Home/ Products/ Drop-Type Fuses/ RW12-35 Porcelain

RW12-35 porcelain drop-out fuse cutout

Drop-Type Fuses · 35 kV · High-strength porcelain

RW12-35 porcelain drop-out fuse cutout for 35 kV overhead lines
Drop-Type Fuses

Overview

The RW12-35 is a 35 kV expulsion drop-out fuse cutout for 33 kV and 35 kV overhead distribution lines. Its fuse link carries the load current; on a fault the link melts, the arc is quenched inside the tube and the carriage drops to give a visible break. The line section is then isolated until the link is replaced from a hot-stick.

This version uses a high-strength porcelain insulator with a galvanised steel base. Porcelain is still the reference insulation in many national utility standards, it holds its shape at higher continuous temperatures than polymer and it is unaffected by UV. The trade-off is weight and the risk of shattering on impact, which is why polymer is usually specified on new pole-top work.

At a glance

Model
RW12-35
Housing
High-strength porcelain
Rated voltage
35 kV
Rated current
100 / 200 A
Lightning impulse
170 kV
Standard
IEC 60282-2

Price

On request

MOQ 1 piece

Where it is installed

Typical applications for the 35 kV class cutout.

  • Pole-mounted transformer protection — the most common duty: one cutout per phase on the transformer cross-arm.
  • 33 kV and 35 kV overhead lines — sectionalising taps and spur lines so a single fault does not trip the feeder.
  • Capacitor banks — visible isolation of pole-mounted capacitor racks for maintenance.
  • Rural electrification — cheap, hot-stick serviceable protection where a circuit breaker is not justified.

Technical data & specifications

Manufacturer data for the 35 kV High-strength porcelain version.

Parameter100 A version200 A version
Rated voltage35 kV35 kV
Rated current / base rated current100 A200 A
Rated frequency50 Hz50 Hz
Rated short-circuit breaking current (kA / A)12.5/100 · 16/10012.5/200 · 16/200
Power-frequency withstand, wet85 / 95 kV85 / 95 kV
Power-frequency withstand, dry90 / 95 kV90 / 95 kV
Rated lightning impulse voltage170 kV170 kV
Creepage distance875 mm875 mm
Mechanical endurance500 operations500 operations
Altitude1,000 m1,000 m
Ambient temperature-40 ... +70 °C-40 ... +70 °C
Overall dimensions68 x 38 x 16 cm68 x 38 x 16 cm

Values as published in the manufacturer parameter table. Breaking ratings are quoted for the 100 A and 200 A fuse links respectively.

Construction and materials

Outline dimensions

RW12-35 Porcelain Drop-Out Fuse Cutout outline dimensions (mm)

Dimensions on the drawing: 680 mm overall height, 530 mm insulator height, 490 mm fuse-tube length, 380 mm mounting pitch, 25 mm bracket hole. Check the drawing against your cross-arm before ordering.

  • Silver-plated copper terminals and contact components.
  • 304 stainless steel contact springs.
  • Upper hood, upper contact plate, upper moving contact and self-aligning hook.
  • UV-resistant fuse tube with internal arc-quenching liner.
  • High-strength porcelain insulator; steel fittings hot-dip galvanised to at least 80 µm.
  • Cast-copper or forged-copper fittings available on request.

Before you order

Three numbers decide whether a 35 kV cutout is right for a line: the system voltage (33 or 35 kV), the transformer rating that sets the fuse-link current, and the creepage the site needs. The High-strength porcelain version gives 875 mm of creepage, which suits light to medium pollution; for heavy industrial or coastal pollution ask for a longer shed profile and confirm the figure on the drawing. If your specification quotes a 12(15) kV cutout, it is a different product — see the RW33-15 and RW12-15F pages for the 10–15 kV class.

Common questions

Is RW12-35 the same voltage class as RW33-15?

No. RW12-35 is rated 35 kV for 33 kV and 35 kV lines. RW33-15 carries 33 only as a series designator and is rated 12(15) kV - it must not be installed on a 33 kV line.

When should I choose porcelain instead of polymer?

When the utility specification names porcelain, when the cutout is installed where mechanical impact is unlikely, or when local stock and spares are porcelain. Porcelain has the wider ambient range (-40 to +70 C against -10 to +70 C for the polymer version).

What is the difference between the 100 A and 200 A versions?

The rated current and the breaking rating of the fuse link: 12.5 kA and 16 kA at 100 A, and 12.5 kA and 16 kA at 200 A. The insulator and the frame are the same, so the choice follows the transformer rating.

Do you supply the fuse links and the mounting bracket?

Cutouts are quoted with or without links and with the pole bracket you specify. Give us the transformer rating and the cross-arm drawing and we will quote the complete set.