High-Voltage Substation Metering Commissioning

On-site commissioning and accuracy verification of instrument transformers in a new high-voltage switchyard.

Instrument transformer under test at a high-voltage substation during commissioning
Utility Substation

A utility opened a new 110 kV switchyard and needed its revenue metering point commissioned to utility-accuracy before the first billing period. NAHU supplied the instrument transformers and our field engineers supervised the installation and accuracy verification on site.

The challenge

The switchyard mixed two feeder bays and one transformer bay, each needing its own metering and protection cores. Accuracy had to hold to 0.2S on the metering cores from 1% to 120% of rated current, and the whole point had to pass utility acceptance before energisation.

Our solution

We supplied dual-core current transformers (0.2S / 10P10) and class 0.2 voltage transformers with 100/√3 V secondaries, matched to the bay ratings. Our engineers then ran the full site test sequence: insulation resistance, ratio verification by primary injection, polarity checks and secondary wiring continuity end-to-end.

Products supplied

Indoor cast-resin current transformers and voltage transformers for the two feeder bays, dual-ratio outdoor current transformers for the transformer bay, plus terminal blocks, shorting links and documentation packs per bay.

Outcome

The metering point passed utility acceptance on the first attempt. Meter readings matched the reference instrument within the 0.2S band across the full load range, and the switchyard was energised and billed without rework.