S11 series · 50-2500 kVA · 13.2-20 kV / 400-433 V · Dyn11 or Yyn0
The S11 series is a three-phase oil-immersed distribution transformer for 20 kV networks with a 0.4 kV secondary, built in a fully sealed corrugated tank. The corrugations act as the cooling surface and as the expansion volume, so the unit has no conservator, no oil gauge and no breathing path: the oil meets air only at the sealed top plate, which keeps moisture and oxygen out and slows oil ageing.
Ratings run from 50 to 2500 kVA at 13.2 / 13.8 / 15 / 20 kV primary with 400, 415 or 433 V secondary, Dyn11 or Yyn0 vector groups, and a tapping range of plus or minus 5 % or plus or minus 2 by 2.5 %. No-load loss runs from 130 W at 50 kVA to 2340 W at 2500 kVA, and load loss at 75 C from 1010 W to 22,220 W over the same range.
Short-circuit impedance is 5.5 % up to 500 kVA, 6.0 % from 630 kVA. Total weight goes from 350 kg to 4885 kg, of which the oil is 80 kg to 645 kg, so transport and foundation loads can be checked against the table before the unit is ordered.
Price
On request
MOQ 1 piece · Lead time 30 days
General data for the S11 20 kV series. Ratings not listed are built to order.
| Parameter | Unit | Value |
|---|---|---|
| Rated high voltage | kV | 13.2 / 13.8 / 15 / 20 |
| Rated low voltage | V | 400 / 415 / 433 |
| Rated capacity | kVA | 50 - 2500 |
| Number of phases | - | Three |
| Rated frequency | Hz | 50 / 60 |
| Vector group | - | Dyn11 / Yyn0 |
| Tapping range | - | ±5 % or ±2×2.5 % |
| Short-circuit impedance | % | 5.5 % up to 500 kVA, 6.0 % from 630 kVA |
| Tank type | - | Corrugated wall, fully sealed |
| Core | - | Laminated cold-rolled silicon steel |
| Winding | - | Oxygen-free copper, multi-layer cylinder |
| Design standard | - | IEC 60076, GB 1094 |
Load loss is stated at 75 C. Outline drawings with the bushing arrangement and the installation pitch are issued per rating.
Standard ratings at 20 kV / 400-433 V. Dimensions are tank length, width and height in mm.
| Rating (kVA) | No-load loss (W) | Load loss 75 C (W) | No-load current (%) | Oil weight (kg) | Total weight (kg) | L (mm) | W (mm) | H (mm) | Pitch L1/L2 (mm) |
|---|---|---|---|---|---|---|---|---|---|
| 50 | 130 | 1,010 | 2.0 | 80 | 350 | 725 | 630 | 905 | 400/400 |
| 80 | 180 | 1,440 | 1.8 | 90 | 415 | 750 | 660 | 920 | 450/450 |
| 100 | 200 | 1,730 | 1.6 | 100 | 485 | 790 | 700 | 955 | 450/450 |
| 125 | 240 | 2,080 | 1.5 | 110 | 550 | 800 | 705 | 985 | 550/550 |
| 160 | 290 | 2,540 | 1.4 | 130 | 670 | 825 | 730 | 1,035 | 550/550 |
| 200 | 340 | 3,000 | 1.3 | 145 | 815 | 1,125 | 800 | 1,055 | 550/550 |
| 250 | 400 | 3,520 | 1.2 | 190 | 1,030 | 1,266 | 816 | 1,195 | 550/550 |
| 315 | 480 | 4,210 | 1.1 | 205 | 1,220 | 1,305 | 835 | 1,115 | 660/660 |
| 400 | 570 | 4,970 | 1.0 | 240 | 1,435 | 1,335 | 885 | 1,135 | 660/660 |
| 500 | 680 | 5,940 | 1.0 | 260 | 1,590 | 1,420 | 970 | 1,155 | 660/660 |
| 630 | 810 | 6,820 | 0.9 | 320 | 2,020 | 1,575 | 1,060 | 1,260 | 660/660 |
| 800 | 980 | 8,250 | 0.8 | 310 | 2,060 | 1,760 | 1,220 | 1,250 | 820/820 |
| 1000 | 1,150 | 11,330 | 0.7 | 360 | 2,430 | 1,715 | 1,200 | 1,675 | 820/820 |
| 1250 | 1,380 | 13,200 | 0.6 | 425 | 3,025 | 1,840 | 1,325 | 1,320 | 820/820 |
| 1600 | 1,660 | 15,950 | 0.6 | 490 | 3,365 | 1,885 | 1,320 | 1,425 | 820/820 |
| 2000 | 1,950 | 19,140 | 0.6 | 590 | 4,205 | 1,920 | 1,330 | 1,560 | 820/1070 |
| 2500 | 2,340 | 22,220 | 0.5 | 645 | 4,885 | 1,945 | 1,350 | 1,630 | 820/1070 |
The transformer is designed and manufactured to the IEC 60076 series, with GB 1094 as the equivalent national basis. Routine tests are carried out on every unit; type test reports for a specific rating are issued with the technical offer on request.
Step-down duty on 20 kV feeders for industrial estates, commercial buildings and municipal networks.
Sealed corrugated tanks tolerate rain, dust and wide temperature swings for outdoor installation.
Step-up duty at solar and wind sites, where the sealed tank removes periodic oil topping.
Factory distribution boards, with losses and impedance published per rating for protection settings.
What does fully sealed mean compared with a conservator tank?
A sealed unit has no conservator and no breathing path: the corrugated walls absorb the oil expansion, and the oil contacts air only at the sealed top plate, which slows oxidation and removes the need for silica gel.
Can the same unit run at other primary voltages?
Yes. The 20 kV class covers 13.2 / 13.8 / 15 / 20 kV primary with 400, 415 or 433 V secondary; the rated voltage and tapping range are fixed at order.
Why is the impedance different from the 10 kV series?
Higher voltage classes need more insulation and a larger winding leakage reactance, so the 20 kV series is built at 5.5 % against 4 % on the 10 kV units. The switchgear rating has to be checked against it.
What do you need to quote a unit?
Rated capacity, primary and secondary voltage, vector group, tapping range, and whether the unit is pole mounted or pad mounted. With those we confirm losses, weight, oil quantity, the outline drawing and the lead time.