S13-M series · 30-2500 kVA · 6-11 kV / 400-433 V · Yyn0 or Dyn11
The S13-M series is the low-loss version of the sealed 10 kV distribution transformer. The core is built from high-grade cold-rolled grain-oriented silicon steel with a step-lap joint, and the winding arrangement was reworked against the earlier S9 platform, so no-load loss falls to 80 W at 30 kVA and 830 W at 1000 kVA against 1150 W on the standard S11 unit of the same rating.
Ratings run from 30 to 2500 kVA at 6, 6.3, 10, 10.5 or 11 kV primary with 400, 415 or 433 V secondary, Yyn0 or Dyn11 vector groups, and a tapping range of plus or minus 5 % or plus or minus 2 by 2.5 %. Load loss at 75 C runs from 600 W to 21,200 W over the same range.
The tank is corrugated and fully sealed: the wall flexes with the oil expansion, so there is no conservator, no oil gauge and no silica gel breather. Total weight goes from 295 kg to 5005 kg, of which the oil is 75 kg to 800 kg.
Price
On request
MOQ 1 piece · Lead time 30 days
| Parameter | Unit | Value |
|---|---|---|
| Rated high voltage | kV | 6 / 6.3 / 10 / 10.5 / 11 |
| Rated low voltage | V | 400 / 415 / 433 |
| Rated capacity | kVA | 30 - 2500 |
| Number of phases | - | Three |
| Rated frequency | Hz | 50 / 60 |
| Vector group | - | Yyn0 / Dyn11 |
| Tapping range | - | ±5 % or ±2×2.5 % |
| Core | - | Step-lap grain-oriented silicon steel |
| Tank type | - | Corrugated wall, fully sealed |
| Design standard | - | IEC 60076, GB 1094 |
Standard ratings at 10 kV / 400-433 V. Load loss is stated at 75 C. Short-circuit impedance is 4 % up to 315 kVA and 4.5 % from 400 kVA.
| Rating (kVA) | No-load loss (W) | Load loss 75 C (W) | No-load current (%) | Oil weight (kg) | Total weight (kg) | L (mm) | W (mm) | H (mm) | Pitch L1/L2 (mm) |
|---|---|---|---|---|---|---|---|---|---|
| 30 | 80 | 600 | 0.80 | 120 | 75 | 295 | 755 | 470 | 960 |
| 50 | 100 | 870 | 0.75 | 200 | 90 | 390 | 765 | 545 | 990 |
| 63 | 110 | 1,040 | 0.70 | 235 | 100 | 450 | 815 | 555 | 1035 |
| 80 | 130 | 1,250 | 0.70 | 250 | 105 | 485 | 830 | 605 | 1040 |
| 100 | 150 | 1,500 | 0.65 | 300 | 115 | 555 | 850 | 620 | 1075 |
| 125 | 170 | 1,800 | 0.65 | 370 | 135 | 660 | 870 | 635 | 1170 |
| 160 | 200 | 2,200 | 0.60 | 465 | 150 | 790 | 900 | 640 | 1280 |
| 200 | 240 | 2,600 | 0.60 | 540 | 190 | 940 | 960 | 725 | 1305 |
| 250 | 290 | 3,050 | 0.50 | 660 | 205 | 1,095 | 1,160 | 690 | 1345 |
| 315 | 340 | 3,650 | 0.45 | 750 | 250 | 1,265 | 1,240 | 760 | 1375 |
| 400 | 410 | 4,300 | 0.40 | 780 | 265 | 1,375 | 1,430 | 940 | 1430 |
| 500 | 480 | 5,100 | 0.40 | 850 | 300 | 1,680 | 1,435 | 950 | 1435 |
| 630 | 570 | 6,200 | 0.40 | 940 | 410 | 1,850 | 1,520 | 1,075 | 1475 |
| 800 | 700 | 7,500 | 0.40 | 1,175 | 500 | 2,260 | 1,535 | 1,080 | 1690 |
| 1000 | 830 | 10,300 | 0.30 | 1,265 | 510 | 2,390 | 1,540 | 1,080 | 1715 |
| 1250 | 970 | 12,000 | 0.30 | 2,090 | 570 | 3,370 | 1,700 | 1,185 | 1740 |
| 1600 | 1,170 | 14,500 | 0.30 | 2,530 | 635 | 3,950 | 1,715 | 1,210 | 1780 |
| 2000 | 1,700 | 17,500 | 0.50 | 3,095 | 750 | 4,715 | 1,745 | 1,285 | 1900 |
| 2500 | 2,040 | 21,200 | 0.40 | 3,130 | 800 | 5,005 | 1,980 | 1,525 | 1920 |
The transformer is designed and manufactured to the IEC 60076 series, with GB 1094 as the equivalent national basis. Routine tests are carried out on every unit; type test reports for a specific rating are issued with the technical offer on request.
How does S13-M differ from S11?
S13-M uses a lower-loss core and a revised winding arrangement, so no-load loss is about 30 % lower at the same rating: 830 W against 1150 W at 1000 kVA.
Is the tank sealed?
Yes. The corrugated wall absorbs the oil expansion, so the unit has no conservator and no breathing path to the atmosphere.
What do you need to quote a unit?
Rated capacity, primary and secondary voltage, vector group, tapping range and the installation type.