10 kV Amorphous Alloy Oil-Immersed Transformer

SBH15-M series · 30-2500 kVA · 10 kV / 400-433 V · SH15 or SH16 core

SBH15-M amorphous alloy oil-immersed distribution transformer
Oil-Immersed Distribution Transformer

Overview

The SBH15-M series uses a wound amorphous alloy core instead of silicon steel. The alloy has no crystal structure, so hysteresis loss is very low: no-load loss is 32 W at 30 kVA and 450 W at 1000 kVA, against 830 W for the S13-M silicon steel unit at the same rating. In a feeder that is energised all day but loaded for a few hours, that difference is the largest single item in the loss bill.

Ratings run from 30 to 2500 kVA at 10 kV with 400, 415 or 433 V secondary. The high-voltage winding is rectangular and cast in resin, the low-voltage winding is copper foil, and the vector group is Dyn11 or Yyn0. Two core grades are listed, SH15 and SH16, with SH16 giving the lower no-load loss column.

The tank follows the sealed arrangement: the corrugated wall takes the oil expansion and replaces the conservator, so the oil contacts air only at the sealed top plate. Note that the factory table for this series lists losses and impedance but not weights or outline dimensions; those are issued on the drawing for the ordered rating.

At a glance

Model
SBH15-M-1000/10
Type
Amorphous alloy, sealed, three phase
Rated capacity
30 - 2500 kVA
Voltage
10 kV / 400-433 V
Vector group
Yyn0 / Dyn11
Tank
Corrugated, fully sealed

Price

On request

MOQ 1 piece · Lead time 30 days

Technical specifications

Table 1 - General data
ParameterUnitValue
Rated high voltagekV6 / 6.3 / 10 / 10.5 / 11
Rated low voltageV400 / 415 / 433
Rated capacitykVA30 - 2500
Number of phases-Three
Rated frequencyHz50 / 60
Vector group-Yyn0 / Dyn11
Tapping range-±5 % or ±2×2.5 %
Core-Amorphous alloy, SH15 or SH16 grade
Tank type-Corrugated wall, fully sealed
Design standard-IEC 60076, GB 1094

SBH15-M losses and impedance

Standard ratings at 10 kV / 400-433 V. Load loss is stated at 75 C. Weights and outline dimensions are issued on the drawing for the ordered rating.

Table 2 - SBH15-M losses and impedance
Rating (kVA)No-load SH15 (W)No-load SH16 (W)I0 SH15 (%)I0 SH16 (%)Load 2 Dyn11 (W)Load 2 Yyn11 (W)Load 1 Dyn11 (W)Load 1 Yyn11 (W)Impedance (%)
3032331.51.06306005655104.0
5043381.20.99108708207854.0
6350421.10.71,0901,0409809354.0
8060461.00.71,3101,2501,1801,1254.0
10075580.90.71,5801,5001,4201,3504.0
12585680.80.61,8901,8001,7001,6204.0
160100780.60.52,3102,2002,0801,9804.0
200120900.60.52,7302,6002,4552,3404.0
2501401100.60.53,2003,0502,8802,7454.0
3151701300.50.43,8303,6503,4453,2854.0
4002001600.50.44,5204,3004,0703,8704.0
5002401900.50.45,4105,1504,8704,6354.0
6303202300.30.36,2006,2005,5805,5804.5
8003802800.30.37,5007,5006,7506,7504.5
10004503300.30.310,30010,3009,2709,2704.5
12505303900.20.212,00012,00010,80010,8004.5
16006304700.20.214,50014,50013,05013,0504.5
20007505700.20.218,30018,30016,47016,4705.0
25009006800.20.221,20021,20019,08019,0805.0

Standards and design basis

The transformer is designed and manufactured to the IEC 60076 series, with GB 1094 as the equivalent national basis. Routine tests are carried out on every unit; type test reports for a specific rating are issued with the technical offer on request.

Frequently asked questions

What is the difference between SH15 and SH16?

Both are amorphous alloy cores. SH16 is the lower-loss grade: no-load loss at 1000 kVA is 330 W against 450 W for SH15. The load loss columns are the same.

Is the tank sealed?

Yes. The corrugated wall absorbs the oil expansion, so there is no conservator, no oil gauge and no silica gel breather.

Why are there two load loss columns?

The table lists loss for Dyn11 and Yyn11 connections and for two efficiency classes; the required combination is fixed at order.