What a usable CT model must contain before the first run

A CT saturation model needs four blocks before it is worth running: the transformer ratio, the secondary winding resistance, the connected burden, and a nonlinear magnetising branch built from the excitation curve. Drop the fourth and the model is a ratio box that can never saturate. Drop the burden and saturation arrives later than in the real circuit.

LZZW-35 outdoor current transformer in red epoxy housing with umbrella skirts and top primary terminals

The model has to answer a timing question, not an accuracy question: at what instant after fault inception does the core leave its linear region, and what does the secondary current look like afterwards. A relay measures a window of one cycle, sometimes less, and acts on what that window contains. A study that reports only a steady-state ratio error answers a question nobody asked.

Two modelling depths are worth distinguishing. A piecewise-linear saturable reactor is enough to get the time to saturation, the peak secondary current and the shape of the distorted waveform right, and it is what most protection studies use. A full hysteresis model adds the loop width and the residual flux left by a previous fault; add it only when the question depends on remanence, as it does for a reclose study.

The definitions of the three measured quantities the model consumes - knee-point voltage, winding resistance and excitation current - are set out in the guide to specifying a PX protection core, and they are not repeated here. What follows is how to turn those numbers into a model, and how to read what comes out of it.

How do you load the excitation curve into ATP/EMTP or Simulink?

The curve that arrives with the routine test sheet is normally a table of applied secondary voltage against excitation current, both in rms. Simulation tools want flux linkage against instantaneous current, so the first job is a conversion, not a data entry. For each row, flux linkage per turn is the peak voltage divided by angular frequency: lambda equals root-two times V rms divided by two pi f. At 50 Hz that is V rms divided by 222, so a knee point of 52.5 V becomes 0.236 weber-turns. Getting this step wrong by a factor of root-two shifts every saturation result by 41 percent, and it is the most common error in imported curves.

In ATP/EMTP the magnetising branch is entered as a nonlinear inductor, type 98, with a piecewise-linear flux-current table, or through the saturable transformer component. The table needs density near the knee: three or four points between 80 and 120 percent of knee voltage, one point at the origin, and one point at roughly ten times knee current so the saturated region is not extrapolated. Linear interpolation between widely spaced points produces a curve that is too stiff above the knee and understates the secondary current in the saturated part of the cycle.

In Simulink, the Saturable Transformer block or the Simscape Electrical current transformer model takes the same characteristic, as a per-unit or SI flux-current table. Whichever tool is used, the time step must resolve the event: a saturation beginning 1 ms after fault inception is only 50 points wide at a 20 microsecond step, and a default 50 microsecond step smears the knee across the quarter cycle.

The primary side is where the model and the hardware most often part company. On the cast post-type body shown below, the primary is a winding cast into the resin and the terminals are marked P1 and P2, so the model carries a fixed number of primary turns and a fixed polarity. On a window or through-core unit the primary is the installed busbar or cable, one turn unless the conductor is threaded more than once, and the effective ratio follows the threading rather than the nameplate alone.

Red epoxy-cast indoor post-type current transformer marked P1 and P2 with a covered secondary terminal block

That difference is not cosmetic. A through-core unit installed with two passes through the bore has half the nameplate ratio and twice the secondary current for the same primary fault, so a single-turn model predicts saturation at the wrong fault level. Where a project mixes post-type panels with busbar units, build two models rather than reusing one excitation table with a different ratio: winding resistance and leakage reactance differ as well.

Which parameters move the answer most

A sensitivity pass is worth more than a finer mesh. The table below lists the inputs that change the time to saturation, where each one comes from, and what a 10 percent error in it does to the result. The numbers in the example column belong to the worked case in the next section, not to a catalogue.

Model inputSymbolWhere it comes fromExample valueEffect of a 10 percent error
Knee-point voltageVkExcitation test, or ALF times rated secondary current times the loop resistance52.5 VTime to saturation moves roughly in proportion, about 10 percent
Secondary winding resistanceRctDC measurement on the delivered unit, stated as a maximum on the datasheet0.45 ohmPlus 0.045 ohm raises the loop by 6 percent and shortens saturation by about 6 percent
Connected burdenZbRelay current input plus leads, not the rated VA0.30 ohmPlus 0.03 ohm shortens saturation by about 4 percent; a 0.1 ohm error costs 12 percent
Residual fluxBrState left by the previous interruption; not on any nameplate0 to 0.8 of saturation fluxCan halve the first-cycle time to saturation on a reclose
System time constanttauX over R at the fault point, from the network study31.8 ms at X/R 10Sets how much of the offset is still present when the core reaches the knee
Primary fault currentIpMaximum and minimum fault levels from the protection study20 kASecondary current scales linearly, so the time to saturation falls by about 9 percent
Three through-core current transformer rings with red bores mounted on brackets before busbar installation

The burden row is the one that quietly ruins otherwise careful studies. A 600/5 protection core rated at 15 VA is tested with 0.6 ohm connected; a modern numerical relay plus 60 metres of 4 square millimetre leads may present 0.25 to 0.35 ohm. Modelling the rated burden instead of the installed one lengthens the predicted time to saturation, and the error is in the unsafe direction. The burden and lead-size calculation gives the loop resistance for a given run length and conductor, and that figure is what belongs in the model.

