S11 series · 50-2500 kVA · 6-11 kV / 0.4 kV · Yyn0 or Dyn11
The S11 series is a three-phase oil-immersed distribution transformer for 10 kV networks with a 0.4 kV secondary, built in a fully sealed corrugated tank. The corrugations act as the cooling surface and as the expansion volume, so the unit has no conservator, no oil gauge and no breathing path to the atmosphere: the oil only meets air at the sealed top plate, which keeps moisture and oxygen out and slows oil ageing.
The core is laminated from high-grade cold-rolled silicon steel strip; the high-voltage winding is oxygen-free copper with a multi-layer cylinder structure, and all fasteners are treated against corrosion. Ratings run from 50 to 2500 kVA at 6, 6.3, 10, 10.5 or 11 kV primary with 0.4 kV secondary, Yyn0 or Dyn11 vector groups, and a tapping range of plus or minus 5 % or plus or minus 2 by 2.5 %.
No-load loss runs from 170 W at 50 kVA to 3400 W at 2500 kVA, and load loss at 75 C from 910 W to 21,000 W over the same range. Short-circuit impedance is 4 % up to 500 kVA and 4.5 % from 630 kVA. Total weight goes from 335 kg to 4250 kg, of which the oil is 75 kg to 765 kg, so the transport and foundation loads can be checked against the table below before the unit is ordered.
Price
On request
MOQ 1 piece · Lead time 30 days
General data for the S11 series. Ratings not listed are built to order.
| Parameter | Unit | Value |
|---|---|---|
| Rated high voltage | kV | 6 / 6.3 / 10 / 10.5 / 11 |
| Rated low voltage | V | 400 / 415 / 433 |
| Rated capacity | kVA | 50 - 2500 |
| Number of phases | - | Three |
| Rated frequency | Hz | 50 / 60 |
| Vector group | - | Yyn0 / Dyn11 |
| Tapping range | - | ±5 % or ±2×2.5 % |
| Short-circuit impedance | % | 4 (50-500 kVA), 4.5 (630-2500 kVA) |
| Tank type | - | Corrugated wall, fully sealed |
| Core | - | Laminated cold-rolled silicon steel |
| Winding | - | Oxygen-free copper, multi-layer cylinder |
| Design standard | - | IEC 60076, GB 1094 |
Load loss is stated at 75 C. Outline drawings with the bushing arrangement and the installation pitch are issued per rating.
Standard ratings at 10 kV / 400-433 V. Dimensions are tank length, width and height in mm.
| Rating (kVA) | No-load loss (W) | Load loss 75 C (W) | No-load current (%) | Oil weight (kg) | Total weight (kg) | L (mm) | W (mm) | H (mm) | Pitch L1/L2 (mm) |
|---|---|---|---|---|---|---|---|---|---|
| 50 | 170 | 910 | 2.0 | 75 | 335 | 750 | 590 | 950 | 400/400 |
| 80 | 240 | 1,310 | 1.8 | 100 | 435 | 815 | 600 | 1,005 | 450/450 |
| 100 | 290 | 1,580 | 1.6 | 105 | 475 | 815 | 680 | 1,000 | 450/450 |
| 125 | 340 | 1,890 | 1.5 | 120 | 555 | 975 | 580 | 1,060 | 550/550 |
| 160 | 400 | 2,310 | 1.4 | 140 | 680 | 1,035 | 640 | 1,020 | 550/550 |
| 200 | 480 | 2,730 | 1.3 | 140 | 710 | 1,060 | 675 | 1,120 | 550/550 |
| 250 | 560 | 3,200 | 1.2 | 165 | 830 | 1,170 | 750 | 1,135 | 550/550 |
| 315 | 670 | 3,830 | 1.1 | 190 | 985 | 1,140 | 695 | 1,275 | 660/660 |
| 400 | 800 | 4,520 | 1.0 | 205 | 1,120 | 1,285 | 835 | 1,215 | 660/660 |
| 500 | 960 | 5,410 | 1.0 | 240 | 1,300 | 1,235 | 755 | 1,355 | 660/660 |
| 630 | 1,200 | 6,200 | 0.9 | 280 | 1,590 | 1,235 | 755 | 1,355 | 660/660 |
| 800 | 1,400 | 7,500 | 0.8 | 305 | 1,790 | 1,545 | 1,005 | 1,395 | 820/820 |
| 1000 | 1,700 | 10,300 | 0.7 | 345 | 2,055 | 1,735 | 1,235 | 1,455 | 820/820 |
| 1250 | 1,950 | 12,000 | 0.6 | 390 | 2,480 | 1,815 | 1,285 | 1,475 | 820/820 |
| 1600 | 2,400 | 14,500 | 0.6 | 490 | 3,130 | 1,840 | 1,300 | 1,730 | 820/820 |
| 2000 | 2,900 | 18,300 | 0.5 | 580 | 3,565 | 1,840 | 1,305 | 1,650 | 820/1070 |
| 2500 | 3,400 | 21,000 | 0.4 | 765 | 4,250 | 1,890 | 1,370 | 1,790 | 820/1070 |
The transformer is designed and manufactured to the IEC 60076 series, with GB 1094 as the equivalent national basis. Routine tests are carried out on every unit; type test reports for a specific rating are issued with the technical offer on request.
Sealed corrugated tanks tolerate rain, dust and wide temperature swings, which suits overhead and pad mounted units on 11 kV and 10 kV feeders.
Step-down duty for factory distribution boards, with losses and impedance published per rating so the protection settings can be checked against the switchgear.
Outdoor compound or dedicated transformer room, where the sealed tank removes the need for periodic oil topping and conservator inspection.
Small ratings from 30 to 100 kVA for scattered loads, with low no-load loss to keep the cost of an idle feeder down.
What does fully sealed mean compared with a conservator tank?
A sealed unit has no conservator and no breathing path: the corrugated walls flex to absorb the oil expansion, and the oil contacts air only at the sealed top plate. Moisture ingress and oil oxidation are therefore much slower, and there is no oil gauge or silica gel to maintain.
Can the same unit run at 6 kV or 11 kV?
Yes. The series is built for 6, 6.3, 10, 10.5 and 11 kV primary with a 0.4 kV secondary. The rated voltage and the tapping range are fixed at order so the nameplate matches the network.
What is the difference between S11 and S13?
Both are sealed oil-immersed distribution transformers. S13 uses a lower-loss core and winding arrangement, so no-load loss is lower at the same rating; S11 is the standard loss level for most distribution projects.
What do you need to quote a unit?
Rated capacity, primary and secondary voltage, vector group, tapping range, and whether the unit is pole mounted or pad mounted. With those we confirm losses, weight, oil quantity, the outline drawing and the lead time.