handled on this rating?
A conservator is mounted above the tank and connected by a pipe, so the oil level rises and falls there instead of building pressure in the tank. The radiator bank on the tank walls provides the cooling surface for the larger ratings in this class.
Can the same unit run at other primary voltages?
Yes. The 33 kV class covers 30 / 33 / 35 kV primary with 400, 415 or 433 V secondary; the rated voltage and tapping range are fixed at order.
Why is the impedance different from the 10 kV series?
Higher voltage classes need more insulation and a larger winding leakage reactance, so the 33 kV series is built at 6.5 % against 4 % on the 10 kV units. The switchgear rating has to be checked against it.
What do you need to quote a unit?
Rated capacity, primary and secondary voltage, vector group, tapping range, and whether the unit is pole mounted or pad mounted. With those we confirm losses, weight, oil quantity, the outline drawing and the lead time.