Worked case: a 20 kA fault on a 600/5 protection core

Take a 600/5 ratio in a 10 kV indoor body, protection core 10P10, winding resistance 0.45 ohm and a connected burden of 0.30 ohm. These are stated assumptions for the arithmetic; substitute the measured values. With a rated burden of 15 VA, which is 0.6 ohm at 5 A, the knee-point voltage implied by the accuracy limit factor is 10 times 5 A times 1.05 ohm, or 52.5 V, corresponding to a flux capacity of 0.236 weber-turns.

For a fully offset current, the volt-seconds the core must absorb rise almost linearly in the first few milliseconds, because the alternating term and the decaying direct term both contribute. The closed-form estimate is the flux capacity divided by twice the loop resistance times the secondary current. On the numbers above, a 20 kA fault gives a secondary current of 166.7 A and a loop resistance of 0.75 ohm, so the estimate is 0.236 divided by 250, or 0.95 ms.

Primary fault currentIdeal secondary currentTime to saturation, fully offsetElectrical angleSymmetrical current
6 kA (accuracy limit, 10 x rated)50 A3.2 ms57 degreesNo saturation, 51 percent of flux capacity used
12 kA100 A1.6 ms28 degreesMarginal, saturates at the crest
20 kA166.7 A0.95 ms17 degreesSaturates at about 36 degrees
31.5 kA262.5 A0.60 ms11 degreesSaturates at about 22 degrees

Three things follow. First, on a fully offset 20 kA fault the core saturates inside the first 20 degrees of the fault, which is well before the first current peak, so there is no clean first peak to measure. Second, the same core does not saturate at all on a symmetrical 6 kA fault, which is exactly the current its accuracy limit is defined at: the standard rating and the transient duty are different tests, and a core that passes one can fail the other. Third, once the core is out of its linear region the secondary current is limited by the knee voltage divided by the loop resistance, about 99 A peak here against an ideal 236 A, so the relay sees less than half the current it was promised at the moment the current matters most.

For scale, the LZZBJ9-10 at 600 A is published with a one-second thermal current of 45 kA and a dynamic current of 100 kA, so a 20 kA fault is comfortably inside the thermal withstand of the primary conductor. The unit survives the fault and is still inside its type-tested duty; the protection core has nonetheless stopped reproducing the current. Withstand and fidelity are separate specifications, and only the second one appears in a saturation study.

Why does DC offset decide saturation more than fault level?

Flux is the integral of voltage, and voltage in the secondary loop is the loop resistance times the current the core is trying to deliver. A fault that closes at a voltage zero produces a current with a fully offset direct component, and that component does not change sign for the first cycle: it adds to the alternating term instead of cancelling it, roughly doubling the volt-seconds the core absorbs in the first 20 ms. A fault closing near a voltage peak produces almost no offset, and the same core absorbs half as much flux.

The decay rate of that offset is set by the system time constant, X over R divided by angular frequency. At X/R 10 the time constant is 31.8 ms, which is longer than a 20 ms cycle, so the offset is still near full value when the first peak arrives. At X/R 3 it is 9.5 ms, and most of the offset has gone by the first peak. Two feeders with the same fault level can therefore load the same CT very differently, which is why a study that states a fault current without an X/R ratio is not reproducible.

This is why transient-performance classes exist. A P class core is rated for symmetrical current up to its accuracy limit factor, while IEC 61869-2 writes the transient classes - TPX, TPY, TPZ - around a duty cycle of a fault and its reclosure. TPY cores carry small air gaps that limit residual flux; TPZ cores carry larger gaps so the direct component does not reach the secondary at all. For unit protection on a 20 kA busbar, the class on the datasheet is a design decision.

How do you read the distortion, and when does protection actually fail?

Report four quantities from the run rather than a single waveform picture. The first is the time to saturation, which is the instant the flux reaches its capacity. The second is the saturation angle, the electrical angle over which the core is out of its linear region in each half cycle. The third is the fundamental ratio: the magnitude of the fundamental component from a one-cycle discrete Fourier transform, divided by the ideal secondary current. The fourth is total harmonic distortion over the same window, which describes the shape but is a poor decision variable on its own because a heavily saturated current can show a large distortion while the fundamental is still usable.

The fundamental ratio is what a numerical relay effectively measures, so compute it window by window rather than once at the end. The first window contains the offset and the saturation transient, the second a decaying offset, and by the fourth or fifth the waveform may have recovered. A single steady-state value hides the interval in which protection decides.

