Drop-Type Fuses · 35 kV · High-strength porcelain
The RW12-35 is a 35 kV expulsion drop-out fuse cutout for 33 kV and 35 kV overhead distribution lines. Its fuse link carries the load current; on a fault the link melts, the arc is quenched inside the tube and the carriage drops to give a visible break. The line section is then isolated until the link is replaced from a hot-stick.
This version uses a high-strength porcelain insulator with a galvanised steel base. Porcelain is still the reference insulation in many national utility standards, it holds its shape at higher continuous temperatures than polymer and it is unaffected by UV. The trade-off is weight and the risk of shattering on impact, which is why polymer is usually specified on new pole-top work.
Price
On request
MOQ 1 piece
Typical applications for the 35 kV class cutout.
Manufacturer data for the 35 kV High-strength porcelain version.
| Parameter | 100 A version | 200 A version |
|---|---|---|
| Rated voltage | 35 kV | 35 kV |
| Rated current / base rated current | 100 A | 200 A |
| Rated frequency | 50 Hz | 50 Hz |
| Rated short-circuit breaking current (kA / A) | 12.5/100 · 16/100 | 12.5/200 · 16/200 |
| Power-frequency withstand, wet | 85 / 95 kV | 85 / 95 kV |
| Power-frequency withstand, dry | 90 / 95 kV | 90 / 95 kV |
| Rated lightning impulse voltage | 170 kV | 170 kV |
| Creepage distance | 875 mm | 875 mm |
| Mechanical endurance | 500 operations | 500 operations |
| Altitude | 1,000 m | 1,000 m |
| Ambient temperature | -40 ... +70 °C | -40 ... +70 °C |
| Overall dimensions | 68 x 38 x 16 cm | 68 x 38 x 16 cm |
Values as published in the manufacturer parameter table. Breaking ratings are quoted for the 100 A and 200 A fuse links respectively.

Dimensions on the drawing: 680 mm overall height, 530 mm insulator height, 490 mm fuse-tube length, 380 mm mounting pitch, 25 mm bracket hole. Check the drawing against your cross-arm before ordering.
Three numbers decide whether a 35 kV cutout is right for a line: the system voltage (33 or 35 kV), the transformer rating that sets the fuse-link current, and the creepage the site needs. The High-strength porcelain version gives 875 mm of creepage, which suits light to medium pollution; for heavy industrial or coastal pollution ask for a longer shed profile and confirm the figure on the drawing. If your specification quotes a 12(15) kV cutout, it is a different product — see the RW33-15 and RW12-15F pages for the 10–15 kV class.
No. RW12-35 is rated 35 kV for 33 kV and 35 kV lines. RW33-15 carries 33 only as a series designator and is rated 12(15) kV - it must not be installed on a 33 kV line.
When the utility specification names porcelain, when the cutout is installed where mechanical impact is unlikely, or when local stock and spares are porcelain. Porcelain has the wider ambient range (-40 to +70 C against -10 to +70 C for the polymer version).
The rated current and the breaking rating of the fuse link: 12.5 kA and 16 kA at 100 A, and 12.5 kA and 16 kA at 200 A. The insulator and the frame are the same, so the choice follows the transformer rating.
Cutouts are quoted with or without links and with the pole bracket you specify. Give us the transformer rating and the cross-arm drawing and we will quote the complete set.