A potential transformer (PT) — called a voltage transformer (VT) in IEC terminology — is an instrument transformer that scales a high system voltage down to a standardized, safe low voltage, typically 100 V or 110 V at rated primary, for meters, protective relays and instrumentation. It is not a power transformer. A PT carries almost no load and exists only to reproduce the primary-voltage waveform accurately at a known ratio, which is why a 100 VA PT and a 100 kVA transformer are different machines despite both having windings.

That single sentence answers most "what is a potential transformer" questions: it is a measurement device, not an energy-transfer device.

JDZX11-20 indoor voltage transformer with three epoxy-cast phases and porcelain or silicone terminal bushings, the electromagnetic potential transformer type explained here

What a Potential Transformer Actually Does

Four jobs define the device, and the fourth is what separates it from everything else in the substation.

  • Steps the voltage down at a fixed ratio. A 11 kV system uses a ratio such as 11000/√3 : 100/√3 V, so the secondary stays at the standardized value whatever the primary.
  • Galvanically isolates the network from the instruments. The metering and protection equipment never touches the high-voltage conductor.
  • Delivers a standardized secondary. Because the secondary is fixed by standard, a meter or relay is interchangeable between installations.
  • Holds the ratio error inside an accuracy class. It does this only because its burden — the load it drives — is kept tiny.

The voltage transformer covers the indoor and outdoor builds used from 12 kV up to sub-transmission voltages.

Potential Transformer vs Power Transformer: The Three Real Differences

PropertyPotential (voltage) transformerPower transformer
PurposeReproduce voltage accurately for measurement and protectionTransfer active and reactive power
Rated powerTens of VA (e.g. 30, 50, 100 VA)kVA to MVA
AccuracyHeld to class 0.2 / 0.5 (metering), 3P / 6P (protection)Not ratio-accuracy rated
Burden it drivesNear-zero, tightly specifiedFull rated load
CoolingNatural convection, no forced coolingOil, ONAN/ONAF, often forced
Failure mode of concernRatio drift, phase error, core saturationThermal, dielectric breakdown under load

The headline difference buyers care about is the first row: capacity. A PT is rated in VA because it is designed to drive almost nothing. A power transformer is rated in kVA because driving load is its whole job. The accuracy row is the second: a PT is certified to a ratio class; a power transformer is not.

JSZV12-10R indoor voltage transformer single-phase epoxy resin cast body showing terminal box and mounting base used in 10 kV metering

How a PT Is Built: Electromagnetic, Capacitive, Electronic

  • Electromagnetic (inductive) VT. A wound transformer, the common choice from 12 kV to around 36–72 kV. Simple, accurate, and the type shown throughout this article.
  • Capacitive VT (CVT). A capacitor divider plus a small electromagnetic unit. Above roughly 72.5 kV it is cheaper than a wound unit, and the same divider can feed a line-carrier coupling device.
  • Electronic (non-conventional) VT. A voltage sensor with a converter, standardized under IEC 61869-10 and IEC 61869-11 for digital substations using IEC 61850 sampled values.

For the 12–36 kV networks most NAHU customers run, the electromagnetic unit dominates. The JDZX11-20 and JSZV12-10R are representative indoor builds.

Accuracy Classes and Burden — Why They Decide the Rating

Accuracy is expressed two ways and both matter. IEC 61869-3 defines metering classes 0.1, 0.2, 0.5 and 1.0, and protection classes 3P and 6P. Each class sets a limit on ratio error and phase-displacement error, but only at the rated burden and below it. Burden is the total load — meters, relay coils, wiring — expressed in VA at a stated power factor, usually 0.8 inductive.

ApplicationTypical classWhat goes wrong if burden is wrong
Revenue metering0.2 or 0.5Oversized burden → ratio error → billing dispute
Protection (distance, overvoltage)3P or 6PUnder-burdened → saturation on fault → slow or wrong trip
General indication1.0 or 3.0Less critical, but still bounded by class

A PT specified without its connected burden is a PT that may pass the factory test and fail in service. State the burden the secondary must support, not just the ratio.

JDZ10-10B indoor voltage transformer three-phase epoxy cast unit with labelled terminals for metering and protection secondaries

Sizing a PT for a Metering or Protection Circuit

Sizing is mostly burden accounting, and the steps are the same whether the PT feeds a meter or a relay.

  • Add the burden of every connected device — meter, relay, transducer, and the wiring (long secondary runs add VA fast).
  • Keep the actual burden between about 25% and 100% of the rated burden; a PT driven far below its rating still meets class, but one driven above it does not.
  • Choose the class against the job: 0.2 / 0.5 for metering, 3P for protection.
  • Fuse the primary for fault clearing, and earth exactly one secondary terminal so a primary-to-secondary fault cannot raise the secondary to system potential.

Where the PT sits with current transformers in a common enclosure, see the high-voltage metering boxes; the same burden rules apply to the CTs, covered in the current transformer guide.

Where Potential Transformers Sit in the Substation

A PT appears wherever a voltage has to be measured safely: incoming feeders, busbar sections, metering cabinets and ring main units. On a three-phase system the usual arrangement is three single-phase VTs for the phase-to-phase and phase-to-earth voltages, plus an open-delta (V-V or broken-delta) connection to derive the residual (zero-sequence) voltage for earth-fault detection. Single-phase units are preferred because one spare covers every position.

What to Write Into the RFQ

ParameterText to put in the specification
RatioPrimary / secondary voltage, e.g. 11000/√3 : 100/√3 V, single or three-phase
ClassMetering 0.2 or 0.5, protection 3P; name both if the unit serves both
BurdenRated burden in VA at cos φ 0.8, and the actual connected burden
Insulation levelRated voltage, power-frequency and impulse withstand per IEC 60071
Frequency50 Hz or 60 Hz — a 50 Hz unit on a 60 Hz system is wrong
MountingIndoor epoxy-cast, outdoor, or in a metering box / RMU
EarthingOne secondary terminal earthed; state which

Frequently Asked Questions About Potential Transformers

What is the difference between a potential transformer and a power transformer?

A potential transformer is an instrument transformer rated in tens of VA that reproduces the primary voltage accurately at a fixed ratio for meters and relays. A power transformer is rated in kVA or MVA and exists to transfer energy. The PT is held to a ratio accuracy class; the power transformer is not.

What is the standard secondary voltage of a potential transformer?

For IEC systems the standardized secondary voltage is 100/√3 V per phase on a 100 V line-to-line basis, or 100 V where a single-phase unit is used phase-to-earth. IEEE practice in North America commonly uses 120 V. The secondary voltage is fixed by standard, not by the primary.

Why does a PT secondary have to be grounded?

One secondary terminal is earthed so that, if the primary-to-secondary insulation fails, the low-voltage side cannot rise to system potential. A single earthing point only — a second earth creates a parallel path that distorts the ratio and can mask a fault.

What PT accuracy class do I need for metering?

Metering normally uses class 0.2 or 0.5 under IEC 61869-3, while protection uses 3P or 6P. Pick the class against the connected burden: the actual burden should sit between roughly 25% and 100% of the rated burden, otherwise the ratio and phase-angle error grow beyond the class limit.

When is a capacitive voltage transformer used instead of a wound PT?

Above about 72.5 kV the capacitor divider of a capacitive voltage transformer is cheaper than a wound electromagnetic unit and the same divider can feed a carrier-coupling device. Below that, wound inductive VTs are simpler and more accurate, so they dominate the 12 to 36 kV range.

Sources and Further Reading