What the model showsWhat it means for the schemeWhat to change before the order
Saturation after 5 ms or later, fundamental ratio above 0.9Fundamental measurement survives the offset; accuracy class error governsNothing on the CT; confirm the relay's declared operating time
Saturation between 2 and 5 ms, fundamental ratio 0.5 to 0.9First window is short of current; time-graded settings may lose selectivityReduce connected burden first, then raise the accuracy limit factor
Saturation under 2 ms, fundamental ratio below 0.5Secondary output is a series of narrow pulses; differential and distance elements see the wrong quantityHigher knee-point voltage, TP class core, or a relay with saturation detection
Recovery within one cycle, offset decaysSecond and third windows are trustworthy; first-cycle decisions are notCheck whether the scheme takes a first-cycle decision at all

One expectation is worth correcting, because it drives a lot of unnecessary hardware. For an instantaneous overcurrent element set at 1.2 times rated current, refusal to trip at 20 kA is not a realistic failure mode: even with a fundamental ratio of 0.3, the relay sees 50 A against a 6 A setting, more than eight times pickup. The failures that saturation actually produces are different ones. In a differential scheme, saturation at one end while the other end is not saturated produces a spurious differential current and can trip on an external fault. In a distance scheme, the collapsed secondary voltage-current relationship moves the measured impedance and the element either over-reaches or under-reaches. In a directional element, the phase shift during saturation can invert the decision. Those are the outcomes to test for, and each one needs the model to keep the CT and the relay algorithm in the same run.

Which modelling mistakes cost money on site?

The expensive ones are all optimistic, and they share a pattern: they replace a measured value with a convenient one. Modelling the rated burden instead of the connected burden is the most common; it can overstate the time to saturation by 30 percent on a long lead run. Modelling the accuracy limit factor as a saturation threshold is the second: the factor describes composite error at a stated burden with symmetrical current, not the current at which the core stops working under offset.

Ignoring residual flux is the third, and it shows up only on the second fault of the night. A core that has just interrupted a fault can hold a large fraction of its flux capacity, so the next asymmetrical fault saturates in a fraction of the predicted time. A study validated against one commissioning record often matches on the first fault and diverges on the reclose.

The fourth is a fix applied without a re-run: raising the ratio to cure saturation. A 1200/5 core instead of 600/5 halves the secondary current for the same fault, which does postpone saturation, but it also halves the current the relay sees at low load, and a 0.5 class core at 1200/5 may no longer hold its accuracy at the 5 percent load the feeder actually carries overnight. The accuracy class limits table shows how the error limit is stated as a function of rated current, and the trade is visible once both ends of the load range are plotted. Re-running the model with the new ratio and the new class is the only way to know whether the fix is a fix.

What to write into the RFQ and the datasheet

A supplier cannot build to a simulation, so the study has to become requirements. State the fault level and the X/R ratio at the CT position, not just the system voltage, because the two together define the transient duty. State ratio, class and burden per core, with the burden as the connected value for your lead length. Where a P class core is specified, add the minimum knee-point voltage and maximum winding resistance: those are the numbers the simulation used.

Ask for the excitation curve, not only the class, and ask for it at three points at least: 80 percent, 100 percent and 120 percent of knee voltage, plus one point at ten times knee current. Ask which tests are routine and which are type tests, and ask for the type-test report to IEC 61869-2 with the certificate number. Where the scheme is unit protection on a high fault level, state the transient class and the duty cycle required; if residual flux is a concern, say so and ask what the core is designed to retain.

  • System voltage, highest system voltage and fault level with X/R at the CT position
  • Ratio, class and connected burden for the metering core and the protection core, stated separately
  • Minimum knee-point voltage and maximum winding resistance, where a P class or PX core is specified
  • Excitation curve at four points, or the type-test report that contains it
  • Transient class and duty cycle, where the scheme is unit protection
  • Routine test report, nameplate drawing and terminal arrangement for approval

A type test proves the design; a routine test proves the unit. The simulation ran against a curve, and that curve has to belong to the unit on site: ask for the routine excitation test on the delivered unit, or measure it at commissioning with a secondary injection set, and update the model if the knee point differs from the design value beyond your tolerance.

Where Nahu Group Fits

Nahu Group manufactures epoxy-cast current transformers from 0.66 kV to 35 kV across nineteen models, including the LZZBJ9-10 indoor range from 5 A to 3000 A, the LZZBJ9-24 and LZZBJ9-35 for 24 kV and 35 kV panels, and the LZZW-35 outdoor unit. Models are type tested to IEC 61869-2 and the reports are supplied with the order. Ratio tables, thermal and dynamic currents and class combinations are on the current transformer product page, and the window and busbar types sit alongside them in the specialty and busbar range.

For a configuration rather than a brochure, send the fault level and X/R at the CT position, the ratio, class and connected burden per core, the panel drawing, and the quantity. Where the study has already been run, send the knee-point voltage and winding resistance it assumed; the delivered unit can then be checked against those numbers rather than against a generic class. The LZZBJ9-10 rating table is a useful starting point for a 10 kV indoor position with a 600/5 protection core.